HP Modular Cooling System manual Indicators Meaning

Page 54

Indicators

Meaning

 

 

Actual operator display alarm

Excessive Moisture

message

 

 

 

Actual web interface alarm

The condensation pump has exceeded x cycles

message

 

 

 

Condition

The water level has exceeded the permissible level of the condensation

 

pump sensor

 

 

Modules or sensors

Condensation pump sensor

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Look for leaks or determine if condensation is the cause.

2.If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Cycles Warning Threshold field.

IMPORTANT: Use caution when entering temperatures in the Condensation Pump Threshold fields. Be sure to determine the proper default settings to prevent false alarms, without masking problems with the MCS.

Default settings will vary, depending on the humidity level of your data center and the heat load generated by the equipment in the MCS.

The condensation pump has run more than x seconds

Indicators

Meaning

 

 

Actual operator display

Excessive Moisture

alarm message

 

 

 

Actual web interface

The condensation pump has run more than x seconds

alarm message

 

 

 

Condition

The water level has exceeded the permissible level of the condensation pump sensor.

 

 

Modules or sensors

Condensation pump sensor

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Look for leaks or determine if condensation is the cause.

2.If no leaks are found, adjust the temperature in the Excessive Moisture: Condensation Pump Running Time Warning Threshold field.

IMPORTANT: Use caution when entering temperatures in the Condensation Pump Threshold fields. Be sure to determine the proper default settings to prevent false alarms, without masking problems with the MCS.

Default settings will vary, depending on the humidity level of your data center and the heat load generated by the equipment in the MCS.

Operator display 54

Image 54
Contents HP Modular Cooling System User Guide Part Number February 2007 Second EditionAudience assumptions Contents Replaceable parts and maintenance and service information Overview IntroductionReference Configuration factors Optimum environment and site requirementsSite preparation Installation MCS kit contentsRack hardware kit contents Required toolsInstalling the MCS unit Installation Installation Installation Installation Installation Powering up and configuring the unit Installation Installation Installation Installation Installation Return to the Main Menu Network Configuration screen Enter 4 Activate Actual ValuesInstallation Installation Configuring the IP address through the web interface Installation Installation Installation Installation Management module Management module overviewManagement module components Logging in through the terminal emulation program Reference DescriptionAccessing the management module through the web interface Web interface requirementsLogging in through the web interface Software BrowserConnecting an external alarm relay To add an external alarm relayManagement module Serial interface HP Modular Cooling System Utility overviewMain menu Option number Submenu DescriptionMenu Network Configuration submenu IP Configuration submenu Change Passwords submenu Info Configuring HyperTerminal Factory Default submenuConfiguring Minicom Operator display Operator display overviewOperator display components Indicators Meaning Sensors Sensors Water group sensor Snmp notification Type of message Solution Solution Uneven heat load Indicators Meaning Page Indicators Meaning Has been exceeded or the water flow is less than 2 l/min Indicators Meaning Adjusting the operator display Operator display Automatic Door Release Kit Automatic Door Release Kit OverviewFrequently asked questions HP Modular Cooling System frequently asked questionsQuestion Answer Port x set out lf=strip Troubleshooting HP Modular Cooling System troubleshootingIssue Resolution Specifications MCS specificationsSpecification Features Specifications HP 10642 G2 Rack specificationsEnvironmental specifications Thermal and air flow performanceAir and water heat exchanger maintenance Replaceable parts and maintenance and service informationMaintenance and service Replaceable partsWater quality requirements and specifications Cooling water composition guidelinesAcceptable water quality range Hydrological data Acceptable range CSBLeveling requirements Monitoring the quality of cooling solutionsAdjust the MCS leveling feet so that the unit is level Frost damageCondensation management HP contact information Technical supportBefore you contact HP Customer Self RepairRéparation par le client CSR Riparazione da parte del cliente Reparaciones del propio cliente Reparo feito pelo cliente Technical support Technical support Technical support Federal Communications Commission notice Regulatory compliance noticesRegulatory compliance identification numbers ModificationsCables Canadian noticeEuropean Union regulatory notice Regulatory compliance notices Battery replacement notice Taiwan battery recycling noticePower cord statement for Japan Acronyms and abbreviations Simple Mail Transfer Protocol Power distribution unitSystems Insight Manager Simple Network Management ProtocolIndex Index