York YHJF18 THRU 60 warranty Heating Performance Data, Entering, Outdoor Unit Indoor Coil, Mbh Cop

Page 20

510667-YTG-B-0509

HEATING PERFORMANCE DATA

CONDENSING UNIT MODEL NO

YHJF18S41S1

 

 

 

 

 

 

 

EVAPORATOR COIL MODEL NO

AHX30

 

 

 

 

 

 

 

 

AIR TEMP.

AIR TEMP.

 

 

 

 

ID CFM

 

 

 

 

ENTERING

ENTERING

 

450

 

 

600

 

 

750

 

OUTDOOR UNIT

INDOOR COIL

 

 

 

 

 

 

 

 

 

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

MBTUH

KW

C.O.P.

 

 

 

 

 

 

 

 

 

 

 

 

60

21.1

4.1

1.3

22.2

4.5

1.2

23.3

4.9

1.1

60

 

 

 

 

 

 

 

 

 

 

70

20.5

3.6

1.5

21.6

4.0

1.4

22.6

4.3

1.3

 

 

 

 

 

 

 

 

 

 

 

 

80

19.9

3.2

1.6

20.9

3.5

1.5

21.9

3.9

1.4

 

 

 

 

 

 

 

 

 

 

 

 

60

18.6

3.8

1.3

19.2

4.0

1.2

19.8

4.2

1.1

47

 

 

 

 

 

 

 

 

 

 

70

17.7

3.3

1.4

18.4

3.5

1.3

19.1

3.7

1.2

 

 

 

 

 

 

 

 

 

 

 

 

80

16.8

2.8

1.6

17.6

3.1

1.5

18.4

3.3

1.4

 

 

 

 

 

 

 

 

 

 

 

 

60

16.7

3.4

1.3

17.3

3.6

1.2

17.9

3.8

1.1

40

 

 

 

 

 

 

 

 

 

 

70

16.1

3.0

1.4

16.8

3.2

1.3

17.4

3.4

1.2

 

 

 

 

 

 

 

 

 

 

 

 

80

15.6

2.7

1.5

16.3

2.9

1.4

17.0

3.1

1.3

 

 

 

 

 

 

 

 

 

 

 

 

60

14.6

3.1

1.2

15.1

3.2

1.2

15.5

3.4

1.1

30

 

 

 

 

 

 

 

 

 

 

70

14.2

2.7

1.4

14.6

2.9

1.3

15.0

3.0

1.2

 

 

 

 

 

 

 

 

 

 

 

 

80

13.7

2.4

1.5

14.1

2.5

1.4

14.4

2.6

1.3

 

 

 

 

 

 

 

 

 

 

 

 

60

11.7

2.6

1.2

12.0

2.6

1.1

12.3

2.7

1.1

17

 

 

 

 

 

 

 

 

 

 

70

11.2

2.2

1.3

11.6

2.3

1.2

11.9

2.4

1.2

 

 

 

 

 

 

 

 

 

 

 

 

80

10.8

2.0

1.5

11.1

2.0

1.4

11.5

2.1

1.3

 

 

 

 

 

 

 

 

 

 

 

 

60

10.1

2.3

1.1

10.3

2.3

1.1

10.4

2.3

1.0

10

 

 

 

 

 

 

 

 

 

 

70

9.6

1.9

1.3

9.9

2.0

1.2

10.2

2.1

1.2

 

 

 

 

 

 

 

 

 

 

 

 

80

9.1

1.7

1.4

9.5

1.8

1.4

9.9

1.9

1.3

NOTE: ALL CAPACITIES ARE NET (KBTUH) WITH INDOOR FAN HEAT ALREADY DEDUCTED AT 1250 BTUH/1000 CFM.

Multipliers for determining the performance with other indoor sections.

Air Handler

Coil

MBH

KW

COP

AV*36

1.00

1.03

0.97

MV12B

FC/MC35B

1.00

0.97

1.03

MV12B

FC/MC43B

1.00

1.01

0.99

Furnace

Coil

MBH

KW

COP

T*(8,L)X*A12

FC/MC/PC32A

0.99

0.99

1.00

Y*(8,L)C*A12

FC/MC/PC32A

1.00

0.97

1.03

Y*(8,L)C*B12

FC/MC/PC35B

1.00

0.99

1.01

Y*(8,L)C*C16

FC/MC/PC35C

1.00

0.98

1.02

(Y*9C/T*9V)*B12

FC/MC/PC35B

1.00

0.98

1.02

(Y*9C/T*9V)*C16

FC/MC/PC35C

1.00

0.99

1.01

Y*(8,L)C*A12

FC/MC/PC37A

1.00

1.01

0.99

Y*(8,L)C*B12

FC/MC/PC43B

1.00

0.98

1.02

20

Johnson Controls Unitary Products

Image 20
Contents Description WarrantyFeatures Physical and Electrical Data ModelFootnotes ProceduresSystem Charge for Various Matched Systems Cooling Capacity With Air Handler Coils SensMV Variable Speed SpeedCooling Capacity With High Efficiency Motor Furnaces Unit Model Furnace Coil MODEL1 Stage Cooling RatedSeer EER CFM Unit FurnaceCooling Model MODEL1 Stage Rated Heating Performance With Air Handler Heating Capacity With Air Handler CoilsWith Variable Speed FURNACES3 Heating Capacity With High Efficiency Motor FurnacesModel Furnace COIL1 ARI HEATING2 Hspf Model Furnace COIL1 ARI HEATING2 Accessories Seer HP with Variable Speed FURNACES3SQI Typical InstallationTypical Field Wiring Temperature Cooling Performance DataCondensing Entering AIRID WB F 21.7 MV12B FC/MC43B MV16C FC/MC43C ID WB F 34.5 MV20D FC/MC62D Condensing Unit Model NO. YHJF48S41S1 Indoor Coil Model no Cooling Performance Data LOW CFM 1-STAGE Operation MV20D FC/MC62DCooling Performance Data High CFM 2-STAGE Operation High CFMHeating Performance Data EnteringOutdoor Unit Indoor Coil MBH COPYTG-B-0509 27.4 1200 1400 1600 1600 1800 MBH COP MV20D FC/MC62D