4.Wiring Specifications

Use 2-core with no polar wire.

Match the length of wire to wire length of the central control system. If mixed in the SMMS system, the wire length is lengthened with all indoor/outdoor inter-unit wire length at side.

To prevent noise trouble, use 2-core shield wire.

No. of wires

Size

2Up to 1000m: twisted wire 1.25mm2

Up to 2000m: twisted wire 2.0mm2

Connect the shield wire by closed-end connection and apply open process (insulating process) to the last terminal. Ground the earth wire to 1 point at indoor unit side. (In case of central controlling of digital inverter (DI, SDI) unit setup)

CAUTION

1)Closed-end connection of shield wire (Connect all the connecting parts of each indoor unit)

2)Apply open process to the last terminal (insulating process).

Central control device

U1 U2

3) Ground earth wire to 1 point at indoor unit side.

Caution 2

Outdoor unit

1 2 3

Indoor unit U3 U4 1 2 3

A B

Remote controller

Caution 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Central control system wiring

 

 

Caution 3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

: 1:1 model connection

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

interface

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(TCC-LINK adapter)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(This option)

 

 

 

 

 

 

 

 

 

 

 

Header

unit

 

Follower unit

 

 

 

 

 

 

Follower unit

 

 

 

 

 

Header unit

 

 

 

 

 

 

 

 

Follower unit

 

 

 

 

 

 

 

 

 

 

 

U3

U4

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

 

 

1

 

2

 

3

 

 

 

U3

U4

 

1

 

2

3

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Earth screw

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

 

Remote controller

 

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Group operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Triple operation)

 

 

 

 

 

 

 

 

 

 

 

 

 

5.P.C. Board Switch (SW01) Setup

When performing collective control by customized setup only, the setup of terminator is necessary.

Using SW01, set up the terminator.

Set up the terminator to only the interface connected to the indoor unit of least line address No.

Central control device

U1 U2

U3 U4

Central control device

U1 U2

U3 U4

Central control devices: Max. 10 units

Refrigerant line 1

Outdoor unit

Refrigerant line 2

Refrigerant line 3

Refrigerant line 4

1 2 3

Indoor unit U3 U4 1 2 3

A B

1:1 model connection interface

(TCC-LINK adapter) ( This product ) sold separately

Remote controller

 

1

2

3

 

 

Header

 

 

unit

U3 U4

1

2

3

A B

Remote controller

 

1

2

3

 

 

 

1

2

3

 

 

Followerunit

 

 

 

 

Follower unit

 

 

 

 

 

1

 

2

 

3

 

 

 

1

 

2

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

A

B

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller wiring

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Remote controller

 

Remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Indoor/outdoor inter-unit wire (AC230V serial) Central control system wiring

 

 

 

 

 

 

 

 

 

 

* Wiring for No.1 and 2 only

 

 

 

 

 

 

 

 

 

Header unit

 

 

Follower

 

 

 

 

 

 

 

 

 

 

 

unit

 

U3 U4

 

1

 

2

3

 

 

 

1

2

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

A B

 

 

 

 

 

 

A B

 

 

 

 

Remote controller

 

 

 

 

 

Group operation (Max. 8 units)

Twin/Triple operation (Example of triple)

 

 

 

 

 

 

 

 

 

 

 

Line address

 

1

 

 

2

 

 

4

 

SW01 Bit 1

 

ON

 

OFF

 

 

OFF

(OFF at shipment from factory)

SW01 Bit 2

 

OFF

 

OFF

 

 

OFF

(OFF at shipment from factory)

Remarks

Turn SW01 Bit 1 to ON.

 

As status shipped from factory

 

As status shipped from factory

 

(Reference) Setup contents of switch

 

 

 

 

 

 

 

SW01

 

Terminator

 

 

Remarks

 

 

Bit 1

Bit 1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OFF

OFF

 

 

None

 

Mixed with SMMS (Link wiring) at shipment from factory

 

ON

OFF

 

 

100Ω

 

Central control by digital inverter only

 

 

OFF

ON

 

 

75Ω

 

Spare

 

 

ON

ON

 

 

43Ω

 

Spare

 

 

– 74 –

Image 74
Contents Split Type Contents 11-3 11-111-2 11-4Original instruction Work undertaken Protective gear worn Explanation of indicationsExplanation of illustrated marks Indication ExplanationConfirmation of warning label on the main unit Electrical Shock HazardProceeding with the repair work Service person is allowed to do this workWithout first conducting these checks DischargedTelephone wires Procedure in the ladders instructionsProtective gloves and safety work clothing Electric shocks, electrical leakage, smoking and/or a fireRefrigerant gas may catch fire Never recover the refrigerant into the outdoor unitWires as before Do not use a welder in the closed roomThough the refrigerant gas itself is innocuous Service panelBefore opening the service panel Refrigerant leaksPage Declaration of Conformity Explanations given to userRelocation Specifications Flare nut Safety Caution Concerned to New RefrigerantCopper pipe Piping JointTools General tools Conventional tools can be usedSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Parts name Type Specifications Concealed Duct TypeIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Indoor unit #1 Heder Wireless remote controllerLCD Outline of specifications Remarks Room temp. control Temperature in heatingSetting at shipment Tc ≥ 60C, the fan speed increases by 1 step Temperature HeatHeating ready is Outline of specificationsFan speed control RemarksTc n TcjTcn ConditionsSetup temperature on Setup at shipmentMode when Room temp. monitorCase of wired remote controller Case of wireless remote controllerValues of various sensors CentralGoes on Conditioner may stop or an error code may be displayed Starts with save operation valid because contents are Pushed for 4 seconds or more on the remote controllerWhen validating the save operation, the next operation This function is set up at the customer’s sideMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Troubleshooting procedure Summary of TroubleshootingBefore troubleshooting Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Central control devices detected Remote controller detectedIndoor unit detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures Check code E01 error E09 errorE04 error E10 errorL09 error E18 errorE08, L03, L07, L08 error P30 error Central controller L20 errorL30 error P10 error F10 errorP12 error CN333 CN334Exchange to cooling cycle P19 errorCheck by tester Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface P31 error Follower indoor unit E03 error Master indoor unitF29 error TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseContents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures Code No. required at leastWriting the setting data to Eeprom Refer to table Button for the temperature settingEeprom layout diagram Type Code No Setting data Type Type name abbSetting data Type Model Name RAV-SM∗∗∗BT-ETRIndoor Unit Test Run Setup on Remote Controller Wired remote controllerWiress remote controller D403 Red Practical operationLED Display on Indoor P.C. Board D501 Red To change the selected indoor unit, proceed to Procedure Function Selection SetupUsing the set temperature To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment When connected 2 remote controllers operate the twin Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit Remote controller address A-B selection settingWireless remote controller A-B selection Wireless remote controller B setupContents Temperature Buttons to change the error „ Calling of error history Contents Order to monitor another error history, push the set PushingUsual regular communication „ Indoor unit power-ON sequenceInitial communication Model Connection Interface TCC-LINK adapter Microprocessor block diagramModel connection interface wiring connection Model name TCB-PCNT30TLE2Use 2-core with no polar wire Wiring SpecificationsC. Board Switch SW01 Setup To prevent noise trouble, use 2-core shield wireAddress setup How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Push Test + Vent buttons for 4 seconds or morePage Address Setup Address setup procedureSingle System configurationAddress Setup & Group Control Terminology Triple Single group operationExample It is not influenced by the line 2 or 3 address indoor unitStandard One outdoor unit Automatic Address Example from Unset Address No miswiringOnly turning on source power supply Automatic completion Multiple groups operationSimultaneously for 4 seconds or more Using timer time Buttons, set the line addressPush SET + CL + Test buttons Folloer unit PushButton if the unit stops ProcedureTo know the position of indoor unit body by address Fan and louver of the selected indoor unit only operateAttachment Part name Procedure RemarksDetachment Cover from the projection of the side plate Suction panelElectric parts Then remove the coverBoard BoxControl P.C From control P.C. board Remove connectors for fan motor wiringFan motor Match the fan motor with turning directionDrain pump Float switchDrain pan AttachmentPerform works of 1 Position and fix it as before, using screwsHeat Set the heat exchanger at the originalRAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E Location Description Model Name RAV SM456BT-E SM566BT-ERAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR Location Model Name RAV Description SM406BT-E SM456BT-E SM566BT-ERAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E 100 RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation