Toshiba RAV-SM806BT-E, RAV-SM406BT-TR, RAV-SM1406BT-E, RAV-SM1606BT-E E04 error, E10 error

Page 47

[E04 error]

NO

Does outdoor operate?

YES

Is group address setup of

NO

 

Check CODE No. [14].

 

 

 

 

 

 

remote controller correct?

 

 

 

 

 

 

 

 

 

 

 

 

YES

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Are wiring in indoor unit and

NO

 

 

1, 2, 3 inter-unit cables correct?

 

 

 

YES

 

 

 

 

 

 

 

 

 

Correct wiring and

inter-unit cables.

Are wirings of terminal blocks (1, 2, 3) wired to CN67 normal?

YES

Does the voltage

NO

Correct wiring of connector

and terminal blocks.

between 2 and 3 of the indoor unit NO inter-unit terminal blocks

(1, 2, 3) vary?

Check indoor P.C. board

(MCC-1631).

Defect Replace

Check indoor P.C. board.

Defect Replace

As shown in the following figure,

carry out measurement within 20 seconds after the power was turned on.

S5277G

Black

3

White

2

1

Terminal block

Check outdoor P.C. board.

Defect Replace

[E10 error]

YES

Is there no disorder of power supply?

NO

Check indoor control P.C. board

(MCC-1631).

Defect Replace

Check power supply voltage.

Correct lines.

Check and eliminate noise, etc.

– 47 –

Image 47
Contents Split Type Contents 11-4 11-111-2 11-3Original instruction Indication Explanation Explanation of indicationsExplanation of illustrated marks Work undertaken Protective gear wornElectrical Shock Hazard Confirmation of warning label on the main unitDischarged Service person is allowed to do this workWithout first conducting these checks Proceeding with the repair workElectric shocks, electrical leakage, smoking and/or a fire Procedure in the ladders instructionsProtective gloves and safety work clothing Telephone wiresDo not use a welder in the closed room Never recover the refrigerant into the outdoor unitWires as before Refrigerant gas may catch fireRefrigerant leaks Service panelBefore opening the service panel Though the refrigerant gas itself is innocuousPage Declaration of Conformity Explanations given to userRelocation Specifications Joint Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Concealed Duct Type Parts name Type SpecificationsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramIndoor unit #1 Heder Wireless remote controller Case of Connection of Wireless Remote ControllerLCD Outline of specifications Remarks Room temp. control Temperature in heatingSetting at shipment Heat Tc ≥ 60C, the fan speed increases by 1 step TemperatureRemarks Outline of specificationsFan speed control Heating ready isConditions TcjTcn Tc nRoom temp. monitor Setup at shipmentMode when Setup temperature onCase of wireless remote controller Case of wired remote controllerValues of various sensors CentralGoes on Conditioner may stop or an error code may be displayed This function is set up at the customer’s side Pushed for 4 seconds or more on the remote controllerWhen validating the save operation, the next operation Starts with save operation valid because contents areMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Wired remote controller type Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Central control devices detected Remote controller detectedIndoor unit detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unit Operation of diagnostic function Check Status Operation of diagnostic function Judgment and measures E09 error Check code E01 errorE10 error E04 errorL09 error E18 errorE08, L03, L07, L08 error P30 error Central controller L20 errorL30 error F10 error P10 errorCN333 CN334 P12 errorExchange to heating cycle P19 errorCheck by tester Exchange to cooling cycleF01 error F02 errorC06 error 11 model connection interface P31 error Follower indoor unit E03 error Master indoor unitF29 error TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresCode No. required at least Setting data read out from EepromC. Board for indoor unit servicing replacement procedures ContentsRefer to table Button for the temperature setting Writing the setting data to EepromEeprom layout diagram Model Name RAV-SM∗∗∗BT-ETR Setting data Type Type name abbSetting data Type Type Code NoIndoor Unit Test Run Setup on Remote Controller Wired remote controllerWiress remote controller D403 Red Practical operationLED Display on Indoor P.C. Board D501 Red To change item to be set up, proceed to Procedure Function Selection SetupUsing the set temperature To change the selected indoor unit, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment Remote controller address A-B selection setting Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit When connected 2 remote controllers operate the twinWireless remote controller B setup Wireless remote controller A-B selectionContents Pushing „ Calling of error history ContentsOrder to monitor another error history, push the set Temperature Buttons to change the errorUsual regular communication „ Indoor unit power-ON sequenceInitial communication Model name TCB-PCNT30TLE2 Microprocessor block diagramModel connection interface wiring connection Model Connection Interface TCC-LINK adapterTo prevent noise trouble, use 2-core shield wire Wiring SpecificationsC. Board Switch SW01 Setup Use 2-core with no polar wirePush Test + Vent buttons for 4 seconds or more How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Address setupPage Address setup procedure Address SetupTriple Single group operation System configurationAddress Setup & Group Control Terminology SingleIt is not influenced by the line 2 or 3 address indoor unit ExampleMultiple groups operation Automatic Address Example from Unset Address No miswiringOnly turning on source power supply Automatic completion Standard One outdoor unitFolloer unit Push Using timer time Buttons, set the line addressPush SET + CL + Test buttons Simultaneously for 4 seconds or moreFan and louver of the selected indoor unit only operate ProcedureTo know the position of indoor unit body by address Button if the unit stopsAttachment Part name Procedure RemarksDetachment Then remove the cover Suction panelElectric parts Cover from the projection of the side plateBoard BoxControl P.C Match the fan motor with turning direction Remove connectors for fan motor wiringFan motor From control P.C. boardAttachment Float switchDrain pan Drain pumpSet the heat exchanger at the original Position and fix it as before, using screwsHeat Perform works of 1RAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E SM456BT-E SM566BT-E Location Description Model Name RAVRAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR SM406BT-E SM456BT-E SM566BT-E Location Model Name RAV DescriptionRAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR 100101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation