HP R7000 manual Launching a terminal emulation program, Be sure that the UPS is powered on

Page 26

2.Connect the RJ-45 connector on the DB-9 to RJ-45 cable to the Settings/AUX connector on the UPS Network Module.

This connection is used to access and configure the UPS Network Module network settings locally through a terminal emulation program.

Launching a terminal emulation program

NOTE: HyperTerminal is the serial communication program provided with Microsoft® Windows® and is used in this section as an example for setting up a terminal emulation session. If you are using another utility, the steps might be different.

1.Be sure that the UPS is powered on.

2.On the host computer, click Start, and select Programs>Accessories>Communications>HyperTerminal. The Connection Description window appears.

3.Enter a description, select an icon for the connection, and then click OK. The Connect To window appears.

4.Select the serial connector on the host computer to which the DB-9 to RJ-45 adapter is attached, and then click OK. The COM Properties window appears.

5.Select the following parameter values, and then click OK. o Bits per second—9600

o Data bits—8 o Parity—None o Stop bits—1

o Flow control—None

Configuring the UPS Network Module network settings

On the terminal emulation session screen running on the host computer:

1.Press any key. The initialization process completes, and then you are prompted to enter the password.

Installation and configuration 26

Image 26
Contents HP UPS R7000 User Guide Part Number February EditionPage Contents Maintenance Power Protector softwareSpares Overview Important safety informationUPS R7000 features UPS R7000 overviewUPS front panel controls Component identificationUPS front panel DescriptionUPS rear panel Repo port ERM rear panel Preparing to install the hardware Installation and configurationPrecautions Tools and materialsReadying the equipment Installing the mounting railsSelecting a site Hex nuts Cage nuts Cage nut-fitting toolInstallation and configuration Installation and configuration Installation and configuration Preparing the rails for integrated shipping Installing the UPS Connecting the battery leadsInstallation and configuration Configuring a USB to serial converter Reassigning the USB COM ports Installation and configuration Installation and configuration Connecting the ground bonding cable Connecting the network cableConnecting the UPS to utility power Connecting devices to the UPSConnecting the configuration cable Configuring the UPS Network ModuleStarting power to the load Launching a terminal emulation program Configuring the UPS Network Module network settingsBe sure that the UPS is powered on Accessing the web interface Installing the ERM Configuring the UPS Network Module settingsAttaching the ERM front bezel Connecting the ERM to the UPS Charging the ERM batteriesAuto-Bypass mode Standby modeOperate mode UPS operationsChanging display functions Configuring the UPSChanging the language After connecting the Repo port on Verifying the Repo port connectionPowering down the UPS Power management Power Protector softwarePower management Maintenance Important battery safety information Replacing the batteriesBattery care and storage guidelines UPS battery replacement procedureMaintenance Replacing the UPS Disconnect the battery leads Remove the UPS battery bracket Replacing the ERM Updating the UPS firmwareTroubleshooting Alarm troubleshootingAlarm number Alarm name Alarm description Alarm type Silencing an audible alarm Battery connection conditionGeneral alarm condition Bypass is out of rangeInput voltage is out of range Internal UPS fault conditionLow battery shutdowns Insufficient warning of low batteriesUPS frequently switches between utility and battery power Site wiring conditionUPS does not provide the expected backup time Repo conditionUtility power condition UPS is in Auto-Bypass modeUPS is on battery UPS is on bypassERM physical specifications SpecificationsUPS physical specifications UPS input specificationsOutput tolerance specifications Power protection specificationsVoltage specifications Output feature specificationsMinimum battery runtime Battery specificationsAverage battery runtime Environmental specifications Repo port specificationsOrdering spares UPS spare parts listSpares Hardware options$250,000 Computer Load Protection Guarantee Safety and regulatory complianceWarranty information Limited warranty Regulatory informationPre-Failure Battery Warranty Recommended duration of useGrounding methods to prevent electrostatic discharge Electrostatic dischargePreventing electrostatic discharge HP contact information Support and other resourcesBefore you contact HP Acronyms and abbreviations Documentation feedback Index Index