HEATING PERFORMANCE DATA |
|
|
|
|
|
|
|
|
| |
CONDENSING UNIT MODEL NO | YHJF36S41S1 |
|
|
|
|
|
|
| ||
EVAPORATOR COIL MODEL NO | AHX36 |
|
|
|
|
|
|
|
| |
AIR TEMP. | AIR TEMP. |
|
|
|
| ID CFM |
|
|
|
|
ENTERING | ENTERING |
| 1000 |
|
| 1200 |
|
| 1400 |
|
OUTDOOR UNIT | INDOOR COIL |
|
|
|
|
|
|
|
|
|
MBTUH | KW | C.O.P. | MBTUH | KW | C.O.P. | MBTUH | KW | C.O.P. | ||
|
|
|
|
|
|
|
|
|
|
|
| 60 | 47.2 | 4.2 | 2.9 | 47.9 | 4.4 | 2.7 | 48.6 | 4.6 | 2.6 |
60 |
|
|
|
|
|
|
|
|
|
|
70 | 46.3 | 3.7 | 3.3 | 46.8 | 3.9 | 3.1 | 47.3 | 4.1 | 2.9 | |
|
|
|
|
|
|
|
|
|
|
|
| 80 | 45.3 | 3.3 | 3.7 | 45.6 | 3.4 | 3.4 | 46.0 | 3.6 | 3.2 |
|
|
|
|
|
|
|
|
|
|
|
| 60 | 40.0 | 3.7 | 2.8 | 40.4 | 3.8 | 2.7 | 40.9 | 4.0 | 2.5 |
47 |
|
|
|
|
|
|
|
|
|
|
70 | 39.5 | 3.3 | 3.2 | 39.8 | 3.4 | 3.0 | 40.1 | 3.5 | 2.8 | |
|
|
|
|
|
|
|
|
|
|
|
| 80 | 38.9 | 2.9 | 3.5 | 39.2 | 3.0 | 3.3 | 39.4 | 3.2 | 3.2 |
|
|
|
|
|
|
|
|
|
|
|
| 60 | 36.8 | 3.5 | 2.7 | 37.0 | 3.6 | 2.6 | 37.2 | 3.7 | 2.5 |
40 |
|
|
|
|
|
|
|
|
|
|
70 | 36.3 | 3.1 | 3.1 | 36.4 | 3.2 | 2.9 | 36.6 | 3.3 | 2.8 | |
|
|
|
|
|
|
|
|
|
|
|
| 80 | 35.7 | 2.7 | 3.5 | 35.9 | 2.8 | 3.3 | 36.0 | 2.9 | 3.1 |
|
|
|
|
|
|
|
|
|
|
|
| 60 | 31.9 | 3.1 | 2.7 | 32.0 | 3.1 | 2.5 | 32.1 | 3.2 | 2.4 |
30 |
|
|
|
|
|
|
|
|
|
|
70 | 31.5 | 2.7 | 3.1 | 31.6 | 2.8 | 2.9 | 31.7 | 2.9 | 2.7 | |
|
|
|
|
|
|
|
|
|
|
|
| 80 | 31.0 | 2.4 | 3.4 | 31.2 | 2.5 | 3.2 | 31.4 | 2.6 | 3.1 |
|
|
|
|
|
|
|
|
|
|
|
| 60 | 25.3 | 2.6 | 2.5 | 25.4 | 2.6 | 2.4 | 25.4 | 2.6 | 2.3 |
17 |
|
|
|
|
|
|
|
|
|
|
70 | 24.2 | 2.2 | 2.9 | 24.7 | 2.3 | 2.8 | 25.2 | 2.3 | 2.6 | |
|
|
|
|
|
|
|
|
|
|
|
| 80 | 23.1 | 1.9 | 3.2 | 24.1 | 2.0 | 3.1 | 25.0 | 2.1 | 3.0 |
|
|
|
|
|
|
|
|
|
|
|
| 60 | 21.6 | 2.3 | 2.3 | 20.9 | 2.3 | 2.3 | 20.2 | 2.2 | 2.2 |
10 |
|
|
|
|
|
|
|
|
|
|
70 | 21.4 | 2.0 | 2.7 | 20.3 | 2.0 | 2.6 | 19.2 | 1.9 | 2.5 | |
|
|
|
|
|
|
|
|
|
|
|
| 80 | 21.1 | 1.8 | 3.1 | 19.6 | 1.7 | 2.9 | 18.2 | 1.6 | 2.7 |
NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.
Multipliers for determining the performance with other indoor sections.
Air Handler | Coil | MBH | KW | COP |
AHX42 | – | 1.00 | 1.01 | 0.99 |
AV*36 | – | 1.00 | 0.99 | 1.01 |
F6FP042 | – | 1.00 | 1.02 | 0.98 |
MV12B | FC/MC43B | 1.00 | 0.98 | 1.02 |
MV16C | FC/MC43C | 1.00 | 0.98 | 1.02 |
Furnace | Coil | MBH | KW | COP |
T*(8,L)X*A12 | FC/MC/PC37A | 1.00 | 1.00 | 1.00 |
T*(8,L)X*B12 | FC/MC/PC43B | 1.00 | 1.00 | 1.00 |
T*(8,L)X*C16 | FC/MC/PC43C | 1.00 | 0.99 | 1.01 |
T*(8,L)X*C20 | FC/MC/PC43C | 1.00 | 1.02 | 0.98 |
T*9X*B12 | FC/MC/PC43B | 1.00 | 1.00 | 1.00 |
T*9X*C16 | FC/MC/PC43C | 1.00 | 1.01 | 0.99 |
T*9X*C20 | FC/MC/PC43C | 1.00 | 0.98 | 1.02 |
Y*(8,L)C*C16 | FC/MC/PC43C | 1.00 | 0.98 | 1.02 |
Y*(8,L)C*C20 | FC/MC/PC43C | 1.00 | 0.98 | 1.02 |
(Y*9C/T*9V)*C16 | FC/MC/PC43C | 1.00 | 0.99 | 1.01 |
(Y*9C/T*9V)*C20 | FC/MC/PC43C | 1.00 | 0.97 | 1.03 |
Johnson Controls Unitary Products | 23 |