HP Modular Cooling System manual Sensors Water group sensor Snmp notification Type of message

Page 48

Solution:

1.View the Overview menu to distinguish which temperature sensor is different from the other temperature sensors.

2.After discovering which temperature sensor is not working properly, remove that module and reinstall it. If the difference is in the Server Exhaust Temperature, replace the appropriate fan unit. If the difference is in the Server Intake Temperature, replace the appropriate HEX unit.

If the warning message does not clear after the module is reseated, replace the HEX unit with a CSR part. For more information on CSR parts, see "Replaceable parts and maintenance and service information (on page 63)."

Low water flow

Indicators

Meaning

 

 

Actual operator display alarm

Water flow Low

message

 

 

 

Actual web interface alarm

Water flow Low

message

 

 

 

Condition

No or low water flow

 

 

Modules

Water group

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

Verify the water supply.

Water temperature input is out of range

Indicators

Meaning

 

 

Actual operator display alarm

Water Temp. In Failed

message

 

 

 

Actual web interface alarm

Water Unit Temperature Input Out of Range

message

 

 

 

Condition

Water temperature sensor is not working properly (possible open circuit)

 

 

Sensors

Water group sensor

 

 

SNMP notification

Warning

 

 

Type of message

Warning

 

 

Solution:

1.Verify the water supply.

2.Verify whether the water temperature is below or above the water temperature expected range.

3.Contact your building supervisor.

4.Contact HP, or see the HP website (http://www.hp.com).

Water temperature output is out of range

Operator display 48

Image 48
Contents HP Modular Cooling System User Guide Part Number February 2007 Second EditionAudience assumptions Contents Replaceable parts and maintenance and service information Overview IntroductionReference Configuration factors Optimum environment and site requirementsSite preparation Installation MCS kit contentsRack hardware kit contents Required toolsInstalling the MCS unit Installation Installation Installation Installation Installation Powering up and configuring the unit Installation Installation Installation Installation Installation Return to the Main Menu Network Configuration screen Enter 4 Activate Actual ValuesInstallation Installation Configuring the IP address through the web interface Installation Installation Installation Installation Management module Management module overviewManagement module components Logging in through the terminal emulation program Reference DescriptionAccessing the management module through the web interface Web interface requirementsLogging in through the web interface Software BrowserConnecting an external alarm relay To add an external alarm relayManagement module Serial interface HP Modular Cooling System Utility overviewMain menu Option number Submenu DescriptionMenu Network Configuration submenu IP Configuration submenu Change Passwords submenu Info Configuring HyperTerminal Factory Default submenuConfiguring Minicom Operator display Operator display overview Operator display components Indicators Meaning Sensors Sensors Water group sensor Snmp notification Type of message Solution Solution Uneven heat load Indicators Meaning Page Indicators Meaning Has been exceeded or the water flow is less than 2 l/min Indicators Meaning Adjusting the operator display Operator display Automatic Door Release Kit Automatic Door Release Kit OverviewFrequently asked questions HP Modular Cooling System frequently asked questionsQuestion Answer Port x set out lf=strip Troubleshooting HP Modular Cooling System troubleshootingIssue Resolution Specifications MCS specificationsSpecification HP 10642 G2 Rack specifications Environmental specificationsFeatures Specifications Thermal and air flow performanceReplaceable parts and maintenance and service information Maintenance and serviceAir and water heat exchanger maintenance Replaceable partsWater quality requirements and specifications Cooling water composition guidelinesAcceptable water quality range Hydrological data Acceptable range CSBMonitoring the quality of cooling solutions Adjust the MCS leveling feet so that the unit is levelLeveling requirements Frost damageCondensation management Technical support Before you contact HPHP contact information Customer Self RepairRéparation par le client CSR Riparazione da parte del cliente Reparaciones del propio cliente Reparo feito pelo cliente Technical support Technical support Technical support Regulatory compliance notices Regulatory compliance identification numbersFederal Communications Commission notice ModificationsCables Canadian noticeEuropean Union regulatory notice Regulatory compliance notices Battery replacement notice Taiwan battery recycling noticePower cord statement for Japan Acronyms and abbreviations Power distribution unit Systems Insight ManagerSimple Mail Transfer Protocol Simple Network Management ProtocolIndex Index
Related manuals
Manual 10 pages 27.17 Kb Manual 93 pages 20.21 Kb Manual 4 pages 15.71 Kb Manual 16 pages 5.24 Kb Manual 83 pages 40.42 Kb Manual 60 pages 37.09 Kb