Toshiba RAV-SM406BT-TR, RAV-SM1406BT-E P19 error, Check by tester, Exchange to cooling cycle

Page 52

[P19 error]

Is operation of 4-way valve normal? NO (Check the pipe temp., etc.

during cooling/heating operation.

YES

Are 1.3 to 1.6kΩ applied to

NO

 

 

 

Replace 4-way valve coil.

 

 

 

 

 

resistance value of 4-way valve coil ?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

YES

Defective

Check temperature sensors.

TE sensor TS sensor Indoor TC sensor

Defective Correct, replace

Check outdoor P.C. board operation.

(See the following description.)

OK

Check 4-way valve.

Defective Replace

Check outdoor P.C. board.

Defective Replace

Operation check direction of the outdoor P.C. board (In case of self-preservation valve)

1)Set the Dip switch SW804 as same as the following table and push SW801 for approx. 1 second. It enables you to check the exchange operation to cooling cycle or heating cycle.

Only for approx. 10 seconds, the power is turned on.

As the heat value of part (coil: resistance R700) is large, when checking the operation continuously, wait 1 minute or more until the next check. (There is no problem if a coil is not connected.)

2)After check, turn off all the Dip switches SW804.

Exchange to cooling cycle

SW804

SW801

CN701

 

4

 

1

 

3

 

 

 

2

Push

 

ON

1

4

 

 

 

DC180V or more

Exchange to heating cycle

SW804

SW801

CN701

 

4

 

1

 

3

 

 

 

2

Push

 

ON

1

4

 

 

 

DC180V or more

Check by tester

Analog tester: Good article if over DC180V

Digital tester: Although in some cases, the value varied and indicated. If the maximum value is DC180V or more, it is good article.

– 52 –

Image 52
Contents Split Type Contents 11-1 11-211-3 11-4Original instruction Explanation of indications Explanation of illustrated marksWork undertaken Protective gear worn Indication ExplanationConfirmation of warning label on the main unit Electrical Shock HazardService person is allowed to do this work Without first conducting these checksProceeding with the repair work DischargedProcedure in the ladders instructions Protective gloves and safety work clothingTelephone wires Electric shocks, electrical leakage, smoking and/or a fireNever recover the refrigerant into the outdoor unit Wires as beforeRefrigerant gas may catch fire Do not use a welder in the closed roomService panel Before opening the service panelThough the refrigerant gas itself is innocuous Refrigerant leaksPage Relocation Explanations given to userDeclaration of Conformity Specifications Safety Caution Concerned to New Refrigerant Copper pipe PipingFlare nut JointTools General tools Conventional tools can be usedSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Parts name Type Specifications Concealed Duct TypeIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Indoor unit #1 Heder Wireless remote controllerLCD Outline of specifications Remarks Setting at shipment Temperature in heatingRoom temp. control Tc ≥ 60C, the fan speed increases by 1 step Temperature HeatOutline of specifications Fan speed controlHeating ready is RemarksTcj TcnTc n ConditionsSetup at shipment Mode whenSetup temperature on Room temp. monitorCase of wired remote controller Case of wireless remote controllerGoes on CentralValues of various sensors Conditioner may stop or an error code may be displayed Pushed for 4 seconds or more on the remote controller When validating the save operation, the next operationStarts with save operation valid because contents are This function is set up at the customer’s sideMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Summary of Troubleshooting Before troubleshootingTroubleshooting procedure Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Indoor unit detected Remote controller detectedCentral control devices detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures Check code E01 error E09 errorE04 error E10 errorE08, L03, L07, L08 error E18 errorL09 error L30 error L20 error P30 error Central controller P10 error F10 errorP12 error CN333 CN334P19 error Check by testerExchange to cooling cycle Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface F29 error E03 error Master indoor unitP31 error Follower indoor unit Temperature Resistance value characteristic table TA, TC, TCJ, TE, TS, to sensorTD, TL sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseSetting data read out from Eeprom C. Board for indoor unit servicing replacement proceduresContents Code No. required at leastWriting the setting data to Eeprom Refer to table Button for the temperature settingEeprom layout diagram Setting data Type Type name abb Setting data TypeType Code No Model Name RAV-SM∗∗∗BT-ETRWiress remote controller Test Run Setup on Remote Controller Wired remote controllerIndoor Unit LED Display on Indoor P.C. Board D501 Red Practical operationD403 Red Function Selection Setup Using the set temperatureTo change the selected indoor unit, proceed to Procedure To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment Wireless remote controller When connected 2 remote controllers operate an idoor unitWhen connected 2 remote controllers operate the twin Remote controller address A-B selection settingWireless remote controller A-B selection Wireless remote controller B setupContents „ Calling of error history Contents Order to monitor another error history, push the setTemperature Buttons to change the error PushingInitial communication „ Indoor unit power-ON sequenceUsual regular communication Microprocessor block diagram Model connection interface wiring connectionModel Connection Interface TCC-LINK adapter Model name TCB-PCNT30TLE2Wiring Specifications C. Board Switch SW01 SetupUse 2-core with no polar wire To prevent noise trouble, use 2-core shield wireHow to set up from indoor unit side by remote controller External view of P.C. board assemblyAddress setup Push Test + Vent buttons for 4 seconds or morePage Address Setup Address setup procedureSystem configuration Address Setup & Group Control TerminologySingle Triple Single group operationExample It is not influenced by the line 2 or 3 address indoor unitAutomatic Address Example from Unset Address No miswiring Only turning on source power supply Automatic completionStandard One outdoor unit Multiple groups operationUsing timer time Buttons, set the line address Push SET + CL + Test buttonsSimultaneously for 4 seconds or more Folloer unit PushProcedure To know the position of indoor unit body by addressButton if the unit stops Fan and louver of the selected indoor unit only operateDetachment Part name Procedure RemarksAttachment Suction panel Electric partsCover from the projection of the side plate Then remove the coverControl P.C BoxBoard Remove connectors for fan motor wiring Fan motorFrom control P.C. board Match the fan motor with turning directionFloat switch Drain panDrain pump AttachmentPosition and fix it as before, using screws HeatPerform works of 1 Set the heat exchanger at the originalRAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E Location Description Model Name RAV SM456BT-E SM566BT-ERAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR Location Model Name RAV Description SM406BT-E SM456BT-E SM566BT-ERAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E 100 RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation