Alarm number | Alarm name | Alarm description | Alarm type |
|
|
|
|
59 | Utility Not Present | The utility level has fallen below the Utility Not Present | Notice |
|
| threshold. |
|
68 | Battery DC Over Voltage | Battery voltage levels have exceeded the maximum | Alarm |
|
| allowable limits. |
|
94 | To Bypass Command | A request to transfer to Manual Bypass Mode | Event |
|
| received from software. |
|
95 | From Bypass Command | A request to transfer to Operate Mode is received | Event |
|
| from software. |
|
143 | On Manual Bypass | The UPS is manually commanded to switch to bypass | Notice |
|
| and will remain in bypass until commanded out of |
|
|
| bypass. |
|
149 | Service Battery | A faulted battery string is detected, and the battery | Alarm |
|
| charger has been disabled until it is replaced. |
|
159 | Output Overload Level 2 | Load levels are greater than a level 2 Overload | Alarm |
|
| condition and less than a level 3 Overload condition. |
|
162 | Output Overload Level 3 | Load levels are greater than a level 3 threshold. | Alarm |
168 | UPS On Battery | The UPS is operating from batteries. | Notice |
169 | UPS On Bypass | The UPS is operating from bypass. | Notice |
170 | UPS Off | The UPS is in Standby mode or Fault mode. | Event |
172 | UPS On Command | Indicates a manually requested transition from | Event |
|
| Standby to Operate. This event is not triggered for |
|
|
| auto restarts. |
|
173 | UPS Off Command | A UPS OFF command was received from remote S/W | Event |
|
| and causes the UPS to open up all output relays and |
|
|
| shed the load. |
|
174 | Battery Shutdown | The UPS has shut down due to running on battery for | Alarm |
|
| a long enough time to exhaust the battery capacity. |
|
181 | UPS Control Power ON | The UPS is powered up. | Event |
191 | Battery Test Failed | A weak battery string is detected during the battery | Notice |
|
| test. |
|
194 | Site Wiring Problem | The difference between ground and neutral voltage is | Alarm |
|
| less than 30 V. |
|
199 | Battery Disconnected | Battery voltage is lower than the batteries | Alarm |
|
| disconnected level defined for this UPS. If ERMs are |
|
|
| attached, this alarm does not trigger unless the ERMs |
|
|
| are also disconnected, since they are paralleled with |
|
|
| the battery bus. |
|
237 | UPS System Normal | The UPS has started or returned to its normal | Event |
|
| operating mode of operation and no alarms are |
|
|
| active. |
|
1600 | ABM State Charging | The status of ABM charge mode is constant current | Event |
|
| charging. |
|
1601 | ABM State Floating | The status of ABM charge mode is floating. | Event |
1602 | ABM State Resting | The status of ABM charge mode is resting. | Event |
1603 | ABM State OFF | The status of ABM charge mode is OFF or disabled. | Event |
1999 | Clock set done | The UPS real time clock setting has been adjusted. | Event |
Troubleshooting 45