RUN INPUT

MAIN (LINE) CONTACTOR

0V

+V

The IR-PCB input common terminal must always be connected to the neutral, common or 0V line of the applied input voltage.

WARNING INPUT (OPTIONAL)

The IR-PCB is equipped with a warning input that can be used to detect warning conditions.

An alarm that stops the compressor, and/or prevents the compressor from running is determined from the “run” and “ready” inputs. Warning detection is optional and is not a requirement.

Alarm Lamp

ALARM RUN READY

C04

Run Signal Circuit

The RUN input will accept 12V to 250V AC (50/60Hz) only. DC cannot be used.

Do not connect a voltage greater than 250V to this input.

12V to 250Vac must be applied to the “run” terminals when the compressor motor is running.

+V

0V

This input can be connected to the control terminals A1 and A2 (coil) of the main starter contactor of the compressor. When the compressor control system energizes the main contactor, the IR-PCB will detect the voltage across the contactor coil terminals and signal the X4I that the compressor is running.

Alternatively, if the main contactor coil voltage is greater than 250Vac, a contactor auxiliary switch can be used to apply a suitable voltage to the “run” input terminals.

MAIN (LINE) CONTACTOR

+V

0V

 

+V

0V

 

AUXILIARY SWITCH

 

ALARM RUN READY

C04

Run Signal Circuit with Auxiliary Switch

In instances where a motor starter contactor is not available or accessible, any part of a compressor control circuit that is energized when the compressor is running can be monitored. For example: fan contactor or voltage signal to a remote starter.

Alarm Run Ready

C04

Warning Input Circuit

The warning input will accept 12V to 250V AC (50/60Hz) or DC.

Do not connect a voltage greater than 250Vac/DC to this input.

This input can be connected to the terminals of an alarm lamp or other accessible part of the control circuit that is energized when the compressor is in a warning condition.

If a warning condition is experienced the compressor warning lamp, or warning circuit, will energize. The IR- PCB will detect the voltage and signal the X4I that a warning has occurred. If the compressor has no accessible warning circuit, or this function is not required, the IR-PCB alarm terminals can be ignored.

The IR-PCB input common terminal must always be connected to the neutral, common or 0V line of the applied input voltage.

www.air.irco.com

10

X4I System Automation

 

Image 10
Contents More Than Air. Answers Table of Contents Intellisys S3 1of2 Intellisys S3 2of2 Introduction X4I System Automation Installation Power Supply Pressure Sensor Connection Input Functions Alarm Lamp Alarm Run ReadyOutput Functions C02 28 RS485 X06Specifications X4I Overview16 is a representation for After the conversion is completed Unigy Phase Unigy Phase 1 1of2Unigy Phase 1 2of2 Unigy Phase 2/3 Unigy Phase 2/3 1of2Unigy Phase 2/3 2of2 Nirvana 15 30KW 20 40HP Nirvana 15 30KW 20-40HP 1of2Nirvana 15 30KW 20-40HP Nirvana 15 30KW 20-40HP 2of2Page SSR Redeye SSR Redeye 1of3SSR Redeye FV SSR Redeye FV 2of3SSR Redeye SD SSR Redeye SD 3of3Page 0VAC 1M 110VAC SE UP 1of2Intellisys SE UP Series SE UP 2of2 SE ESA 1of2 Intellisys SE ESA SeriesSE ESA 2of2 J5 34 33 SE DSA 1of2Intellisys SE DSA Contact Cooled SE DSA 2of2 Page P2 3 2 SG SSR 1of21Sb Intellisys SGSG SSR 2of2 SG Sierra SG Sierra 1of2SG Sierra 2of2 Page SSR UP5 11-22 SD SSR UP5 11-22 SD 1of2SSR UP5 11-22 SD 2of2 Relay Contact SSR UP5 22-37 SDSSR UP5 22-37 SD 1of2 Contact 110VACSSR UP5 22-37 SD 2of2 Restart TD Relay SSR UP6 15-30 FVSSR UP6 15-30 FV 1of2 Contact To TR Relay To M ContactSSR UP6 15-30 FV 2of2 SSR UP6 15-30 SD 1of2 SSR UP6 15-30 SDContact To TR Relay To 1M Contact To 2M Contact VAC SSR UP6 15-30 SD 2of2 Relay Relay Contact Contact SSR UP6 40-50 FVSSR UP6 40-50 FV 1of2 To TR Relay To 1M ContactSSR UP6 40-50 FV 2of2 SSR UP6 40-50 SD 1of2 C01 VFD/fixed Load Enable To TR RelaySSR UP6 40-50 SD Load/Unload To 1M ContactSSR UP6 40-50 SD 2of2 To CR Relay UP6 5-15 FV 1PH 60HzUP6 5-15 FV 1PH 60Hz 1of2 To HMUP6 5-15 FV 1PH 60Hz 2of2 UP6 5-15 FV 3PH 60Hz UP6 5-15 FV 3PH 60Hz 1of2UP6 5-15 FV 3PH 60Hz 2of2 UP6 5-15 SD 3PH 60Hz 1of2 UP6 5-15 SD 3PH 60Hz110VAC To EDV To 1M/1S/2M Contacts To TD Relay VAC 1M UP6 5-15 SD 3PH 60Hz 2of2 UP6 5-15 FV 3PH 50Hz 1of2 UP6 5-15 FV 3PH 50HzTo HM 110VAC HATSTo EDV KM1/KM2/KM3 Contacts To KM1 UP6 5-15 FV 3PH 50Hz 2of2 UP6 5-15 SD 3PH 50Hz UP6 5-15 SD 3PH 50Hz 1of2UP6 5-15 SD 3PH 50Hz 2of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 1of2SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 2of2 M37-50 M37-50 1of2M37-50 2of2 EP 20-30 ESP FV EP 20-30 ESP FV 1of2EP 20-30 ESP FV 2of2 EP 20-30 ESP SD 1of2 EP 20-30 ESP SDContact To 1TD Relay To 2M Contact VAC EP 20-30 ESP SD 2of2 Page Nirvana SGN/SGNe Nirvana SGN/SGNe 1of3Nirvana SGN/SGNe 2of3 Nirvana SGN/SGNe 3of3 SI1 Interface to Redeye, SE, SG Controllers SI1 Interface to Redeye, SE, SG ControllersRedeye X4I Interconnect To Ingersoll Rand Intellisys S3 X4I Interconnect To Ingersoll Rand Intellisys S3X04 Intellisys S3Intellisys S3 1of2 X02Intellisys S3 2of2 Page UP6RE 7.5-15 175, UP6RX 7.5-15 175 1of3 UP6RE 7.5-15 175, UP6RX 7.5-15110VAC To ETM UP6RE 7.5-15 175, UP6RX 7.5-15 175 2of3 UP6RE 7.5-15 175, UP6RX 7.5-15 175 3of3 To Customer Supplied External Neutral Models 2340, 2475, 2545, 7100, 15TModels 2340, 2475, 2545, 7100, 15T & 3000 10f3 External 110VAC Contact L2Models 2340, 2475, 2545, 7100, 15T & 3000 2of3 Models 2340, 2475, 2545, 7100, 15T & 3000 3of3 X4I Compressor #1 X01 Terminal Pressure