Toshiba RAV-SM456BT-E Outline of judgment, Lamp indication Check code Cause of trouble occurrence

Page 38

Outline of judgment

When one of the following phenomena appears, an error of the power relay (RY01) is considered; therefore replace the P.C. board.

The operation started from the remote controller.

The fan stops immediately.

The display on the remote controller disappears.

After approx. 1minute

30 seconds, "Under setting" is displayed.

The screen of the remote controller enters in STOP status.

The primary judgment to check whether a trouble occurred in the indoor unit or outdoor unit is carried out with the following method.

Method to judge the erroneous position by display panel of the indoor unit (lamp display of the wireless receiving part)

The indoor unit monitors the operating status of the air conditioner, and the blocked contents of self-diagnosis are displayed restricted to the following cases if a protective circuit works.

 

 

 

 

 

 

 

 

: Go off,

: Go on,

: Flash (0.5 sec.)

 

 

 

 

 

 

 

 

 

Lamp indication

Check code

Cause of trouble occurrence

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Power supply OFF or miswiring between lamp indication unit and indoor unit

 

No indication at all

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E01

Receiving error

 

 

 

 

 

 

 

 

 

 

 

 

 

Receiving unit

Miswiring or wire connection error

 

 

 

 

 

 

E02

 

 

 

 

 

 

Sending error

 

 

 

 

 

 

 

 

between receiving unit and indoor unit

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E03

Communication stop

 

 

 

 

 

 

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E08

Duplicated indoor unit No.

 

 

Setup error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flash

 

 

 

 

E09

Duplicated master units of remote controller

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E10

Communication error between CPUs on indoor unit P.C. board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E18

Wire connection error between indoor units, Indoor power OFF

 

 

 

 

 

 

 

(Communication stop between indoor header and follower)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

E04

Miswiring between indoor unit and outdoor unit or connection erorr

 

 

 

 

 

 

 

(Communication stop between indoor and outdoor units)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Operation

Timer

Ready

P10

Overflow was detected.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective device of indoor unit worked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P12

Indoor DC fan error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Alternate flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P03

Outdoor unit discharge temp. error

 

Protective device of

1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P04

Outdoor high pressure system error

outdoor unit worked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P05

Negative phase detection error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P07

Heat sink overheat error

 

 

Outdoor unit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Gas leak detection error

 

 

 

 

 

 

Operation

Timer

Ready

P15

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P19

4-way valve system error (Indoor or outdoor unit judged.)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P20

Outdoor unit high pressure protection

 

 

 

 

 

 

Alternate flash

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P22

Outdoor unit: Outdoor unit error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Protective device of

 

 

 

 

 

 

 

P26

Outdoor unit: Inverter Idc operation

 

1

 

 

 

 

 

 

 

 

 

 

outdoor unit worked.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P29

Outdoor unit: Position detection error

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

P31

Stopped because of error of other indoor unit in a group

 

 

 

 

 

 

 

 

(Check codes of E03/L03/L07/L08)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1: These are representative examples and the check code differs according to the outdoor unit to be combined.

– 38 –

Image 38
Contents Split Type Contents 11-3 11-111-2 11-4Original instruction Work undertaken Protective gear worn Explanation of indicationsExplanation of illustrated marks Indication ExplanationConfirmation of warning label on the main unit Electrical Shock HazardProceeding with the repair work Service person is allowed to do this workWithout first conducting these checks DischargedTelephone wires Procedure in the ladders instructionsProtective gloves and safety work clothing Electric shocks, electrical leakage, smoking and/or a fireRefrigerant gas may catch fire Never recover the refrigerant into the outdoor unitWires as before Do not use a welder in the closed roomThough the refrigerant gas itself is innocuous Service panelBefore opening the service panel Refrigerant leaksPage Declaration of Conformity Explanations given to userRelocation Specifications Flare nut Safety Caution Concerned to New RefrigerantCopper pipe Piping JointTools General tools Conventional tools can be usedSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Parts name Type Specifications Concealed Duct TypeIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Indoor unit #1 Heder Wireless remote controllerLCD Outline of specifications Remarks Room temp. control Temperature in heatingSetting at shipment Tc ≥ 60C, the fan speed increases by 1 step Temperature HeatHeating ready is Outline of specificationsFan speed control RemarksTc n TcjTcn ConditionsSetup temperature on Setup at shipmentMode when Room temp. monitorCase of wired remote controller Case of wireless remote controllerValues of various sensors CentralGoes on Conditioner may stop or an error code may be displayed Starts with save operation valid because contents are Pushed for 4 seconds or more on the remote controllerWhen validating the save operation, the next operation This function is set up at the customer’s sideMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Troubleshooting procedure Summary of TroubleshootingBefore troubleshooting Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Central control devices detected Remote controller detectedIndoor unit detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures Check code E01 error E09 errorE04 error E10 errorL09 error E18 errorE08, L03, L07, L08 error P30 error Central controller L20 errorL30 error P10 error F10 errorP12 error CN333 CN334Exchange to cooling cycle P19 errorCheck by tester Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface P31 error Follower indoor unit E03 error Master indoor unitF29 error TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseContents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures Code No. required at leastWriting the setting data to Eeprom Refer to table Button for the temperature settingEeprom layout diagram Type Code No Setting data Type Type name abbSetting data Type Model Name RAV-SM∗∗∗BT-ETRIndoor Unit Test Run Setup on Remote Controller Wired remote controllerWiress remote controller D403 Red Practical operationLED Display on Indoor P.C. Board D501 Red To change the selected indoor unit, proceed to Procedure Function Selection SetupUsing the set temperature To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment When connected 2 remote controllers operate the twin Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit Remote controller address A-B selection settingWireless remote controller A-B selection Wireless remote controller B setupContents Temperature Buttons to change the error „ Calling of error history ContentsOrder to monitor another error history, push the set PushingUsual regular communication „ Indoor unit power-ON sequenceInitial communication Model Connection Interface TCC-LINK adapter Microprocessor block diagramModel connection interface wiring connection Model name TCB-PCNT30TLE2Use 2-core with no polar wire Wiring SpecificationsC. Board Switch SW01 Setup To prevent noise trouble, use 2-core shield wireAddress setup How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Push Test + Vent buttons for 4 seconds or morePage Address Setup Address setup procedureSingle System configurationAddress Setup & Group Control Terminology Triple Single group operationExample It is not influenced by the line 2 or 3 address indoor unitStandard One outdoor unit Automatic Address Example from Unset Address No miswiringOnly turning on source power supply Automatic completion Multiple groups operationSimultaneously for 4 seconds or more Using timer time Buttons, set the line addressPush SET + CL + Test buttons Folloer unit PushButton if the unit stops ProcedureTo know the position of indoor unit body by address Fan and louver of the selected indoor unit only operateAttachment Part name Procedure RemarksDetachment Cover from the projection of the side plate Suction panelElectric parts Then remove the coverBoard BoxControl P.C From control P.C. board Remove connectors for fan motor wiringFan motor Match the fan motor with turning directionDrain pump Float switchDrain pan AttachmentPerform works of 1 Position and fix it as before, using screwsHeat Set the heat exchanger at the originalRAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E Location Description Model Name RAV SM456BT-E SM566BT-ERAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR Location Model Name RAV Description SM406BT-E SM456BT-E SM566BT-ERAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E 100 RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation

RAV-SM456BT-E, RAV-SM566BT-TR, RAV-SM566BT-E, RAV-SM456BT-TR, RAV-SM806BT-E specifications

Toshiba has long been recognized as a leader in air conditioning technology, and their latest models, including the RAV-SM806BT-E, RAV-SM566BT-TR, RAV-SM1106BT-E, RAV-SM456BT-E, and RAV-SM1406BT-E, are prime examples of innovation in climate control solutions. These models combine energy efficiency, advanced technology, and user-friendly features to meet diverse cooling and heating needs for both residential and commercial spaces.

The RAV-SM806BT-E is notable for its impressive cooling and heating capabilities, making it suitable for larger areas. With a robust cooling capacity of 8.0 kW, this model is equipped with inverter technology, providing variable speed control that optimizes energy consumption while ensuring consistent comfort levels. Its quiet operation makes it ideal for settings where noise control is crucial, such as offices and bedrooms.

Similarly, the RAV-SM566BT-TR offers a balanced solution for medium-sized environments. With a capacity of 5.6 kW, it features advanced air filtration systems that enhance indoor air quality by removing dust, allergens, and pollutants. This model is particularly appreciated in regions with high air pollution levels, providing a healthier living or working environment.

The RAV-SM1106BT-E stands out for its high efficiency and eco-friendly refrigerant use. This model is designed to reduce greenhouse gas emissions while delivering significant cooling output, making it a responsible choice for environmentally conscious consumers. Additionally, Toshiba’s smart temperature control technology allows users to precisely manage their climate settings through a user-friendly remote control or smartphone app, offering convenience and ease of use.

For those looking for a compact yet powerful solution, the RAV-SM456BT-E is designed to fit smaller spaces without sacrificing performance. With a cooling capacity of 4.5 kW, it still utilizes sophisticated inverter technology, ensuring minimal energy loss and optimal heating and cooling efficiency. Its compact design allows for flexible installations in varied spaces.

Lastly, the RAV-SM1406BT-E model emphasizes versatility and performance. With a cooling capacity of 14.0 kW, it is designed for larger commercial spaces, delivering powerful climate control while maintaining energy efficiency. Its advanced multi-zone system allows simultaneous operation across different areas, adapting to the unique requirements of each zone.

In summary, Toshiba's RAV-SM series reflects the company's commitment to innovation, energy efficiency, and user comfort. Each model offers unique features tailored to specific needs, setting new standards in the air conditioning industry. Whether for residential or commercial use, these systems provide reliable performance while promoting sustainable practices.