HP R7000 manual Battery specifications, Average battery runtime, Minimum battery runtime

Page 52

Feature

Specification

 

 

Voltage wave shape

Sine wave; 5% THD with typical PFC load

Surge suppression

High-energy 6500 A peak

Noise filtering

MOVs and line filter for normal and common mode

 

use

Battery specifications

Feature

Specification

 

 

Type

Each model contains maintenance-free, sealed, valve

 

regulated lead-acid batteries with an 8-year minimum float

 

service life at 25°C (77°F).

 

 

Voltage

The battery modules have a battery string voltage of 216 V.

Charging

Complete charge takes no more than 48 hours.

 

Approximately 3 hours to 80 percent capacity at default

 

nominal utility voltage and no load.

 

 

Average battery runtime

Average battery runtimes are approximate and vary depending on connected equipment, configuration, battery age, temperature, and so on. These estimates are based on the batteries at beginning of life.

Load %

Estimated battery

 

Runtime with one

 

Runtime with four

 

 

runtime (minutes)

 

ERM (minutes)

 

ERMs (minutes)

 

 

 

 

 

 

 

 

 

NA/JPN

INTL

NA/JPN

INTL

NA/JPN

INTL

 

 

 

 

 

 

 

20

52

62

98

117

301

359

50

13

15

33

37

103

115

80

6

7

18

21

57

66

100

4

5

13

15

39

50

Minimum battery runtime

Minimum battery runtimes are at beginning of life.

Load %

Internal battery runtime

 

Runtime with one

 

Runtime with four

 

 

(minutes)

 

ERM (minutes)

 

ERMs (minutes)

 

 

 

 

 

 

 

 

 

NA/JPN

INTL

NA/JPN

INTL

NA/JPN

INTL

 

 

 

 

 

 

 

20

42

50

80

95

240

300

50

10

12

27

30

80

95

80

5

6

16

18

52

60

100

3

4

11

13

35

45

Specifications 52

Image 52
Contents HP UPS R7000 User Guide Part Number February EditionPage Contents Maintenance Power Protector softwareSpares Important safety information UPS R7000 featuresOverview UPS R7000 overviewComponent identification UPS front panelUPS front panel controls DescriptionUPS rear panel Repo port ERM rear panel Installation and configuration PrecautionsPreparing to install the hardware Tools and materialsInstalling the mounting rails Selecting a siteReadying the equipment Hex nuts Cage nuts Cage nut-fitting toolInstallation and configuration Installation and configuration Installation and configuration Preparing the rails for integrated shipping Installing the UPS Connecting the battery leadsInstallation and configuration Configuring a USB to serial converter Reassigning the USB COM ports Installation and configuration Installation and configuration Connecting the ground bonding cable Connecting the network cableConnecting the UPS to utility power Connecting devices to the UPSStarting power to the load Configuring the UPS Network ModuleConnecting the configuration cable Be sure that the UPS is powered on Configuring the UPS Network Module network settingsLaunching a terminal emulation program Accessing the web interface Installing the ERM Configuring the UPS Network Module settingsAttaching the ERM front bezel Connecting the ERM to the UPS Charging the ERM batteriesStandby mode Operate modeAuto-Bypass mode UPS operationsChanging the language Configuring the UPSChanging display functions After connecting the Repo port on Verifying the Repo port connectionPowering down the UPS Power management Power Protector softwarePower management Maintenance Important battery safety information Replacing the batteriesBattery care and storage guidelines UPS battery replacement procedureMaintenance Replacing the UPS Disconnect the battery leads Remove the UPS battery bracket Replacing the ERM Updating the UPS firmwareTroubleshooting Alarm troubleshootingAlarm number Alarm name Alarm description Alarm type Battery connection condition General alarm conditionSilencing an audible alarm Bypass is out of rangeInternal UPS fault condition Low battery shutdownsInput voltage is out of range Insufficient warning of low batteriesSite wiring condition UPS does not provide the expected backup timeUPS frequently switches between utility and battery power Repo conditionUPS is in Auto-Bypass mode UPS is on batteryUtility power condition UPS is on bypassSpecifications UPS physical specificationsERM physical specifications UPS input specificationsPower protection specifications Voltage specificationsOutput tolerance specifications Output feature specificationsAverage battery runtime Battery specificationsMinimum battery runtime Environmental specifications Repo port specificationsUPS spare parts list SparesOrdering spares Hardware optionsSafety and regulatory compliance Warranty information Limited warranty$250,000 Computer Load Protection Guarantee Regulatory informationPre-Failure Battery Warranty Recommended duration of usePreventing electrostatic discharge Electrostatic dischargeGrounding methods to prevent electrostatic discharge Before you contact HP Support and other resourcesHP contact information Acronyms and abbreviations Documentation feedback Index Index