571209-YTG-C-1012
COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD36S41S4 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
INDOOR COIL MODEL NO. | AHP36 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
|
| 1000 |
|
|
|
| 1200 |
|
|
|
| 1400 |
|
|
ENTERING AIR | ID DB (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID WB (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
| T.C. | 35.0 | 39.8 | 39.9 | 42.7 | 45.2 | 37.7 | 40.6 | 41.0 | 43.5 | 45.7 | 40.5 | 41.5 | 42.0 | 44.4 | 46.1 |
65 | S.C. | 34.9 | 32.4 | 27.9 | 27.1 | 22.7 | 37.7 | 35.4 | 29.9 | 28.6 | 23.2 | 40.4 | 38.5 | 31.8 | 30.2 | 23.8 |
| KW | 2.40 | 2.40 | 2.40 | 2.50 | 2.50 | 2.50 | 2.50 | 2.50 | 2.50 | 2.50 | 2.60 | 2.60 | 2.60 | 2.60 | 2.60 |
| T.C. | 33.3 | 36.8 | 36.9 | 39.9 | 42.9 | 35.7 | 37.6 | 37.9 | 40.8 | 43.4 | 38.1 | 38.5 | 38.9 | 41.8 | 43.9 |
75 | S.C. | 33.2 | 31.1 | 26.5 | 25.9 | 21.5 | 35.7 | 33.7 | 28.5 | 27.6 | 22.2 | 38.1 | 36.4 | 30.5 | 29.4 | 22.9 |
| KW | 2.60 | 2.60 | 2.60 | 2.70 | 2.70 | 2.70 | 2.70 | 2.70 | 2.70 | 2.80 | 2.80 | 2.80 | 2.80 | 2.80 | 2.80 |
| T.C. | 31.6 | 33.8 | 33.9 | 37.1 | 40.6 | 33.7 | 34.6 | 34.8 | 38.2 | 41.2 | 35.8 | 35.5 | 35.7 | 39.2 | 41.8 |
85 | S.C. | 31.5 | 29.7 | 25.1 | 24.8 | 20.2 | 33.6 | 32.1 | 27.2 | 26.7 | 21.1 | 35.7 | 34.4 | 29.2 | 28.5 | 22.0 |
| KW | 2.80 | 2.80 | 2.80 | 2.90 | 2.90 | 2.90 | 2.90 | 2.90 | 2.90 | 3.00 | 3.00 | 3.00 | 3.00 | 3.00 | 3.10 |
| T.C. | 29.9 | 30.8 | 30.8 | 34.3 | 38.4 | 31.7 | 31.6 | 31.7 | 35.5 | 39.0 | 33.5 | 32.5 | 32.6 | 36.6 | 39.6 |
95 | S.C. | 29.8 | 28.4 | 23.7 | 23.6 | 19.0 | 31.6 | 30.4 | 25.8 | 25.7 | 20.1 | 33.4 | 32.4 | 27.9 | 27.7 | 21.1 |
| KW | 2.90 | 2.90 | 3.00 | 3.10 | 3.10 | 3.00 | 3.10 | 3.10 | 3.10 | 3.20 | 3.20 | 3.20 | 3.20 | 3.20 | 3.30 |
| T.C. | 26.3 | 26.7 | 27.4 | 31.4 | 35.3 | 28.6 | 28.5 | 28.1 | 32.4 | 35.9 | 30.9 | 30.4 | 28.8 | 33.3 | 36.5 |
105 | S.C. | 26.3 | 25.5 | 22.3 | 22.4 | 17.8 | 28.6 | 27.9 | 24.3 | 24.5 | 18.9 | 30.9 | 30.4 | 26.3 | 26.5 | 20.0 |
| KW | 3.10 | 3.10 | 3.10 | 3.20 | 3.30 | 3.20 | 3.20 | 3.20 | 3.30 | 3.40 | 3.30 | 3.30 | 3.30 | 3.40 | 3.50 |
| T.C. | 22.8 | 22.6 | 24.1 | 28.5 | 32.2 | 25.6 | 25.5 | 24.5 | 29.2 | 32.8 | 28.4 | 28.4 | 25.0 | 30.0 | 33.5 |
115 | S.C. | 22.8 | 22.5 | 20.8 | 21.3 | 16.6 | 25.5 | 25.4 | 22.8 | 23.3 | 17.8 | 28.3 | 28.3 | 24.8 | 25.3 | 18.9 |
| KW | 3.20 | 3.20 | 3.20 | 3.40 | 3.50 | 3.40 | 3.40 | 3.30 | 3.50 | 3.60 | 3.50 | 3.50 | 3.40 | 3.60 | 3.60 |
| T.C. | 19.3 | 18.4 | 20.7 | 25.6 | 29.1 | 22.5 | 22.4 | 20.9 | 26.1 | 29.8 | 25.8 | 26.4 | 21.2 | 26.7 | 30.4 |
125 | S.C. | 19.2 | 18.4 | 19.3 | 20.1 | 15.4 | 22.5 | 22.4 | 20.9 | 22.1 | 16.6 | 25.8 | 26.3 | 21.2 | 24.0 | 17.8 |
| KW | 3.40 | 3.40 | 3.30 | 3.50 | 3.70 | 3.60 | 3.50 | 3.50 | 3.60 | 3.70 | 3.70 | 3.70 | 3.60 | 3.80 | 3.80 |
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handlers | Coils | T.C. | S.C. | KW |
– | FC/MC/PC37 | 1.03 | 1.02 | 1.02 |
– | FC/MC/PC43 | 1.03 | 1.02 | 1.02 |
– | FC/MC/PC48 | 1.03 | 1.03 | 1.02 |
– | UC48 | 1.04 | 1.03 | 1.02 |
AHE36C | – | 1.05 | 1.04 | 0.96 |
AHE42D | – | 1.05 | 1.05 | 0.94 |
AHR36B | – | 1.04 | 1.04 | 1.02 |
AHR42C | – | 1.04 | 1.04 | 1.01 |
AHV36C | – | 1.04 | 1.04 | 0.97 |
AHV42D | – | 1.05 | 1.05 | 0.95 |
AV*36 | – | 1.05 | 1.04 | 0.96 |
MV12B | FC/MC43B | 1.04 | 1.04 | 0.97 |
MV12D | FC/MC48D | 1.06 | 1.05 | 0.93 |
MV16C | FC/MC43C | 1.05 | 1.04 | 0.96 |
MV16C | FC/MC48C | 1.05 | 1.05 | 0.95 |
MX12B | FC/MC43B | 1.04 | 1.04 | 0.97 |
MX12D | FC/MC48D | 1.05 | 1.05 | 0.95 |
MX16C | FC/MC43C | 1.05 | 1.04 | 0.94 |
MX16C | FC/MC48C | 1.06 | 1.05 | 0.93 |
Continued on next page.
30 | Johnson Controls Unitary Products |