York YHJD18 THRU 60 warranty AHE48D AHR48D AHV48D

Page 32

571209-YTG-C-1012

COOLING PERFORMANCE DATA

CONDENSING UNIT MODEL NO. YHJD42S41S4

 

 

 

 

 

 

 

 

 

 

 

 

INDOOR COIL MODEL NO.

AHP48

 

 

 

 

 

 

 

 

 

 

 

 

 

CONDENSING

IDCFM

 

 

1200

 

 

 

 

1400

 

 

 

 

1600

 

 

ENTERING AIR

ID DB (°F)

80

80

75

80

80

80

80

75

80

80

80

80

75

80

80

TEMPERATURE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ID WB (°F)

57

62

62

67

72

57

62

62

67

72

57

62

62

67

72

 

T.C.

42.5

44.2

45.0

49.4

52.7

44.4

45.8

46.4

50.5

53.5

46.4

47.4

47.7

51.5

54.4

65

S.C.

42.5

38.4

32.9

32.8

26.7

44.4

42.2

35.3

34.7

27.6

46.4

46.0

37.6

36.7

28.6

 

KW

2.70

2.80

2.80

2.80

2.90

2.80

2.80

2.90

2.90

2.90

2.90

2.90

2.90

3.00

3.00

 

T.C.

39.9

40.7

41.7

46.3

49.8

41.8

42.3

42.9

47.2

50.6

43.7

43.9

44.1

48.1

51.3

75

S.C.

39.9

36.8

31.4

31.4

25.4

41.8

40.0

33.7

33.3

26.4

43.7

43.2

36.0

35.3

27.4

 

KW

2.90

2.90

2.90

3.00

3.10

3.00

3.00

3.00

3.10

3.10

3.10

3.10

3.10

3.20

3.20

 

T.C.

37.4

37.3

38.4

43.2

47.0

39.2

38.8

39.5

44.0

47.6

41.0

40.4

40.6

44.8

48.3

85

S.C.

37.4

35.1

29.8

29.9

24.1

39.2

37.8

32.1

32.0

25.1

41.0

40.4

34.4

34.0

26.1

 

KW

3.10

3.10

3.10

3.20

3.30

3.20

3.20

3.20

3.30

3.30

3.30

3.30

3.30

3.40

3.40

 

T.C.

34.8

33.9

35.0

40.1

44.1

36.6

35.4

36.0

40.7

44.7

38.3

36.8

37.0

41.4

45.3

95

S.C.

34.8

33.4

28.3

28.5

22.8

36.6

35.4

30.6

29.9

23.8

38.3

36.8

32.8

32.6

24.8

 

KW

3.30

3.30

3.30

3.40

3.50

3.40

3.40

3.40

3.50

3.50

3.50

3.50

3.50

3.60

3.60

 

T.C.

31.6

31.2

30.9

36.1

40.5

33.4

32.8

31.7

37.1

41.2

35.3

34.5

32.6

38.0

42.0

105

S.C.

31.6

31.2

26.5

26.9

21.3

33.4

32.8

28.6

29.1

22.4

35.3

34.5

30.8

31.3

23.6

 

KW

3.50

3.50

3.50

3.60

3.70

3.60

3.60

3.60

3.70

3.80

3.80

3.70

3.70

3.80

3.90

 

T.C.

28.3

28.5

26.7

32.1

36.9

30.3

30.3

27.4

33.4

37.8

32.2

32.1

28.1

34.7

38.6

115

S.C.

28.3

28.5

24.6

25.3

19.7

30.3

30.3

26.7

27.6

21.0

32.2

32.1

28.1

29.9

22.4

 

KW

3.70

3.70

3.60

3.80

3.90

3.80

3.80

3.70

3.90

4.00

4.00

4.00

3.80

4.00

4.10

 

T.C.

25.1

25.8

22.6

28.1

33.3

27.1

27.8

23.1

29.7

34.3

29.1

29.7

23.7

31.3

35.3

125

S.C.

25.1

25.8

22.6

23.6

18.1

27.1

27.8

23.1

26.1

19.6

29.1

29.7

23.7

28.6

21.2

 

KW

3.90

3.90

3.80

4.00

4.20

4.00

4.00

3.90

4.10

4.30

4.20

4.20

4.00

4.20

4.40

NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT. KW VALUES ARE FOR THE SYSTEM (OUTDOOR + INDOOR).

Multipliers for determining the performance with other indoor sections.

NOTE: For dry bulb temperatures different than those listed (between 73-87 °F), sensible capacity increases by 1060 BTUH per 1000 CFM per degree above the listed temperature and decreases by 1060 BTUH per 1000 CFM per degree below the listed temperature.

Air Handlers

Coils

T.C.

S.C.

KW

FC/MC/PC60

0.96

0.99

1.01

UC60

0.96

0.98

1.02

AHE48D

0.98

1.01

0.94

AHR48D

0.96

0.96

1.01

AHV48D

0.97

0.97

0.96

AV*48

0.98

1.01

0.94

AV*60

0.98

1.01

0.94

MV16C

FC60C

0.98

1.00

0.97

MV20D

FC/MC60D

0.98

1.00

0.96

MX16C

FC60C

0.98

1.01

0.94

MX20D

FC/MC60D

1.01

1.06

0.94

Furnaces

Coils

T.C.

S.C.

KW

T*(8,L)V*C16

FC/PC60C

0.97

1.00

0.98

T*(8,L)V*C16

UC60C

0.97

1.00

0.97

T*(8,L)V*C20

FC/PC60C

0.98

1.00

0.96

T*(8,L)V*C20

UC60C

0.97

1.00

0.96

T*(8,L)X*C16

FC/PC60C

0.98

1.01

0.94

T*(8,L)X*C16

UC60C

0.98

1.01

0.94

T*(8,L)X*C20

FC/PC60C

1.01

1.06

0.96

T*(8,L)X*C20

UC60C

0.98

1.04

0.95

T*9(C,V)*C16

FC/PC60C

0.97

0.99

1.01

Furnaces

Coils

T.C.

S.C.

KW

T*9(C,V)*C16

UC60C

0.96

0.99

1.00

T*9(C,V)*C20

FC/PC60C

0.97

1.00

0.99

T*9(C,V)*C20

UC60C

0.97

0.99

0.99

T*9(C,V)*D20

FC/MC/PC60D

0.97

1.00

0.98

T*9(C,V)*D20

UC60D

0.97

1.00

0.98

T*9X*C16

FC/PC60C

1.00

1.04

0.97

T*9X*C16

UC60C

0.97

1.00

0.96

T*9X*C20

FC/PC60C

1.00

1.05

0.96

T*9X*C20

UC60C

0.98

1.00

0.96

T*9X*D20

FC/MC/PC60D

1.01

1.08

0.95

T*9X*D20

UC60D

1.00

1.05

0.95

Y*(8,L)C*C16

FC/PC60C

0.97

1.00

0.98

Y*(8,L)C*C16

UC60C

0.97

1.00

0.97

Y*(8,L)C*C20

FC/PC60C

0.98

1.00

0.96

Y*(8,L)C*C20

UC60C

0.97

1.00

0.96

Y*9C*C16

FC/PC60C

0.97

0.99

1.01

Y*9C*C16

UC60C

0.96

0.99

1.00

Y*9C*C20

FC/PC60C

0.97

1.00

0.99

Y*9C*C20

UC60C

0.97

0.99

0.99

Y*9C*D20

FC/MC/PC60D

0.97

1.00

0.98

Y*9C*D20

UC60D

0.97

1.00

0.98

32

Johnson Controls Unitary Products

Image 32
Contents Technical Guide Physical and Electrical Data ModelSystem Charge for Various Matched Systems FootnotesUnit AIR Handler Cooling Model Width MODEL1 Rated NET MBH Seer EER CFMSens Seer HP with AIR HandlersFC60C Coil CFM Range Cooling Unit Model Rated NET MBH SEER1 Width Seer HP CoilUnit Furnace Coil Cooling Rated Model Width MODEL1 Seer EERUnit Model Furnace Width Coil MODEL1 Cooling Rated FC/MC/PC32A FC/MC/PC48C FC/MC/PC48D FC/PC60C 9C,V*D20 24.5 MBH COP STD Seer HP with AIR Handlers Unit AIR COIL1 HEATING2 Model HandlerHspf MV16C FC60C Unit COIL1 HEATING2 Model MBH COP STD Seer HP Coil only RatingsEfficiency Motor FURNACES3 Model Furnace COIL1 HEATING2MBH COP STD Model Furnace COIL1 HEATING2 Hspf 27.4 16.0 34.0 21.4 LX*C20 40.0 22.4 9X*C20 45.5 27.2 9C*C20 Accessories SQITypical Installation Entering AIR TemperatureCondensing Idcfm Furnaces Coils MV12B FC/MC35B FC/MC43B MX12B FC/MC/PC32A MV12B FC/MC35B FC/MC43B MV16C FC/MC35C FC/MC43C MX12B MX16C YTG-C-1012 FC/MC/PC37 FC/MC/PC43 FC/MC/PC48 FC/MC/PC48C AHE48D AHR48D AHV48D FC/MC/PC60 FC/MC62 YTG-C-1012 AHE60D AHR60D AHV60D MV20D FC/MC62D FC64D MX20D MBH COP EnteringOutdoor Unit Indoor Coil FC/MC/PC18A 28.3 27.5 1000 1200 On next FC/MC/PC48C FC/MC/PC60 1600 1800 Johnson Controls Unitary Products York Drive Norman, OK
Related manuals
Manual 30 pages 24.1 Kb