Ingersoll-Rand X41 technical manual Input Functions

Page 9

Consult the air compressor manual or your air compressor supplier/specialist for details before installing the X4I.

Each air compressor must be equipped with an online/offline pressure regulation system capable of accepting a remote load/unload signal through a volt free switching contact or a single electro-mechanical pressure switch.

The IR-PCB accepts a 12V to 250V input voltage detection system and utilizes universal relay contact control outputs (250V “CE” / 115V “UL” @ 5A maximum) integrated directly into the circuits of an air compressor. The IR-PCB avoids the need for additional relays or remote inputs. The IR-PCB also acts as an electrical barrier between the compressor and the X4I providing protection and voltage isolation.

Consult the X4I Interconnect and Application Guide prior to the installation of the X4I and the IR-PCB to the air compressor.

INPUT FUNCTIONS

The IR-PCB is fitted with a six-pin terminal, C04, for compressor monitoring. The IR-PCB uses two inputs, Ready and Run, to determine compressor status. An alarm input can be used if compressor warning indication is available and required. The alarm input is optional and is not necessary for system operation.

READY INPUT

The ‘Ready’ connection is intended to indicate that the compressor is in a “started” state, has no alarm condition that has shut down the compressor, and is ready to respond to X4I regulation without manual intervention.

READY LAMP

0V

+V

ALARM RUN READY

C04

Typical Ready Input Wiring

The READY input will accept 12V to 250V ac (50/60Hz) or dc.

Do not connect a voltage greater than 250Vac/dc to this input.

This input must be connected to a circuit of the compressor control system that will be energized when

the compressor is in a started (standby or running) condition. For example, locate the circuit across the ready or operating lamp as shown.

The voltage to this input must de-energize when the compressor is stopped and unavailable to produce air upon a load signal, or the emergency stop button is pressed, or when the compressor experiences a fault that prevents the compressor from running.

When the compressor ready lamp or other control circuit is energized, the IR-PCB will detect the voltage and signal the X4I that the compressor is ready and available to load and produce air when a load request signal is given.

The IR-PCB common input terminal must always be connected to the neutral, common or 0V line of the applied input voltage.

READY INPUT, ALTERNATIVE CONNECTION METHOD

In instances where a convenient voltage signal for a compressor ready condition is not available, the “ready” input can be connected directly to a constant compressor control voltage (12V to 250Vac or dc). This will signal the X4I that the compressor is ready and available at all times when power is applied to the compressor. The X4I has a built-in function to determine when a compressor is not responding, or is in a shutdown condition, even if the “ready” signal says otherwise. If the X4I requests a compressor to run/load, but fails to detect a RUN signal within 60 seconds, the X4I will regard the compressor as “not ready” and indicate the compressor as not available. If a RUN signal is reacquired at any time, the X4I will automatically reset the compressor “not ready” condition and re-establish control.

+Vac

F1

0Vac

READY

Alternative Ready Signal Connection

Never connect the “Ready” input positive voltage connection directly to the output of a control system transformer. Always connect after a fuse or circuit breaker.

If a normally closed contact of an emergency stop button is included in the compressor power supply circuit, connect after the emergency stop button contacts. This will instantly indicate a compressor “not ready” condition if the emergency stop button is activated.

www.air.irco.com

9

X4I System Automation

 

Image 9
Contents More Than Air. Answers Table of Contents Intellisys S3 1of2 Intellisys S3 2of2 Introduction X4I System Automation Installation Power Supply Pressure Sensor Connection Input Functions Alarm Run Ready Alarm LampOutput Functions C02 X06 28 RS485X4I Overview Specifications16 is a representation for After the conversion is completed Unigy Phase 1 1of2 Unigy PhaseUnigy Phase 1 2of2 Unigy Phase 2/3 1of2 Unigy Phase 2/3Unigy Phase 2/3 2of2 Nirvana 15 30KW 20-40HP 1of2 Nirvana 15 30KW 20 40HPNirvana 15 30KW 20-40HP 2of2 Nirvana 15 30KW 20-40HPPage SSR Redeye 1of3 SSR RedeyeSSR Redeye FV 2of3 SSR Redeye FVSSR Redeye SD 3of3 SSR Redeye SDPage SE UP 1of2 0VAC 1M 110VACIntellisys SE UP Series SE UP 2of2 Intellisys SE ESA Series SE ESA 1of2SE ESA 2of2 SE DSA 1of2 J5 34 33Intellisys SE DSA Contact Cooled SE DSA 2of2 Page 1Sb SG SSR 1of2P2 3 2 Intellisys SGSG SSR 2of2 SG Sierra 1of2 SG SierraSG Sierra 2of2 Page SSR UP5 11-22 SD 1of2 SSR UP5 11-22 SDSSR UP5 11-22 SD 2of2 SSR UP5 22-37 SD 1of2 SSR UP5 22-37 SDRelay Contact Contact 110VACSSR UP5 22-37 SD 2of2 SSR UP6 15-30 FV 1of2 SSR UP6 15-30 FVRestart TD Relay Contact To TR Relay To M ContactSSR UP6 15-30 FV 2of2 SSR UP6 15-30 SD SSR UP6 15-30 SD 1of2Contact To TR Relay To 1M Contact To 2M Contact VAC SSR UP6 15-30 SD 2of2 SSR UP6 40-50 FV 1of2 SSR UP6 40-50 FVRelay Relay Contact Contact To TR Relay To 1M ContactSSR UP6 40-50 FV 2of2 SSR UP6 40-50 SD C01 VFD/fixed Load Enable To TR RelaySSR UP6 40-50 SD 1of2 Load/Unload To 1M ContactSSR UP6 40-50 SD 2of2 UP6 5-15 FV 1PH 60Hz 1of2 UP6 5-15 FV 1PH 60HzTo CR Relay To HMUP6 5-15 FV 1PH 60Hz 2of2 UP6 5-15 FV 3PH 60Hz 1of2 UP6 5-15 FV 3PH 60HzUP6 5-15 FV 3PH 60Hz 2of2 UP6 5-15 SD 3PH 60Hz UP6 5-15 SD 3PH 60Hz 1of2110VAC To EDV To 1M/1S/2M Contacts To TD Relay VAC 1M UP6 5-15 SD 3PH 60Hz 2of2 UP6 5-15 FV 3PH 50Hz UP6 5-15 FV 3PH 50Hz 1of2To HM 110VAC HATSTo EDV KM1/KM2/KM3 Contacts To KM1 UP6 5-15 FV 3PH 50Hz 2of2 UP6 5-15 SD 3PH 50Hz 1of2 UP6 5-15 SD 3PH 50HzUP6 5-15 SD 3PH 50Hz 2of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 1of2 SSR M15-22c 20-30HP XF EP HP HXP 50-60HzSSR M15-22c 20-30HP XF EP HP HXP 50-60Hz 2of2 M37-50 1of2 M37-50M37-50 2of2 EP 20-30 ESP FV 1of2 EP 20-30 ESP FVEP 20-30 ESP FV 2of2 EP 20-30 ESP SD EP 20-30 ESP SD 1of2Contact To 1TD Relay To 2M Contact VAC EP 20-30 ESP SD 2of2 Page Nirvana SGN/SGNe 1of3 Nirvana SGN/SGNeNirvana SGN/SGNe 2of3 Nirvana SGN/SGNe 3of3 SI1 Interface to Redeye, SE, SG Controllers SI1 Interface to Redeye, SE, SG ControllersRedeye X4I Interconnect To Ingersoll Rand Intellisys S3 X4I Interconnect To Ingersoll Rand Intellisys S3Intellisys S3 1of2 Intellisys S3X04 X02Intellisys S3 2of2 Page UP6RE 7.5-15 175, UP6RX 7.5-15 UP6RE 7.5-15 175, UP6RX 7.5-15 175 1of3110VAC To ETM UP6RE 7.5-15 175, UP6RX 7.5-15 175 2of3 UP6RE 7.5-15 175, UP6RX 7.5-15 175 3of3 Models 2340, 2475, 2545, 7100, 15T & 3000 10f3 Models 2340, 2475, 2545, 7100, 15TTo Customer Supplied External Neutral External 110VAC Contact L2Models 2340, 2475, 2545, 7100, 15T & 3000 2of3 Models 2340, 2475, 2545, 7100, 15T & 3000 3of3 X4I Compressor #1 X01 Terminal Pressure