Solution:
1.View the Overview menu to distinguish which temperature sensor is different from the other temperature sensors.
2.After discovering which temperature sensor is not working properly, remove that module and reinstall it. If the difference is in the Server Exhaust Temperature, replace the appropriate fan unit. If the difference is in the Server Intake Temperature, replace the appropriate HEX unit.
If the warning message does not clear after the module is reseated, replace the HEX unit with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance and service information (on page 63)."
Low water flow
Indicators | Meaning |
|
|
Actual operator display alarm | Water flow Low |
message |
|
|
|
Actual web interface alarm | Water flow Low |
message |
|
|
|
Condition | No or low water flow |
|
|
Modules | Water group |
|
|
SNMP notification | Warning |
|
|
Type of message | Warning |
|
|
Solution:
Verify the water supply.
Water temperature input is out of range
Indicators | Meaning |
|
|
Actual operator display alarm | Water Temp. In Failed |
message |
|
|
|
Actual web interface alarm | Water Unit Temperature Input Out of Range |
message |
|
|
|
Condition | Water temperature sensor is not working properly (possible open circuit) |
|
|
Sensors | Water group sensor |
|
|
SNMP notification | Warning |
|
|
Type of message | Warning |
|
|
Solution:
1.Verify the water supply.
2.Verify whether the water temperature is below or above the water temperature expected range.
3.Contact your building supervisor.
4.Contact HP, or see the HP website (http://www.hp.com).
Water temperature output is out of range
Operator display 48