Ingersoll-Rand X41 technical manual Installation

Page 6

SECTION 4 — INSTALLATION

It is recommended that installation and commissioning be carried out by an authorized and trained product supplier.

UNIT LOCATION

The X4I can be mounted on a wall using conventional bolts. The X4I can be located remotely from the compressors as long as it is within 330 feet (100 meters) of cable length. The X4I must also be located within 330 feet (100 meters) of the system pressure transducer.

Dimensions

SPECIFICATIONS

11.45” x 9.45” x 6.0”

Weight

291mm x 241mm x 152mm

14lb (6.4kg)

Mounting

Wall, 4 x screw fixings

Enclosure

IP65, NEMA 4

Supply

230Vac +/- 10%, 50 Hz

Power

115Vac +/- 10%, 60 Hz

50VA

Temperature 32°F to 115°F

Humidity

(0°C to 46°C)

0% to 95% RH

 

(non-condensing)

Ingersoll Rand Automation

Model X4I

COMPRESSOR CONTROL CABLE

7 Conductor Cable, 18 Gauge, Stranded, Earth Shielded

OR

Single Conductor Wire, 18 Gauge Stranded, Quantity (7)

In Grounded Conduit

No Greater Than 330FT (100M)

24VAC Control Voltage

Compressor #4 Control Cable

Local Disconnect (Breaker) Box

On/Off

 

 

 

 

 

 

Compressor #3 Control Cable

Fused for 50VA

 

Supply Voltage Cable

 

Compressor #2 Control Cable

Power Cable

 

Switch

 

 

 

 

 

 

 

Compressor #1 Control Cable

 

3 conductor (L, N, E)

 

 

 

 

 

 

(Sized in accordance with local

 

 

 

 

 

 

 

 

 

electrical and safety regulations).

Pressure Transducer Cable

Compressor

IR-PCB

 

 

Reference X4I Compressor

 

 

 

Interconnect and Application Guide

 

 

 

 

 

 

 

 

 

 

#1

 

 

 

For Connections Between The

PRESSURE TRANSDUCER CABLE

 

 

Compressor #1 Control Cable

 

 

Compressor And The IR-PCB

2 Conductor Cable, 18 Gauge Stranded

 

X4I X01 CONNECTOR

IR-PCB CONNECTOR

 

 

 

 

 

 

V1

 

V1

 

 

 

 

Earth Shielded

 

 

 

 

 

 

 

 

 

1

 

1

 

 

 

 

No Greater Than 330FT (100M)

 

 

2

 

2

 

 

 

 

24VDC Control Voltage

 

 

3

 

3

 

Compressor

IR-PCB

 

 

4

 

4

 

 

 

 

 

 

 

 

#2

 

X4I X05 CONNECTOR

PT CONNECTOR

 

 

5

 

5

 

 

 

 

 

6

 

6

Compressor #2 Control Cable

25

+VDC Pin #3

 

 

 

 

 

 

 

 

 

 

X4I X02 CONNECTOR

IR-PCB CONNECTOR

26

Signal Pin #1

 

 

 

 

 

V3

 

V1

 

Reference X4I Operations Manual for Pressure

 

 

 

 

 

7

 

1

 

Sensor Connection Details

 

 

 

 

 

8

 

2

 

 

 

 

 

 

9

 

3

 

 

 

 

 

 

 

 

10

 

4

 

 

PRESSURE TRANSDUCER

 

 

 

 

11

 

5

 

 

 

 

 

 

12

 

6

 

 

Compressor IR-PCB

RECEIVER

#3

 

 

Compressor #3 Control Cable

 

X4I X03 CONNECTOR

IR-PCB CONNECTOR

 

V3

 

V1

131

 

14

2

 

 

 

 

15

3

Compressor

IR-PCB

 

16

4

 

 

#4

 

 

17

5

 

 

DRIP LEG

18

6

Compressor #4 Control Cable

 

 

 

 

 

X4I X04 CONNECTOR

IR-PCB CONNECTOR

 

 

 

V4

 

V1

 

 

 

19

 

1

 

 

 

20

 

2

 

 

 

21

 

3

 

 

 

22

 

4

 

 

 

23

 

5

 

 

 

24

 

6

www.air.irco.com

6

X4I System Automation

 

Image 6
Contents More Than Air. Answers Table of Contents Intellisys S3 1of2 Intellisys S3 2of2 Introduction X4I System Automation Installation Power Supply Pressure Sensor Connection Input Functions Alarm Lamp Alarm Run ReadyOutput Functions C02 28 RS485 X06Specifications X4I Overview16 is a representation for After the conversion is completed Unigy Phase Unigy Phase 1 1of2Unigy Phase 1 2of2 Unigy Phase 2/3 Unigy Phase 2/3 1of2Unigy Phase 2/3 2of2 Nirvana 15 30KW 20 40HP Nirvana 15 30KW 20-40HP 1of2Nirvana 15 30KW 20-40HP Nirvana 15 30KW 20-40HP 2of2Page SSR Redeye SSR Redeye 1of3SSR Redeye FV SSR Redeye FV 2of3SSR Redeye SD SSR Redeye SD 3of3Page SE UP 1of2 0VAC 1M 110VACIntellisys SE UP Series SE UP 2of2 SE ESA 1of2 Intellisys SE ESA SeriesSE ESA 2of2 SE DSA 1of2 J5 34 33Intellisys SE DSA Contact Cooled SE DSA 2of2 Page P2 3 2 SG SSR 1of21Sb Intellisys SGSG SSR 2of2 SG Sierra SG Sierra 1of2SG Sierra 2of2 Page SSR UP5 11-22 SD SSR UP5 11-22 SD 1of2SSR UP5 11-22 SD 2of2 Relay Contact SSR UP5 22-37 SDSSR UP5 22-37 SD 1of2 Contact 110VACSSR UP5 22-37 SD 2of2 Restart TD Relay SSR UP6 15-30 FVSSR UP6 15-30 FV 1of2 Contact To TR Relay To M ContactSSR UP6 15-30 FV 2of2 SSR UP6 15-30 SD SSR UP6 15-30 SD 1of2Contact To TR Relay To 1M Contact To 2M Contact VAC SSR UP6 15-30 SD 2of2 Relay Relay Contact Contact SSR UP6 40-50 FVSSR UP6 40-50 FV 1of2 To TR Relay To 1M ContactSSR UP6 40-50 FV 2of2 SSR UP6 40-50 SD 1of2 C01 VFD/fixed Load Enable To TR RelaySSR UP6 40-50 SD Load/Unload To 1M ContactSSR UP6 40-50 SD 2of2 To CR Relay UP6 5-15 FV 1PH 60HzUP6 5-15 FV 1PH 60Hz 1of2 To HMUP6 5-15 FV 1PH 60Hz 2of2 UP6 5-15 FV 3PH 60Hz UP6 5-15 FV 3PH 60Hz 1of2UP6 5-15 FV 3PH 60Hz 2of2 UP6 5-15 SD 3PH 60Hz UP6 5-15 SD 3PH 60Hz 1of2110VAC To EDV To 1M/1S/2M Contacts To TD Relay VAC 1M UP6 5-15 SD 3PH 60Hz 2of2 UP6 5-15 FV 3PH 50Hz UP6 5-15 FV 3PH 50Hz 1of2To HM 110VAC HATSTo EDV KM1/KM2/KM3 Contacts To KM1 UP6 5-15 FV 3PH 50Hz 2of2 UP6 5-15 SD 3PH 50Hz UP6 5-15 SD 3PH 50Hz 1of2UP6 5-15 SD 3PH 50Hz 2of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 1of2SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 2of2 M37-50 M37-50 1of2M37-50 2of2 EP 20-30 ESP FV EP 20-30 ESP FV 1of2EP 20-30 ESP FV 2of2 EP 20-30 ESP SD EP 20-30 ESP SD 1of2Contact To 1TD Relay To 2M Contact VAC EP 20-30 ESP SD 2of2 Page Nirvana SGN/SGNe Nirvana SGN/SGNe 1of3Nirvana SGN/SGNe 2of3 Nirvana SGN/SGNe 3of3 SI1 Interface to Redeye, SE, SG Controllers SI1 Interface to Redeye, SE, SG ControllersRedeye X4I Interconnect To Ingersoll Rand Intellisys S3 X4I Interconnect To Ingersoll Rand Intellisys S3X04 Intellisys S3Intellisys S3 1of2 X02Intellisys S3 2of2 Page UP6RE 7.5-15 175, UP6RX 7.5-15 UP6RE 7.5-15 175, UP6RX 7.5-15 175 1of3110VAC To ETM UP6RE 7.5-15 175, UP6RX 7.5-15 175 2of3 UP6RE 7.5-15 175, UP6RX 7.5-15 175 3of3 To Customer Supplied External Neutral Models 2340, 2475, 2545, 7100, 15TModels 2340, 2475, 2545, 7100, 15T & 3000 10f3 External 110VAC Contact L2Models 2340, 2475, 2545, 7100, 15T & 3000 2of3 Models 2340, 2475, 2545, 7100, 15T & 3000 3of3 X4I Compressor #1 X01 Terminal Pressure