York YHJD18 THRU 60 warranty System Charge for Various Matched Systems, Footnotes

Page 3

571209-YTG-C-1012

System Charge for Various Matched Systems

Outdoor Unit

YHJD18S41S2

YHJD24S41S4

YHJD30S41S4

YHJD36S41S4

YHJD42S41S4

YHJD48S41S4

YHJD60S41S5

Required Orifice or TXV 1,2

.051/4F1

.054, .059/4G1

.063/4G1

.071/4H1

.075/4H1

4J1

4K1

 

 

 

 

 

 

Indoor Unit 3,4,5

 

 

Additional Charge, Oz

 

 

AHE18B

.051/ TXV + 0

AHE24B

.054 / TXV + 0

AHE30B

.054 / TXV + 0

.063 / TXV + 0

AHE36C

.063 / TXV + 25

.071 / TXV + 0

AHE42D

.071 / TXV + 16

AHE48D

.075 / TXV + 0

TXV + 0

AHE60D

TXV + 25

TXV + 0

AHR18B

.051/ TXV + 0

AHR24B

.054 / TXV + 0

AHR30B

.063 / TXV + 0

AHR36B

.063 / TXV + 25

.071 / TXV + 6

AHR42C

.071 / TXV + 16

AHR48D

.075 / TXV + 0

TXV + 0

AHR60D

TXV + 25

TXV + 0

AHV18B

.051/ TXV + 0

AHV24B

.054 / TXV + 0

AHV30B

.054 / TXV + 0

.063 / TXV + 0

AHV36C

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

AHV42D

.071 / TXV + 16

AHV48D

.075 / TXV + 0

TXV + 0

AHV60D

TXV + 25

TXV + 0

AV*24

.051/ TXV + 3

AV*36

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

AV*48

.075 / TXV + 0

TXV + 0

AV*60

.075 / TXV + 0

TXV + 0

FC/MC/PC18

.051/ TXV + 0

FC/MC/PC24

.051/ TXV + 5

FC/MC/PC30

.051/ TXV + 5

FC/MC/PC32

.059 / TXV + 0

.063 / TXV + 0

FC/MC/PC35

.059 / TXV + 0

.063 / TXV + 0

FC/MC/PC37

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

FC/MC/PC43

.059 / TXV + 23 .063 / TXV + 25

.071 / TXV + 6

FC/MC/PC/UC48

.071 / TXV + 16

FC/MC/PC/UC60

.075 / TXV + 0

TXV + 0

FC/MC62

TXV + 25

TXV + 0

FC64

TXV + 23

UC18

.051/ TXV + 1

UC24

.051/ TXV + 7

UC30

.051/ TXV + 7

UC48

.071 / TXV + 25

UC60

.075 / TXV + 2

TXV + 11

Some of the combinations shown in the above System Charge table require Advanced Main Air Circulating Fan indoor product. For approved coil only matches, please see the “COOLING CAPACITY - Upflow, Downflow & Horizontal Furnaces and Coils” table.

FOOTNOTES:

1.For applications requiring a TXV use S1-1TVM*** series kit.

2.Approved orifice(s) shipped with outdoor unit.

3.Systems matched with furnaces or air handlers not equipped with blower-off delays may require blower Time Delay Kit S1-2FD06700224.

4.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

5.Refer to Cooling and Heating Performance Data tables for actual performance for specified system matches.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the outdoor unit, the smallest matched indoor unit, and 15 feet of interconnecting line tubing.

2.Verify the TXV or orifice and additional charge required for specific matched indoor unit in the system using the above table.

3.Add additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.

4.For indoor matches requiring additional charge, the refrigerant needs to be weighed in for specific matched indoor unit and lineset length.

5.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + charge adder for matched indoor unit + charge adder for line set.

Johnson Controls Unitary Products

3

Image 3
Contents Technical Guide Model Physical and Electrical DataFootnotes System Charge for Various Matched SystemsSeer HP with AIR Handlers Unit AIR HandlerCooling Model Width MODEL1 Rated NET MBH Seer EER CFM SensFC60C Model Width MODEL1 Seer EER Coil CFM Range Cooling Unit Model Rated NET MBH SEER1 WidthSeer HP Coil Unit Furnace Coil Cooling RatedUnit Model Furnace Width Coil MODEL1 Cooling Rated FC/MC/PC32A FC/MC/PC48C FC/MC/PC48D FC/PC60C 9C,V*D20 24.5 Unit AIR COIL1 HEATING2 Model Handler HspfMBH COP STD Seer HP with AIR Handlers MV16C FC60C MBH COP STD Seer HP Coil only Ratings Unit COIL1 HEATING2 ModelModel Furnace COIL1 HEATING2 MBH COP STDEfficiency Motor FURNACES3 Model Furnace COIL1 HEATING2 Hspf 27.4 16.0 34.0 21.4 LX*C20 40.0 22.4 9X*C20 45.5 27.2 9C*C20 SQI AccessoriesTypical Installation Temperature Condensing IdcfmEntering AIR Furnaces Coils MV12B FC/MC35B FC/MC43B MX12B FC/MC/PC32A MV12B FC/MC35B FC/MC43B MV16C FC/MC35C FC/MC43C MX12B MX16C YTG-C-1012 FC/MC/PC37 FC/MC/PC43 FC/MC/PC48 FC/MC/PC48C AHE48D AHR48D AHV48D FC/MC/PC60 FC/MC62 YTG-C-1012 AHE60D AHR60D AHV60D MV20D FC/MC62D FC64D MX20D Entering Outdoor Unit Indoor CoilMBH COP FC/MC/PC18A 28.3 27.5 1000 1200 On next FC/MC/PC48C FC/MC/PC60 1600 1800 Johnson Controls Unitary Products York Drive Norman, OK