York YHJF18 THRU 60 warranty System Charge for Various Matched Systems, Footnotes, Procedures

Page 3

510667-YTG-B-0509

System Charge for Various Matched Systems

Outdoor Unit

YHJF18

YHJF24

YHJF30

 

YHJF36

 

YHJF42

YHJF48

YHJF60

S41S1

S41S1

S41S1

 

S41S1

 

S41S1

S41S1

S41S1

 

 

 

 

 

 

 

 

 

 

 

Required Orifice or TXV 1,2

.051/1TVM4F1

.059/1TVM4G1

.063/1TVM4G1

.071/1TVM4H1

.075/1TVM4J1

1TVM4J1

1TVM4K1

Factory Charge, lbs-oz

6 - 15

7 - 14

9 - 14

 

10 - 9

 

10 - 9

14 - 2

14 - 2

 

 

 

 

 

 

 

 

 

 

Indoor Coil3,4

 

 

 

Additional Charge, Oz

 

 

 

FC/MC/PC/UC32

.051 + 0

.059 + 0

 

 

 

 

 

 

 

 

 

 

 

 

FC/MC/PC/UC35

.051 + 0

.059 + 0

 

 

 

 

 

 

 

 

 

 

 

 

FC/MC/PC/UC37

.051 + 13

.059 + 12

.063 + 0

 

.071 + 0

 

 

 

 

 

 

 

 

 

 

 

FC/MC/PC/UC43

.051 + 13

.059 + 12

.063 + 0

 

.071 + 0

 

 

 

 

 

 

 

 

 

 

 

FC/PC62D3X

 

 

.075 + 0

TXV + 0

TXV + 0

 

 

 

 

 

 

 

 

 

 

AHX30

.051 + 0

.059 + 0

 

 

 

 

 

 

 

 

 

 

 

 

AHX36

.051 + 13

.059 + 12

.063 + 0

 

.071 + 0

 

 

 

 

 

 

 

 

 

 

 

AHX60

 

 

 

 

 

 

.075 + 0

TXV + 0

TXV + 0

 

 

 

 

 

 

 

 

 

 

AV36

.051 + 13

.059 + 12

.063 + 0

 

.071 + 0

 

 

 

 

 

 

 

 

 

 

 

F6FP030H06

.051 + 0

.059 + 0

 

 

 

 

 

 

 

 

 

 

 

 

F6FP036H06

.051 + 0

.059 + 0

 

 

 

 

 

 

 

 

 

 

 

 

F6FP042H06

.063 + 3

 

.063 + 3

 

 

 

 

 

 

 

 

 

 

 

F6FP060H06

 

 

.075 + 0

TXV + 0

TXV + 0

FOOTNOTES:

 

 

 

 

 

 

 

 

 

1.For applications requiring a TXV use 1TVM series kit.

2.Approved orifice shipped with outdoor unit.

3.Systems matched with furnace or air handlers not equipped with blower-off delays may require blower Time Delay Kit 2FD06700224.

4.PC coils cannot be used in downflow or horizontal applications. FC coils cannot be used in horizontal applications.

PROCEDURES:

1.Unit factory charge listed on the unit nameplate includes refrigerant for the condenser, the smallest evaporator and 15 feet of interconnecting line tubing.

2.Verify the TXV and additional charge required for specific evaporator coil in the system using the above table.

3.Additional charge for the amount of interconnecting line tubing greater than 15 feet at the rate specified in Physical and Electrical Data Table.

4.For orifice or TXV matches requiring additional charge, the refrigerant needs to be weighed in for specific coil match and lineset length.

5.Permanently mark the unit nameplate with the total system charge. Total System Charge = Base Charge (as shipped) + adder for evaporator + adder for line set.

Johnson Controls Unitary Products

3

Image 3
Contents Warranty FeaturesDescription Model Physical and Electrical DataProcedures System Charge for Various Matched SystemsFootnotes Speed Cooling Capacity With Air Handler CoilsSens MV Variable SpeedUnit Model Furnace Coil MODEL1 Stage Cooling Rated Cooling Capacity With High Efficiency Motor FurnacesUnit Furnace Cooling Model MODEL1 Stage RatedSeer EER CFM Heating Capacity With Air Handler Coils Heating Performance With Air HandlerHeating Capacity With High Efficiency Motor Furnaces Model Furnace COIL1 ARI HEATING2 HspfWith Variable Speed FURNACES3 Model Furnace COIL1 ARI HEATING2 Seer HP with Variable Speed FURNACES3 AccessoriesTypical Installation Typical Field WiringSQI Entering AIR TemperatureCooling Performance Data CondensingID WB F 21.7 MV12B FC/MC43B MV16C FC/MC43C ID WB F 34.5 MV20D FC/MC62D Condensing Unit Model NO. YHJF48S41S1 Indoor Coil Model no MV20D FC/MC62D Cooling Performance Data LOW CFM 1-STAGE OperationHigh CFM Cooling Performance Data High CFM 2-STAGE OperationMBH COP Heating Performance DataEntering Outdoor Unit Indoor CoilYTG-B-0509 27.4 1200 1400 1600 1600 1800 MBH COP MV20D FC/MC62D