Thermo Products PGT11-125 Furnace Checkout Procedure, IV. Installers Instructions to User

Page 31

All installations and services must be performed by qualified service personnel.

ORIFICE CHART

FURNACE

L.P.

NAT.

MODEL NO.

 

 

 

 

 

PGT5-100

.113 OR #33 DMS

.196 OR #9 DMS

PGT11-125

.1285 OR #30 DMS

.213 OR #3 DMS

PGT16-160

.144 OR #44 DMS

.238 OR B DMS

PGL20-180

.213 OR #3 DMS

.277 OR J DMS

PGL33-250

.265 OR 17/64 DMS

.332 OR Q DMS

PGL37-312

.297 OR 19/64 DMS

.390 OR 25/64 DMS

PGL39-400

.332 OR Q DMS

.468 OR 15/32 DMS

 

 

 

D. FURNACE CHECKOUT PROCEDURE

Before any system of gas piping is finally put into service, it shall be carefully tested to assure that it is gas tight as indicated in Gas Piping Section of Burner Manual.

NOTICE: All controls on the unit should be checked for proper functioning prior to the qualified service personnel leaving the job site. Specifically the following should be checked:

With furnace in normal heating operation, check to make certain blower will start and stop automatically under control of fan switch.

a. Check safety limit control as follows:

1.

Shut off incoming power.

2.

Block return air opening or remove blower belt on belt drive or unplug blower at terminal strip on direct drive.

3.Restore power to furnace.

4.Set thermostat above room temperature calling for heat.

5. When temperatures are reached in furnace at limit control setting with blower out of operation, burner should be shut off.

6. Shut off electrical power, remove blockage and restore power.

b. Make certain thermostat will automatically start and stop the burner and fan control operates blower properly.

IV. INSTALLER'S INSTRUCTIONS TO USER:

After completing the installation, the installer shall inform and demonstrate to the homeowner: 1. The Sequence of Operations. 2. Operating Instructions and Routine Maintenance. 3. Review label reproductions at beginning of this manual.

29

Image 31
Contents Models Table of Contents Section Page Page Construction Materials II. General InstallationGeneral Instructions Codes and ClearancesFurnace Location and Combustion AIR Minimum Clearances to Combustible MaterialsVenting MAKE-UP AIRExample Condensing in the Chimney Vent DampersGeneral GAS Piping Replacing AN Existing Furnace from a Common VentInstallation of Natural GAS Piping Black Pipe Size for Natural GAS Installation of Liquified Petroleum GAS LP PipingTypical Piping for TWO Stage Regulation Copper Tubing Size for Liquified Petroleum Gases Burner InstallationTOP View Burner Insertion Illustration PGL Side View Burner Insertion Illustration PGT TWO Piece Mounting PlateHorizontal Furnace Positions Midco RE32 Burner AdjustmentGAS Natural GASDraftoverfire Requirements and Sizing of Duct Work Duct Sizes for HOMES, Quiet Offices or Similar Installations Duct WORK/AIR Conditioning PGT Horizontal Units PGL Lowboy FiltersFAN and Limit Position and Location FAN & Limit Location with H-COIL WiringLatest Edition Page Page Page Page Latest Edition Burner Combustion Adjustment of BTU Input RateII. Starting the Unit A. Initial Start UP Operating InstructionsPage IV. Installers Instructions to User Furnace Checkout ProcedureCleaning Heat Exchanger Dealer Maintenance ElectricalVI. Troubleshooting VII. Replacement Parts Page Page

PGL33-250, PGL39-400, PGL37-312, PGT11-125, PGL20-180 specifications

Thermo Products offers a robust lineup of heating devices designed to meet diverse industrial requirements. Among these, models PGL33-250, PGT5-100, PGL39-400, PGL20-180, and PGT11-125 stand out for their innovative technology and exceptional performance.

The PGL33-250 is particularly noted for its high output, making it an ideal choice for larger industrial applications. With an advanced heating element, it ensures rapid temperature increases while maintaining consistent heat distribution. This model is equipped with smart control systems that allow for remote monitoring and adjustments, enhancing operational efficiency.

Next in the lineup is the PGT5-100, a compact yet powerful solution perfectly suited for smaller spaces where efficiency is key. It features an energy-efficient design that reduces operational costs without compromising on performance. The PGT5-100 includes built-in overheat protection, ensuring safe operation even in demanding environments.

The PGL39-400 takes versatility to the next level. Its dual-mode heating capabilities allow users to switch between high-efficiency and high-output settings, catering to varying workload requirements. The advanced insulation technology employed in this model minimizes heat loss, thereby maximizing energy efficiency and reducing environmental impact.

In the mid-range category, the PGL20-180 offers robust performance with a focus on user-friendly features. This model includes a sophisticated digital control panel, providing real-time temperature readings and programmable settings. Its lightweight design makes installation straightforward, while its durability ensures long-term reliability.

Finally, the PGT11-125 stands out for its innovative thermal regulation system. This system adapts the heating output based on real-time environmental conditions, ensuring optimal performance at all times. The PGT11-125 is also constructed using high-quality materials that resist corrosion and wear, making it suitable for various industrial applications.

Collectively, these models from Thermo Products exemplify the company's commitment to quality and technological advancement. With features such as smart controls, advanced insulation, and dual-mode operation, these heating solutions not only offer efficient performance but also contribute to energy savings and a reduced carbon footprint. As industries continue to evolve, Thermo Products remains at the forefront, providing reliable and innovative heating solutions for all industrial needs.