Toshiba RAV-SM1106BT-TR, RAV-SM406BT-TR Operation of diagnostic function Judgment and measures

Page 45

Error mode detected by remote controller or central controller (TCC-LINK)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation of diagnostic function

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Judgment and measures

 

 

 

Check code

Cause of operation

Status of

Condition

 

 

 

 

 

 

 

 

 

air conditioner

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply error of remote controller, Indoor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EEPROM error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check remote controller inter-unit wiring.

 

Not displayed at all

No communication with master indoor unit

 

 

2.

Check remote controller.

 

 

 

 

 

• Remote controller wiring is not correct.

 

 

3.

Check indoor power wiring.

 

(Operation on

Stop

 

 

 

remote controller

• Power of indoor unit is not turned on.

4.

Check indoor P.C. board.

 

 

 

 

is impossible.)

 

 

 

 

• Automatic address cannot be completed.

 

 

5.

Check indoor EEPROM.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(including socket insertion)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Automatic address repeating phenom-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

enon generates.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No communication with master indoor unit

Stop

 

Receiving error from remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check remote controller inter-unit wiring.

 

 

 

 

 

 

E01

• Disconnection of inter-unit wire between

(Automatic reset)

Displayed when

 

 

 

 

 

 

2.

Check remote controller.

 

 

 

 

 

 

2

remote controller and master indoor unit

If center exists,

error is detected

 

 

 

 

 

 

3.

Check indoor power wiring.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Detected by remote controller side)

operation continues.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4.

Check indoor P.C. board.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

Sending error of remote controller

 

 

 

 

 

 

E02

Signal send error to indoor unit

(Automatic reset)

Displayed when

1. Check sending circuit inside of remote

 

 

 

 

 

 

 

 

 

 

 

 

 

(Detected by remote controller side)

If center exists,

error is detected

 

controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

operation continues.

 

 

Replace remote controller.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Stop

 

1.

In 2-remote controllers (including wireless),

 

 

 

 

 

 

E09

There are multiple main remote controllers.

Displayed when

 

there are multiple main units.

 

 

 

 

 

 

(Sub unit

 

 

 

 

 

 

 

(Detected by remote controller side)

error is detected

 

Check that there are 1 main remote

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

continues operation.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

controller and other sub remote controllers.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

L20

Duplicated indoor central addresses on

Stop

Displayed when

1.

Check setting of central control system

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

network address. (Network adapter SW01)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

communication of central control system

 

 

Central controller

(Automatic reset)

error is detected

2.

Check network adapter P.C. board.

 

(Detected by indoor/central controller side)

 

 

 

 

 

 

 

 

 

L20

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.

Check communication wire / miswiring

 

 

 

 

 

 

3

 

 

 

2.

Check communication (U3, U4 terminals)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Communication circuit error of central

Continues

Displayed when

3.

Check network adapter P.C. board.

 

Central controller

 

control system

4. Check central controller (such as central

 

 

 

 

 

(Send)

(By remote controller)

error is detected

 

 

 

 

 

(Detected by central controller side)

 

 

 

 

 

 

C05

 

 

 

control remote controller, etc.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5.

Check terminal resistance. (TCC-LINK)

 

 

 

 

(Receive)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

C06

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor Gr sub unit error

Continuation/Stop

Displayed when

Check the check code of the corresponding

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(According

 

Central controller

(Detected by central controller side)

error is detected

unit from remote controller.

 

to each case)

 

 

 

 

 

 

P30

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2 The check code cannot be displayed by the wired remote controller. (Usual operation of air conditioner becomes unavailable.)

For the wireless models, an error is notified with indication lamp.

3 This trouble is related to communication of remote controller (A, B), central system (TCC-LINK U3, U4), and [E01], [E02], [E03], [E09] or [E18] is displayed or no check display on the remote controller according to the contents.

– 45 –

Image 45
Contents Split Type Contents 11-2 11-111-3 11-4Original instruction Explanation of illustrated marks Explanation of indicationsWork undertaken Protective gear worn Indication ExplanationElectrical Shock Hazard Confirmation of warning label on the main unitWithout first conducting these checks Service person is allowed to do this workProceeding with the repair work DischargedProtective gloves and safety work clothing Procedure in the ladders instructionsTelephone wires Electric shocks, electrical leakage, smoking and/or a fireWires as before Never recover the refrigerant into the outdoor unitRefrigerant gas may catch fire Do not use a welder in the closed roomBefore opening the service panel Service panelThough the refrigerant gas itself is innocuous Refrigerant leaksPage Explanations given to user RelocationDeclaration of Conformity Specifications Copper pipe Piping Safety Caution Concerned to New RefrigerantFlare nut JointGeneral tools Conventional tools can be used ToolsSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Concealed Duct Type Parts name Type SpecificationsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramIndoor unit #1 Heder Wireless remote controller Case of Connection of Wireless Remote ControllerLCD Outline of specifications Remarks Temperature in heating Setting at shipmentRoom temp. control Heat Tc ≥ 60C, the fan speed increases by 1 step TemperatureFan speed control Outline of specificationsHeating ready is RemarksTcn TcjTc n ConditionsMode when Setup at shipmentSetup temperature on Room temp. monitorCase of wireless remote controller Case of wired remote controllerCentral Goes onValues of various sensors Conditioner may stop or an error code may be displayed When validating the save operation, the next operation Pushed for 4 seconds or more on the remote controllerStarts with save operation valid because contents are This function is set up at the customer’s sideMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Before troubleshooting Summary of TroubleshootingTroubleshooting procedure Wired remote controller typeWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Remote controller detected Indoor unit detectedCentral control devices detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures E09 error Check code E01 errorE10 error E04 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller F10 error P10 errorCN333 CN334 P12 errorCheck by tester P19 errorExchange to cooling cycle Exchange to heating cycleF01 error F02 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit TA, TC, TCJ, TE, TS, to sensor Temperature Resistance value characteristic tableTD, TL sensor TD, TL sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresC. Board for indoor unit servicing replacement procedures Setting data read out from EepromContents Code No. required at leastRefer to table Button for the temperature setting Writing the setting data to EepromEeprom layout diagram Setting data Type Setting data Type Type name abbType Code No Model Name RAV-SM∗∗∗BT-ETRTest Run Setup on Remote Controller Wired remote controller Wiress remote controllerIndoor Unit Practical operation LED Display on Indoor P.C. Board D501 RedD403 Red Using the set temperature Function Selection SetupTo change the selected indoor unit, proceed to Procedure To change item to be set up, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment When connected 2 remote controllers operate an idoor unit Wireless remote controllerWhen connected 2 remote controllers operate the twin Remote controller address A-B selection settingWireless remote controller B setup Wireless remote controller A-B selectionContents Order to monitor another error history, push the set „ Calling of error history ContentsTemperature Buttons to change the error Pushing„ Indoor unit power-ON sequence Initial communicationUsual regular communication Model connection interface wiring connection Microprocessor block diagramModel Connection Interface TCC-LINK adapter Model name TCB-PCNT30TLE2C. Board Switch SW01 Setup Wiring SpecificationsUse 2-core with no polar wire To prevent noise trouble, use 2-core shield wireExternal view of P.C. board assembly How to set up from indoor unit side by remote controllerAddress setup Push Test + Vent buttons for 4 seconds or morePage Address setup procedure Address SetupAddress Setup & Group Control Terminology System configurationSingle Triple Single group operationIt is not influenced by the line 2 or 3 address indoor unit ExampleOnly turning on source power supply Automatic completion Automatic Address Example from Unset Address No miswiringStandard One outdoor unit Multiple groups operationPush SET + CL + Test buttons Using timer time Buttons, set the line addressSimultaneously for 4 seconds or more Folloer unit PushTo know the position of indoor unit body by address ProcedureButton if the unit stops Fan and louver of the selected indoor unit only operatePart name Procedure Remarks DetachmentAttachment Electric parts Suction panelCover from the projection of the side plate Then remove the coverBox Control P.CBoard Fan motor Remove connectors for fan motor wiringFrom control P.C. board Match the fan motor with turning directionDrain pan Float switchDrain pump AttachmentHeat Position and fix it as before, using screwsPerform works of 1 Set the heat exchanger at the originalRAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E SM456BT-E SM566BT-E Location Description Model Name RAVRAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR SM406BT-E SM456BT-E SM566BT-E Location Model Name RAV DescriptionRAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR 100101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation

RAV-SM456BT-E, RAV-SM566BT-TR, RAV-SM566BT-E, RAV-SM456BT-TR, RAV-SM806BT-E specifications

Toshiba has long been recognized as a leader in air conditioning technology, and their latest models, including the RAV-SM806BT-E, RAV-SM566BT-TR, RAV-SM1106BT-E, RAV-SM456BT-E, and RAV-SM1406BT-E, are prime examples of innovation in climate control solutions. These models combine energy efficiency, advanced technology, and user-friendly features to meet diverse cooling and heating needs for both residential and commercial spaces.

The RAV-SM806BT-E is notable for its impressive cooling and heating capabilities, making it suitable for larger areas. With a robust cooling capacity of 8.0 kW, this model is equipped with inverter technology, providing variable speed control that optimizes energy consumption while ensuring consistent comfort levels. Its quiet operation makes it ideal for settings where noise control is crucial, such as offices and bedrooms.

Similarly, the RAV-SM566BT-TR offers a balanced solution for medium-sized environments. With a capacity of 5.6 kW, it features advanced air filtration systems that enhance indoor air quality by removing dust, allergens, and pollutants. This model is particularly appreciated in regions with high air pollution levels, providing a healthier living or working environment.

The RAV-SM1106BT-E stands out for its high efficiency and eco-friendly refrigerant use. This model is designed to reduce greenhouse gas emissions while delivering significant cooling output, making it a responsible choice for environmentally conscious consumers. Additionally, Toshiba’s smart temperature control technology allows users to precisely manage their climate settings through a user-friendly remote control or smartphone app, offering convenience and ease of use.

For those looking for a compact yet powerful solution, the RAV-SM456BT-E is designed to fit smaller spaces without sacrificing performance. With a cooling capacity of 4.5 kW, it still utilizes sophisticated inverter technology, ensuring minimal energy loss and optimal heating and cooling efficiency. Its compact design allows for flexible installations in varied spaces.

Lastly, the RAV-SM1406BT-E model emphasizes versatility and performance. With a cooling capacity of 14.0 kW, it is designed for larger commercial spaces, delivering powerful climate control while maintaining energy efficiency. Its advanced multi-zone system allows simultaneous operation across different areas, adapting to the unique requirements of each zone.

In summary, Toshiba's RAV-SM series reflects the company's commitment to innovation, energy efficiency, and user comfort. Each model offers unique features tailored to specific needs, setting new standards in the air conditioning industry. Whether for residential or commercial use, these systems provide reliable performance while promoting sustainable practices.