HEATING CAPACITY - Upflow, Downflow, and Horizontal Furnaces and Coils (Coil Only Ratings)
UNIT | COIL1 |
|
|
| HEATING2 |
|
|
| |
MODEL | MODEL |
| 47 °F |
|
| 17 °F |
| HSPF | |
|
| MBH | COP | KW | MBH | COP | KW | STD | |
|
| 13 SEER HP | COIL ONLY | RATINGS |
|
|
|
| |
| FC/MC/PC18 | 18.0 | 3.36 | 1.50 | 12.7 | 2.16 | 1.24 | 8.20 | |
| FC/MC/PC24 | 18.0 | 3.36 | 1.45 | 10.4 | 2.60 | 1.17 | 8.20 | |
YHJD18S41S2 | FC/MC/PC30 | 18.0 | 3.42 | 1.54 | 11.4 | 2.18 | 1.53 | 7.75 | |
| UC24 | 18.0 | 3.42 | 1.54 | 11.4 | 2.20 | 1.52 | 7.75 | |
| UC30 | 18.0 | 3.42 | 1.54 | 11.4 | 2.20 | 1.52 | 7.75 | |
| FC/MC/PC32 | 24.0 | 3.36 | 2.09 | 13.9 | 2.38 | 1.71 | 7.70 | |
YHJD24S41S4 | FC/MC/PC35 | 23.8 | 3.32 | 2.10 | 13.9 | 2.36 | 1.73 | 7.70 | |
FC/MC/PC37 | 24.0 | 3.44 | 2.04 | 14.1 | 2.42 | 1.71 | 7.70 | ||
| |||||||||
| FC/MC/PC43 | 24.0 | 3.44 | 2.04 | 14.1 | 2.42 | 1.71 | 7.70 | |
| FC/MC/PC32 | 27.4 | 3.28 | 2.45 | 16.0 | 2.30 | 2.04 | 7.70 | |
YHJD30S41S4 | FC/MC/PC35 | 27.4 | 3.28 | 2.45 | 16.0 | 2.30 | 2.04 | 7.70 | |
FC/MC/PC37 | 28.0 | 3.38 | 2.43 | 16.1 | 2.32 | 2.03 | 7.70 | ||
| |||||||||
| FC/MC/PC43 | 28.0 | 3.38 | 2.43 | 16.1 | 2.32 | 2.03 | 7.70 | |
| FC/MC/PC37 | 34.4 | 3.42 | 2.95 | 22.4 | 2.62 | 2.51 | 7.70 | |
YHJD36S41S4 | FC/MC/PC43 | 34.6 | 3.40 | 2.98 | 22.2 | 2.60 | 2.50 | 7.70 | |
FC/MC/PC48 | 34.8 | 3.44 | 2.96 | 22.6 | 2.64 | 2.51 | 7.70 | ||
| |||||||||
| UC48 | 35.0 | 3.52 | 2.91 | 22.4 | 2.62 | 2.51 | 7.70 | |
YHJD42S41S4 | FC/MC/PC60 | 40.5 | 3.72 | 3.19 | 23.0 | 2.50 | 2.70 | 7.70 | |
UC60 | 40.0 | 3.68 | 3.18 | 22.8 | 2.48 | 2.69 | 7.70 | ||
| |||||||||
| FC/MC/PC60 | 46.0 | 3.58 | 3.76 | 27.4 | 2.76 | 2.91 | 7.70 | |
YHJD48S41S4 | FC/MC62 | 46.0 | 3.54 | 3.81 | 27.4 | 2.76 | 2.91 | 7.70 | |
| UC60 | 46.0 | 3.56 | 3.79 | 27.4 | 2.74 | 2.93 | 7.70 | |
YHJD60S41S5 | FC/MC62 | 58.0 | 3.44 | 5.24 | 39.5 | 2.66 | 4.35 | 7.80 | |
FC64 | 58.0 | 3.36 | 5.49 | 40.5 | 2.76 | 4.30 | 7.80 | ||
|
1.Rated CFM same as for cooling.
2.Heating MBH based on AHRI standards of 70 °F DB (Dry Bulb) entering indoor air, 72% RH (Relative Humidity) outdoor air with 25 feet of interconnecting piping and no supplemental electric heat operation.
COP equals MBH output divided by (total KW input x 3.412).
HSPF (Heating Seasonal Performance Factor) is the total heating output during a normal annual usage period for heating divided by the total electric power input during the same period.
MA Modular Air Handlers use Coil Only Ratings.
PSC furnaces, such as the TG8S, TGLS, and TG9S, use Coil Only Ratings.
— = Not Applicable.
Johnson Controls Unitary Products | 15 |