HP Modular Cooling System manual Sensors

Page 47

Indicators

Meaning

 

 

Sensors

HEX1, HEX2, or HEX3 sensors (this is the water to air heat exchanger unit

 

temperature of the intake to the servers)

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Remove the fan unit.

2.Remove the HEX unit.

3.Reinstall the same HEX unit.

4.Reinstall the same fan unit.

If the warning message does not clear after the module is reseated, replace the HEX unit with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance and service information (on page 63)."

HEX temperature out failed (Server Exhaust Temperature failed)

Indicators

Meaning

 

 

Actual operator display alarm

FAN1, FAN2, or FAN3 Temp. Out Failed

message

 

 

 

Actual web interface alarm

Top Fan Exhaust Air Temperature Sensor from Server Failed

message

 

 

 

Condition

Temperature reading is beyond limit (possible open circuit)

 

 

Sensors

FAN1, FAN2, or FAN3 sensors (this is the fan unit temperature of the

 

exhaust from the servers)

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Remove the fan unit.

2.Reinstall the same fan unit.

If the warning message does not clear after the module is reseated, replace the fan unit with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance and service information (on page 63)."

Air temperature sensor failed

Indicators

Meaning

 

 

Actual operator display alarm

Air Temp. Sens Failed

message

 

 

 

Actual web interface alarm

Air Temperature Sensor Failed

message

 

 

 

Condition

Single air temperature sensor is significantly different from the others

 

 

Sensors

Air temperature sensors

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Operator display 47

Image 47
Contents Part Number February 2007 Second Edition HP Modular Cooling System User GuideAudience assumptions Contents Replaceable parts and maintenance and service information Introduction OverviewReference Site preparation Configuration factorsOptimum environment and site requirements MCS kit contents InstallationRequired tools Rack hardware kit contentsInstalling the MCS unit Installation Installation Installation Installation Installation Powering up and configuring the unit Installation Installation Installation Installation Installation Enter 4 Activate Actual Values Return to the Main Menu Network Configuration screenInstallation Installation Configuring the IP address through the web interface Installation Installation Installation Installation Management module overview Management moduleManagement module components Reference Description Logging in through the terminal emulation programWeb interface requirements Accessing the management module through the web interfaceSoftware Browser Logging in through the web interfaceTo add an external alarm relay Connecting an external alarm relayManagement module HP Modular Cooling System Utility overview Serial interfaceOption number Submenu Description Main menuMenu Network Configuration submenu IP Configuration submenu Change Passwords submenu Info Factory Default submenu Configuring HyperTerminal Configuring Minicom Operator display components Operator displayOperator display overview Indicators Meaning Sensors Sensors Water group sensor Snmp notification Type of message Solution Solution Uneven heat load Indicators Meaning Page Indicators Meaning Has been exceeded or the water flow is less than 2 l/min Indicators Meaning Adjusting the operator display Operator display Automatic Door Release Kit Overview Automatic Door Release KitQuestion Answer Frequently asked questionsHP Modular Cooling System frequently asked questions Port x set out lf=strip Issue Resolution TroubleshootingHP Modular Cooling System troubleshooting Specification SpecificationsMCS specifications Thermal and air flow performance HP 10642 G2 Rack specificationsEnvironmental specifications Features SpecificationsReplaceable parts Replaceable parts and maintenance and service informationMaintenance and service Air and water heat exchanger maintenanceAcceptable water quality range Water quality requirements and specificationsCooling water composition guidelines CSB Hydrological data Acceptable rangeFrost damage Monitoring the quality of cooling solutionsAdjust the MCS leveling feet so that the unit is level Leveling requirementsCondensation management Customer Self Repair Technical supportBefore you contact HP HP contact informationRéparation par le client CSR Riparazione da parte del cliente Reparaciones del propio cliente Reparo feito pelo cliente Technical support Technical support Technical support Modifications Regulatory compliance noticesRegulatory compliance identification numbers Federal Communications Commission noticeEuropean Union regulatory notice CablesCanadian notice Regulatory compliance notices Taiwan battery recycling notice Battery replacement noticePower cord statement for Japan Acronyms and abbreviations Simple Network Management Protocol Power distribution unitSystems Insight Manager Simple Mail Transfer ProtocolIndex Index