HP R7000 manual Repo port

Page 9

Item

13

14

15

16

17

Description

Load segment 2 (3) C19 receptacles

Load segment 2 circuit breaker (controls the C19 receptacles, but does not control the large output receptacle)

Large output NEMA L6-30R receptacle (NA/JPN) or IEC-320-C19A receptacle (INTL) associated with load segment 2

ERM communication port

ERM connector for the large plug on the split ERM cable

REPO port

The UPS includes an isolated REPO port. When properly wired, the REPO feature enables the power at the UPS output receptacles to be switched off from a remote location. To use this feature, the REPO port must be connected to a remote, normally open switch (not supplied). The REPO switch is used in conjunction with a main disconnect device that removes the AC source from the input of the UPS. When the switch is closed:

The REPO feature immediately powers down protected devices and does not utilize the orderly shutdown procedure initiated by power management software.

The REPO feature shuts down UPS units operating under either utility or battery power.

NOTE: If the UPS was operating on battery power when the remote switch was closed, no power is available to the load devices until utility power is restored and the UPS has been manually powered up.

To restore power to the load devices after the REPO feature is activated, press the On button after the AC source is reconnected to the UPS.

IMPORTANT: Pressing and holding the On button without utility present normally initiates a battery start and the UPS assumes the load. However, if the On button is pressed and a REPO is detected, battery start is inhibited and the UPS is not able to assume the load. The electronics module fan spins and the General Alarm LED and an audible alarm are active as long as the On button is held.

To power down the entire network in the event of an emergency, the REPO ports of multiple UPS units can be connected to a single switch.

Component identification 9

Image 9
Contents Part Number February Edition HP UPS R7000 User GuidePage Contents Power Protector software MaintenanceSpares UPS R7000 features Important safety informationOverview UPS R7000 overviewUPS front panel Component identificationUPS front panel controls DescriptionUPS rear panel Repo port ERM rear panel Precautions Installation and configurationPreparing to install the hardware Tools and materialsSelecting a site Installing the mounting railsReadying the equipment Hex nuts Cage nuts Cage nut-fitting toolInstallation and configuration Installation and configuration Installation and configuration Preparing the rails for integrated shipping Connecting the battery leads Installing the UPSInstallation and configuration Configuring a USB to serial converter Reassigning the USB COM ports Installation and configuration Installation and configuration Connecting the network cable Connecting the ground bonding cableConnecting devices to the UPS Connecting the UPS to utility powerConfiguring the UPS Network Module Starting power to the loadConnecting the configuration cable Configuring the UPS Network Module network settings Be sure that the UPS is powered onLaunching a terminal emulation program Accessing the web interface Configuring the UPS Network Module settings Installing the ERMAttaching the ERM front bezel Charging the ERM batteries Connecting the ERM to the UPSOperate mode Standby modeAuto-Bypass mode UPS operationsConfiguring the UPS Changing the languageChanging display functions Verifying the Repo port connection After connecting the Repo port onPowering down the UPS Power Protector software Power managementPower management Maintenance Replacing the batteries Important battery safety informationUPS battery replacement procedure Battery care and storage guidelinesMaintenance Replacing the UPS Disconnect the battery leads Remove the UPS battery bracket Updating the UPS firmware Replacing the ERMAlarm troubleshooting TroubleshootingAlarm number Alarm name Alarm description Alarm type General alarm condition Battery connection conditionSilencing an audible alarm Bypass is out of rangeLow battery shutdowns Internal UPS fault conditionInput voltage is out of range Insufficient warning of low batteriesUPS does not provide the expected backup time Site wiring conditionUPS frequently switches between utility and battery power Repo conditionUPS is on battery UPS is in Auto-Bypass modeUtility power condition UPS is on bypassUPS physical specifications SpecificationsERM physical specifications UPS input specificationsVoltage specifications Power protection specificationsOutput tolerance specifications Output feature specificationsBattery specifications Average battery runtimeMinimum battery runtime Repo port specifications Environmental specificationsSpares UPS spare parts listOrdering spares Hardware optionsWarranty information Limited warranty Safety and regulatory compliance$250,000 Computer Load Protection Guarantee Regulatory informationRecommended duration of use Pre-Failure Battery WarrantyElectrostatic discharge Preventing electrostatic dischargeGrounding methods to prevent electrostatic discharge Support and other resources Before you contact HPHP contact information Acronyms and abbreviations Documentation feedback Index Index