Toshiba RAV-SM456BT-E, RAV-SM406BT-TR, RAV-SM1406BT-E, RAV-SM1606BT-E Check of Concentration Limit

Page 103

WARNINGS ON REFRIGERANT LEAKAGE

Check of Concentration Limit

The room in which the air conditioner is to be installed requires a design that in the event of refrigerant gas leaking out, its concentration will not exceed a set limit.

The refrigerant R410A which is used in the air conditioner is safe, without the toxicity or combustibility of ammonia, and is not restricted by laws to be imposed which protect the ozone layer.

However, since it contains more than air, it poses the risk of suffocation if its concentration should rise excessively. Suffocation from leakage of R410A is almost non-existent.

With the recent increase in the number of high concentration buildings, however, the installation of multi air conditioner systems is on the increase because of the need for effective use of floor space, individual control, energy conservation by curtailing heat and carrying power etc.

Most importantly, the multi air conditioner system is able to replenish a large amount of refrigerant compared with conventional individual air conditioners.

If a single unit of the multi conditioner system is to be installed in a small room, select a suitable model and installation procedure so that if the refrigerant accidentally leaks out, its concentration does not reach the limit (and in the event of an emergency, measures can be made before injury can occur).

In a room where the concentration may exceed the limit, create an opening with adjacent rooms, or install mechanical ventilation combined with a gas leak detection device.

The concentration is as given below.

Total amount of refrigerant (kg)

Min. volume of the indoor unit installed room (m³)

Concentration limit (kg/m³)

The concentration limit of R410A which is used in multi air conditioners is 0.3kg/m³.

NOTE 1 :

If there are 2 or more refrigerating systems in a single refrigerating device, the amounts of refrigerant should be as charged in each independent device.

Outdoor unit

e.g., charged

amount (10kg) e.g.,

charged amount (15kg)

Room A Room B Room C Room D Room E Room F

Indoor unit

For the amount of charge in this example:

The possible amount of leaked refrigerant gas in rooms A, B and C is 10kg.

The possible amount of leaked refrigerant gas in rooms D, E and F is 15kg.

Important

NOTE 2 :

The standards for minimum room volume are as follows.

(1)No partition (shaded portion)

(2)When there is an effective opening with the adjacent room for ventilation of leaking refrigerant gas (opening without a door, or an opening 0.15% or larger than the respective floor spaces at the top or bottom of the door).

Outdoor unit

Refrigerant piping

Indoor unit

(3)If an indoor unit is installed in each partitioned room and the refrigerant piping is interconnected, the smallest room of course becomes the object. But when a mechanical ventilation is installed interlocked with a gas leakage detector in the smallest room where the density limit is exceeded, the volume of the next smallest room becomes the object.

 

 

Refrigerant piping

 

 

Outdoor unit

Very

 

 

small

 

Indoor unit

room

 

Small

Medium

Large room

room

room

 

Mechanical ventilation device - Gas leak detector

NOTE 3 :

The minimum indoor floor area compared with the amount of refrigerant is roughly as follows: (When the ceiling is 2.7m high)

 

40

 

 

 

 

35

Range below the

 

 

 

density limit

 

 

 

 

30

of 0.3 kg/m³

 

 

 

 

(countermeasures

 

 

 

 

 

 

 

 

 

25

not needed)

 

 

 

area

 

 

 

 

20

 

 

 

 

floor

15

 

Range above

 

 

the density limit

 

indoor

10

 

of 0.3 kg/m³

 

 

(countermeasures

 

 

 

needed)

 

 

Min.

5

 

 

 

 

 

 

 

0

 

 

 

 

 

10

20

30

 

 

 

 

 

 

Total amount of refrigerant

kg

– 4 –

Image 103
Contents Split Type Contents 11-4 11-111-2 11-3Original instruction Indication Explanation Explanation of indicationsExplanation of illustrated marks Work undertaken Protective gear wornElectrical Shock Hazard Confirmation of warning label on the main unitDischarged Service person is allowed to do this workWithout first conducting these checks Proceeding with the repair workElectric shocks, electrical leakage, smoking and/or a fire Procedure in the ladders instructionsProtective gloves and safety work clothing Telephone wiresDo not use a welder in the closed room Never recover the refrigerant into the outdoor unitWires as before Refrigerant gas may catch fireRefrigerant leaks Service panelBefore opening the service panel Though the refrigerant gas itself is innocuousPage Relocation Explanations given to userDeclaration of Conformity Specifications Joint Safety Caution Concerned to New RefrigerantCopper pipe Piping Flare nutGeneral tools Conventional tools can be used ToolsSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Concealed Duct Type Parts name Type SpecificationsCase of Connection of Wired Simple Remote Controller Indoor Controller Block DiagramIndoor unit #1 Heder Wireless remote controller Case of Connection of Wireless Remote ControllerLCD Outline of specifications Remarks Setting at shipment Temperature in heatingRoom temp. control Heat Tc ≥ 60C, the fan speed increases by 1 step TemperatureRemarks Outline of specificationsFan speed control Heating ready isConditions TcjTcn Tc nRoom temp. monitor Setup at shipmentMode when Setup temperature onCase of wireless remote controller Case of wired remote controllerGoes on CentralValues of various sensors Conditioner may stop or an error code may be displayed This function is set up at the customer’s side Pushed for 4 seconds or more on the remote controllerWhen validating the save operation, the next operation Starts with save operation valid because contents areMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Wired remote controller type Summary of TroubleshootingBefore troubleshooting Troubleshooting procedureWireless remote controller type Lamp indication Check code Cause of trouble occurrence Outline of judgmentLamp indication Check code Others Other than Check Code Indoor unit detected Remote controller detectedCentral control devices detected Error mode detected by indoor unit Check Code ListAir conditioner Error mode detected by outdoor unitOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures E09 error Check code E01 errorE10 error E04 errorE08, L03, L07, L08 error E18 errorL09 error L30 error L20 errorP30 error Central controller F10 error P10 errorCN333 CN334 P12 errorExchange to heating cycle P19 errorCheck by tester Exchange to cooling cycleF01 error F02 errorC06 error 11 model connection interface F29 error E03 error Master indoor unitP31 error Follower indoor unit TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPosition Resistance value Part name Checking procedureCase Replacement proceduresCode No. required at least Setting data read out from EepromC. Board for indoor unit servicing replacement procedures ContentsRefer to table Button for the temperature setting Writing the setting data to EepromEeprom layout diagram Model Name RAV-SM∗∗∗BT-ETR Setting data Type Type name abbSetting data Type Type Code NoWiress remote controller Test Run Setup on Remote Controller Wired remote controllerIndoor Unit LED Display on Indoor P.C. Board D501 Red Practical operationD403 Red To change item to be set up, proceed to Procedure Function Selection SetupUsing the set temperature To change the selected indoor unit, proceed to ProcedureDescription At shipment Item No. DN table Selection of functionDescription At shipment Remote controller address A-B selection setting Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit When connected 2 remote controllers operate the twinWireless remote controller B setup Wireless remote controller A-B selectionContents Pushing „ Calling of error history ContentsOrder to monitor another error history, push the set Temperature Buttons to change the errorInitial communication „ Indoor unit power-ON sequenceUsual regular communication Model name TCB-PCNT30TLE2 Microprocessor block diagramModel connection interface wiring connection Model Connection Interface TCC-LINK adapterTo prevent noise trouble, use 2-core shield wire Wiring SpecificationsC. Board Switch SW01 Setup Use 2-core with no polar wirePush Test + Vent buttons for 4 seconds or more How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Address setupPage Address setup procedure Address SetupTriple Single group operation System configurationAddress Setup & Group Control Terminology SingleIt is not influenced by the line 2 or 3 address indoor unit ExampleMultiple groups operation Automatic Address Example from Unset Address No miswiringOnly turning on source power supply Automatic completion Standard One outdoor unitFolloer unit Push Using timer time Buttons, set the line addressPush SET + CL + Test buttons Simultaneously for 4 seconds or moreFan and louver of the selected indoor unit only operate ProcedureTo know the position of indoor unit body by address Button if the unit stopsDetachment Part name Procedure RemarksAttachment Then remove the cover Suction panelElectric parts Cover from the projection of the side plateControl P.C BoxBoard Match the fan motor with turning direction Remove connectors for fan motor wiringFan motor From control P.C. boardAttachment Float switchDrain pan Drain pumpSet the heat exchanger at the original Position and fix it as before, using screwsHeat Perform works of 1RAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E SM456BT-E SM566BT-E Location Description Model Name RAVRAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR SM406BT-E SM456BT-E SM566BT-E Location Model Name RAV DescriptionRAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR 100101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation

RAV-SM456BT-E, RAV-SM566BT-TR, RAV-SM566BT-E, RAV-SM456BT-TR, RAV-SM806BT-E specifications

Toshiba has long been recognized as a leader in air conditioning technology, and their latest models, including the RAV-SM806BT-E, RAV-SM566BT-TR, RAV-SM1106BT-E, RAV-SM456BT-E, and RAV-SM1406BT-E, are prime examples of innovation in climate control solutions. These models combine energy efficiency, advanced technology, and user-friendly features to meet diverse cooling and heating needs for both residential and commercial spaces.

The RAV-SM806BT-E is notable for its impressive cooling and heating capabilities, making it suitable for larger areas. With a robust cooling capacity of 8.0 kW, this model is equipped with inverter technology, providing variable speed control that optimizes energy consumption while ensuring consistent comfort levels. Its quiet operation makes it ideal for settings where noise control is crucial, such as offices and bedrooms.

Similarly, the RAV-SM566BT-TR offers a balanced solution for medium-sized environments. With a capacity of 5.6 kW, it features advanced air filtration systems that enhance indoor air quality by removing dust, allergens, and pollutants. This model is particularly appreciated in regions with high air pollution levels, providing a healthier living or working environment.

The RAV-SM1106BT-E stands out for its high efficiency and eco-friendly refrigerant use. This model is designed to reduce greenhouse gas emissions while delivering significant cooling output, making it a responsible choice for environmentally conscious consumers. Additionally, Toshiba’s smart temperature control technology allows users to precisely manage their climate settings through a user-friendly remote control or smartphone app, offering convenience and ease of use.

For those looking for a compact yet powerful solution, the RAV-SM456BT-E is designed to fit smaller spaces without sacrificing performance. With a cooling capacity of 4.5 kW, it still utilizes sophisticated inverter technology, ensuring minimal energy loss and optimal heating and cooling efficiency. Its compact design allows for flexible installations in varied spaces.

Lastly, the RAV-SM1406BT-E model emphasizes versatility and performance. With a cooling capacity of 14.0 kW, it is designed for larger commercial spaces, delivering powerful climate control while maintaining energy efficiency. Its advanced multi-zone system allows simultaneous operation across different areas, adapting to the unique requirements of each zone.

In summary, Toshiba's RAV-SM series reflects the company's commitment to innovation, energy efficiency, and user comfort. Each model offers unique features tailored to specific needs, setting new standards in the air conditioning industry. Whether for residential or commercial use, these systems provide reliable performance while promoting sustainable practices.