Toshiba RAV-SM1406BT-E Item No. DN table Selection of function, Description At shipment

Page 66

Item No. (DN) table (Selection of function)

DN

Item

 

 

 

Description

 

 

 

 

 

 

 

 

At shipment

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

01

Filter sign lighting time}

0000

: None

 

 

 

 

 

 

 

 

 

 

0002

: 2500H

 

 

 

 

0002

: 2500H (4-Way/Duct/Ceiling Type)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

02

Dirty state of filter

0000

: Standard

 

0001 : High degree of dirt

 

0000

: Standard

 

 

 

 

 

 

 

 

 

 

(Half of standard time)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

03

Central control address

0001

: No.1 unit

to

0064 : No.64 unit

 

 

 

0099

: Unfixed

 

 

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

06

Heating suction temp shift

0000

: No shift

 

0001 : +1°C

 

 

 

 

 

0002

: +2°C

 

 

 

 

0002

: +2°C

to

0010 : –10°C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(Up to recommendation + 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0F

Cooling only

0000

: Heat pump

 

0001 : Cooling only

 

 

 

0000

: Heat pump

 

 

 

 

 

 

(No display of [AUTO] [HEAT])

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

10

Type

0004

: Concealed duct type

0007 : Ceiling type

 

 

 

According to model type

 

 

0014

: Compact 4-way cassette type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

Indoor unit capacity

0000

: Unfixed

 

0006 :

40 type

 

 

 

According to capacity type

 

 

0007

: 45 type

 

0009 :

56 type

 

 

 

 

 

 

 

 

 

 

 

 

0012

: 80 type

 

0015 : 110 type

 

 

 

 

 

 

 

 

 

 

 

 

0017

: 140 type

 

0018 : 160 type

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

12

Line address

0001

: No.1 unit

to

0030 : No.30 unit

 

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

13

Indoor unit address

0001

: No.1 unit

to

0064 : No.64 unit

 

 

 

0099

: Unfixed

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

14

Group address

0000

: Individual

 

0001 : Master of group

 

 

 

0099

: Unfixed

 

 

 

 

0002

: Follower of group

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

19

Louver type

0000

: No louver

 

0001 : Swing only

 

 

 

According to model type

 

(Air direction adjustment)

0002

: 1-way

 

0003 : 2-way

 

 

 

 

 

 

 

 

 

 

 

 

 

None for concealed duct

0004

: 4-way

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1E

Temp difference of

0000

: 0 deg to

 

0010 :

10 deg

 

 

 

0003

: 3 deg (Ts±1.5)

 

automatic cooling/heating

(For setup temperature, reversal of COOL/HEAT by ± (Data value)/2)

 

 

 

 

 

 

 

 

mode selection COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HEAT, HEAT COOL

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

28

Auto restart after power

0000

: None

 

0001 : Auto restart

 

 

 

0000

: None

 

 

 

failure

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2A

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0002

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2b

Thermo output selection

0000

: Indoor thermo ON

 

 

 

 

 

 

 

 

 

0000: Thermo. ON

 

(T10 e)

0001

: Output of outdoor comp-ON receiving

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2E

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

30

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

31

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0000

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

32

Sensor selection

0000

: Body TA sensor0001 :

Remote controller sensor

 

0000

: Body sensor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

33

Temperature indication

0000

: °C (celsius)

 

0001 : °F (Fahrenheit)

 

 

 

0000

: °C

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

40

Option

 

 

 

 

 

 

 

 

 

 

 

 

 

0003

: Default

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5d

High ceiling selection

 

 

 

 

 

 

 

 

 

 

 

 

 

According to capacity type

 

(External static pressure

<Concealed Duct type>

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

selection)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Set data

0000

 

0001

 

0002

 

0003

 

0004

 

 

0005

 

0006

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

External static

40 Pa

 

30 Pa

 

65 Pa

 

50 Pa

 

80 Pa

 

 

100 Pa

 

120 Pa

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

To 3HP

 

 

 

4 to 6HP

 

 

 

 

 

 

 

 

 

 

 

 

 

pressure

 

 

 

 

 

 

 

 

 

 

 

 

 

(Factory

 

 

(Factory

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

default)

 

 

 

default)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

The list above is when SW501-1 and SW501-2 is OFF.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

– 66 –

Image 66
Contents Split Type Contents 11-3 11-111-2 11-4Original instruction Work undertaken Protective gear worn Explanation of indicationsExplanation of illustrated marks Indication ExplanationConfirmation of warning label on the main unit Electrical Shock HazardProceeding with the repair work Service person is allowed to do this workWithout first conducting these checks DischargedTelephone wires Procedure in the ladders instructionsProtective gloves and safety work clothing Electric shocks, electrical leakage, smoking and/or a fireRefrigerant gas may catch fire Never recover the refrigerant into the outdoor unitWires as before Do not use a welder in the closed roomThough the refrigerant gas itself is innocuous Service panelBefore opening the service panel Refrigerant leaksPage Explanations given to user RelocationDeclaration of Conformity Specifications Flare nut Safety Caution Concerned to New RefrigerantCopper pipe Piping JointTools General tools Conventional tools can be usedSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Parts name Type Specifications Concealed Duct TypeIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Indoor unit #1 Heder Wireless remote controllerLCD Outline of specifications Remarks Temperature in heating Setting at shipmentRoom temp. control Tc ≥ 60C, the fan speed increases by 1 step Temperature HeatHeating ready is Outline of specificationsFan speed control RemarksTc n TcjTcn ConditionsSetup temperature on Setup at shipmentMode when Room temp. monitorCase of wired remote controller Case of wireless remote controllerCentral Goes onValues of various sensors Conditioner may stop or an error code may be displayed Starts with save operation valid because contents are Pushed for 4 seconds or more on the remote controllerWhen validating the save operation, the next operation This function is set up at the customer’s sideMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Troubleshooting procedure Summary of TroubleshootingBefore troubleshooting Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Remote controller detected Indoor unit detectedCentral control devices detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures Check code E01 error E09 errorE04 error E10 errorE18 error E08, L03, L07, L08 errorL09 error L20 error L30 errorP30 error Central controller P10 error F10 errorP12 error CN333 CN334Exchange to cooling cycle P19 errorCheck by tester Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface E03 error Master indoor unit F29 errorP31 error Follower indoor unit TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseContents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures Code No. required at leastWriting the setting data to Eeprom Refer to table Button for the temperature settingEeprom layout diagram Type Code No Setting data Type Type name abbSetting data Type Model Name RAV-SM∗∗∗BT-ETR Test Run Setup on Remote Controller Wired remote controller Wiress remote controller Indoor Unit Practical operation LED Display on Indoor P.C. Board D501 RedD403 Red To change the selected indoor unit, proceed to Procedure Function Selection SetupUsing the set temperature To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment When connected 2 remote controllers operate the twin Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit Remote controller address A-B selection settingWireless remote controller A-B selection Wireless remote controller B setupContents Temperature Buttons to change the error „ Calling of error history ContentsOrder to monitor another error history, push the set Pushing„ Indoor unit power-ON sequence Initial communicationUsual regular communication Model Connection Interface TCC-LINK adapter Microprocessor block diagramModel connection interface wiring connection Model name TCB-PCNT30TLE2Use 2-core with no polar wire Wiring SpecificationsC. Board Switch SW01 Setup To prevent noise trouble, use 2-core shield wireAddress setup How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Push Test + Vent buttons for 4 seconds or morePage Address Setup Address setup procedureSingle System configurationAddress Setup & Group Control Terminology Triple Single group operationExample It is not influenced by the line 2 or 3 address indoor unitStandard One outdoor unit Automatic Address Example from Unset Address No miswiringOnly turning on source power supply Automatic completion Multiple groups operationSimultaneously for 4 seconds or more Using timer time Buttons, set the line addressPush SET + CL + Test buttons Folloer unit PushButton if the unit stops ProcedureTo know the position of indoor unit body by address Fan and louver of the selected indoor unit only operatePart name Procedure Remarks DetachmentAttachment Cover from the projection of the side plate Suction panelElectric parts Then remove the coverBox Control P.CBoard From control P.C. board Remove connectors for fan motor wiringFan motor Match the fan motor with turning directionDrain pump Float switchDrain pan AttachmentPerform works of 1 Position and fix it as before, using screwsHeat Set the heat exchanger at the originalRAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E Location Description Model Name RAV SM456BT-E SM566BT-ERAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR Location Model Name RAV Description SM406BT-E SM456BT-E SM566BT-ERAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E 100 RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation