COOLING PERFORMANCE DATA
CONDENSING UNIT MODEL NO. YHJF18S41S1 |
|
|
|
|
|
|
|
|
|
|
|
| ||||
INDOOR COIL MODEL NO. | AHX30 |
|
|
|
|
|
|
|
|
|
|
|
|
| ||
CONDENSING | IDCFM |
|
| 400 |
|
|
|
| 600 |
|
|
|
| 800 |
|
|
ENTERING AIR | ID DB (°F) | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 | 80 | 80 | 75 | 80 | 80 |
TEMPERATURE |
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
|
ID WB (°F) | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | 57 | 62 | 62 | 67 | 72 | |
| T.C. | 17.2 | 18.8 | 18.8 | 20.5 | 22.2 | 19.2 | 19.9 | 20.1 | 21.7 | 22.9 | 21.2 | 20.9 | 21.3 | 22.8 | 23.6 |
65 | S.C. | 16.8 | 14.9 | 12.9 | 12.9 | 11.0 | 18.8 | 17.7 | 15.2 | 14.7 | 11.7 | 20.8 | 20.5 | 17.4 | 16.5 | 12.5 |
| KW | 0.9 | 0.9 | 0.9 | 0.9 | 0.9 | 0.9 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 |
| T.C. | 16.4 | 17.9 | 17.9 | 19.7 | 21.3 | 18.4 | 19.1 | 19.0 | 20.8 | 22.1 | 20.4 | 20.2 | 20.2 | 21.8 | 22.9 |
75 | S.C. | 16.1 | 14.5 | 12.5 | 12.5 | 10.5 | 18.0 | 17.1 | 14.8 | 14.4 | 11.5 | 20.0 | 19.8 | 17.0 | 16.3 | 12.4 |
| KW | 1.0 | 1.0 | 1.0 | 1.0 | 1.0 | 1.1 | 1.1 | 1.1 | 1.1 | 1.1 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 |
| T.C. | 15.7 | 17.0 | 17.0 | 18.9 | 20.4 | 17.7 | 18.3 | 18.0 | 19.9 | 21.3 | 19.6 | 19.5 | 19.1 | 20.8 | 22.1 |
85 | S.C. | 15.4 | 14.1 | 12.1 | 12.1 | 10.1 | 17.3 | 16.6 | 14.3 | 14.2 | 11.2 | 19.2 | 19.1 | 16.6 | 16.2 | 12.2 |
| KW | 1.1 | 1.1 | 1.1 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.2 | 1.3 | 1.3 | 1.3 | 1.3 | 1.3 | 1.3 |
| T.C. | 15.0 | 16.1 | 16.1 | 18.1 | 19.6 | 16.9 | 17.4 | 17.0 | 19.0 | 20.4 | 18.8 | 18.8 | 18.0 | 19.8 | 21.3 |
95 | S.C. | 14.7 | 13.7 | 11.6 | 11.8 | 9.7 | 16.5 | 16.0 | 13.9 | 13.9 | 10.9 | 18.4 | 18.4 | 16.2 | 16.0 | 12.1 |
| KW | 1.3 | 1.3 | 1.3 | 1.3 | 1.3 | 1.4 | 1.4 | 1.4 | 1.4 | 1.4 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 |
| T.C. | 14.0 | 14.7 | 14.8 | 16.7 | 18.4 | 15.9 | 16.2 | 15.7 | 17.6 | 19.2 | 17.7 | 17.7 | 16.6 | 18.5 | 20.1 |
105 | S.C. | 13.7 | 13.1 | 11.0 | 11.2 | 9.2 | 15.5 | 15.2 | 13.3 | 13.4 | 10.4 | 17.3 | 17.3 | 15.6 | 15.6 | 11.6 |
| KW | 1.4 | 1.4 | 1.4 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.5 | 1.6 | 1.6 | 1.6 | 1.6 | 1.6 | 1.7 |
| T.C. | 13.1 | 13.4 | 13.4 | 15.4 | 17.2 | 14.8 | 15.0 | 14.4 | 16.2 | 18.0 | 16.6 | 16.6 | 15.3 | 17.1 | 18.8 |
115 | S.C. | 12.8 | 12.5 | 10.5 | 10.6 | 8.7 | 14.5 | 14.4 | 12.7 | 12.9 | 9.9 | 16.2 | 16.2 | 15.0 | 15.1 | 11.2 |
| KW | 1.6 | 1.6 | 1.6 | 1.6 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.7 | 1.8 | 1.8 | 1.8 | 1.8 | 1.8 |
| T.C. | 12.2 | 12.1 | 12.1 | 14.0 | 16.1 | 13.8 | 13.8 | 13.0 | 14.9 | 16.8 | 15.5 | 15.5 | 14.0 | 15.7 | 17.5 |
125 | S.C. | 11.9 | 11.9 | 9.9 | 10.1 | 8.2 | 13.5 | 13.5 | 12.1 | 12.3 | 9.5 | 15.1 | 15.1 | 14.0 | 14.6 | 10.7 |
| KW | 1.7 | 1.7 | 1.7 | 1.8 | 1.8 | 1.8 | 1.8 | 1.8 | 1.9 | 1.9 | 2.0 | 2.0 | 1.9 | 2.0 | 2.0 |
NOTE: ALL CAPACITIES INCLUDE INDOOR FAN HEAT AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
NOTE: For dry bulb temperatures different than those listed (between
Air Handler | Coil | T.C. | S.C. | KW |
AV*36 | – | 1.00 | 1.00 | 1.08 |
MV12B | FC/MC35B | 1.00 | 0.98 | 1.08 |
MV12B | FC/MC43B | 1.00 | 1.00 | 1.08 |
Furnace | Coil | T.C. | S.C. | KW |
T*(8,L)X*A12 | FC/MC/PC32A | 1.00 | 0.98 | 1.08 |
Y*(8,L)C*A12 | FC/MC/PC32A | 1.00 | 0.98 | 1.08 |
Y*(8,L)C*B12 | FC/MC/PC35B | 1.00 | 1.01 | 1.08 |
Y*(8,L)C*C16 | FC/MC/PC35C | 1.00 | 0.98 | 1.08 |
(Y*9C/T*9V)*B12 | FC/MC/PC35B | 1.00 | 0.98 | 1.08 |
(Y*9C/T*9V)*C16 | FC/MC/PC35C | 1.00 | 1.01 | 1.08 |
Y*(8,L)C*A12 | FC/MC/PC37A | 1.00 | 1.00 | 1.08 |
Y*(8,L)C*B12 | FC/MC/PC43B | 1.00 | 0.96 | 1.08 |
12 | Johnson Controls Unitary Products |