COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJD24S41S4 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
INDOOR COIL MODEL NO. | AHP30 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
|
| 600 |
|
|
|
| 800 |
|
|
|
| 1000 |
|
|
ENTERING AIR | ID DB (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID WB (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
| T.C. | 22.6 | 25.9 | 25.9 | 28.3 | 29.4 | 25.2 | 27.1 | 26.8 | 29.2 | 30.4 | 27.9 | 28.3 | 27.6 | 30.0 | 31.4 |
65 | S.C. | 22.6 | 20.9 | 18.1 | 18.1 | 15.5 | 25.2 | 23.9 | 19.7 | 19.5 | 16.1 | 27.9 | 26.9 | 21.3 | 20.9 | 16.6 |
| KW | 1.60 | 1.60 | 1.60 | 1.70 | 1.70 | 1.70 | 1.70 | 1.70 | 1.70 | 1.70 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 |
| T.C. | 21.5 | 24.1 | 24.2 | 26.6 | 28.1 | 23.9 | 25.3 | 25.1 | 27.5 | 29.0 | 26.3 | 26.4 | 26.0 | 28.5 | 29.9 |
75 | S.C. | 21.5 | 20.1 | 17.3 | 17.3 | 14.7 | 23.9 | 22.8 | 19.1 | 18.9 | 15.4 | 26.3 | 25.6 | 20.9 | 20.6 | 16.1 |
| KW | 1.70 | 1.80 | 1.80 | 1.80 | 1.80 | 1.80 | 1.90 | 1.80 | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 2.00 | 2.00 |
| T.C. | 20.4 | 22.3 | 22.4 | 24.8 | 26.8 | 22.6 | 23.4 | 23.4 | 25.9 | 27.6 | 24.7 | 24.5 | 24.4 | 26.9 | 28.4 |
85 | S.C. | 20.4 | 19.4 | 16.5 | 16.4 | 13.8 | 22.6 | 21.8 | 18.6 | 18.4 | 14.7 | 24.7 | 24.3 | 20.6 | 20.3 | 15.6 |
| KW | 1.90 | 1.90 | 1.90 | 1.90 | 1.90 | 2.00 | 2.00 | 2.00 | 2.00 | 2.00 | 2.10 | 2.10 | 2.10 | 2.10 | 2.10 |
| T.C. | 19.4 | 20.6 | 20.6 | 23.0 | 25.5 | 21.2 | 21.6 | 21.7 | 24.2 | 26.2 | 23.1 | 22.6 | 22.7 | 25.4 | 26.9 |
95 | S.C. | 19.4 | 18.6 | 15.7 | 15.6 | 13.0 | 21.2 | 20.8 | 18.0 | 17.8 | 14.0 | 23.1 | 22.6 | 20.2 | 20.0 | 15.1 |
| KW | 2.00 | 2.00 | 2.00 | 2.00 | 2.10 | 2.10 | 2.10 | 2.10 | 2.10 | 2.20 | 2.20 | 2.20 | 2.20 | 2.30 | 2.30 |
| T.C. | 17.6 | 18.0 | 18.0 | 20.9 | 23.5 | 19.4 | 19.5 | 18.9 | 21.9 | 24.3 | 21.3 | 21.0 | 19.9 | 23.0 | 25.1 |
105 | S.C. | 17.6 | 17.2 | 14.5 | 14.7 | 12.0 | 19.4 | 19.3 | 16.7 | 16.9 | 13.2 | 21.3 | 21.0 | 18.8 | 19.1 | 14.4 |
| KW | 2.10 | 2.10 | 2.10 | 2.20 | 2.20 | 2.20 | 2.20 | 2.20 | 2.30 | 2.30 | 2.30 | 2.30 | 2.30 | 2.40 | 2.40 |
| T.C. | 15.8 | 15.5 | 15.4 | 18.8 | 21.5 | 17.6 | 17.5 | 16.2 | 19.7 | 22.4 | 19.5 | 19.5 | 17.0 | 20.6 | 23.3 |
115 | S.C. | 15.8 | 15.5 | 13.3 | 13.9 | 11.1 | 17.6 | 17.5 | 15.3 | 16.0 | 12.4 | 19.5 | 19.5 | 17.0 | 18.2 | 13.7 |
| KW | 2.20 | 2.20 | 2.20 | 2.30 | 2.40 | 2.30 | 2.30 | 2.30 | 2.40 | 2.50 | 2.50 | 2.50 | 2.40 | 2.50 | 2.60 |
| T.C. | 13.9 | 13.0 | 12.7 | 16.6 | 19.5 | 15.8 | 15.5 | 13.4 | 17.4 | 20.5 | 17.7 | 17.9 | 14.1 | 18.2 | 21.5 |
125 | S.C. | 13.9 | 13.0 | 12.1 | 13.0 | 10.1 | 15.8 | 15.5 | 13.4 | 15.2 | 11.5 | 17.7 | 17.9 | 14.1 | 17.3 | 13.0 |
| KW | 2.30 | 2.20 | 2.20 | 2.40 | 2.50 | 2.40 | 2.40 | 2.40 | 2.50 | 2.60 | 2.60 | 2.60 | 2.50 | 2.60 | 2.70 |
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handlers | Coils | T.C. | S.C. | KW |
– | FC/MC/PC32 | 1.02 | 1.00 | 1.02 |
– | FC/MC/PC35 | 1.02 | 1.00 | 1.02 |
– | FC/MC/PC37 | 1.03 | 1.02 | 1.02 |
– | FC/MC/PC43 | 1.03 | 1.02 | 1.02 |
AHE24B | – | 1.03 | 1.02 | 0.94 |
AHE30B | – | 1.03 | 1.02 | 0.94 |
AHR24B | – | 1.02 | 0.98 | 0.98 |
AHV24B | – | 1.02 | 0.97 | 0.93 |
AHV30B | – | 1.02 | 1.01 | 0.94 |
AHV36C | – | 1.03 | 1.02 | 0.93 |
AV*36 | – | 1.02 | 1.00 | 0.92 |
MV12B | FC/MC35B | 1.05 | 1.03 | 0.94 |
MV12B | FC/MC43B | 1.06 | 1.04 | 0.94 |
MX12B | FC/MC35B | 1.06 | 1.03 | 0.92 |
MX12B | FC/MC43B | 1.02 | 1.01 | 0.92 |
Continued on next page.
26 | Johnson Controls Unitary Products |