Toshiba RAV-SM566BT-E Though the refrigerant gas itself is innocuous, Refrigerant leaks

Page 10

 

When the refrigerant gas leaks, find up the leaked position and repair it surely.

 

If the leaked position cannot be found up and the repair work is interrupted, pump-down and

 

tighten the service valve, otherwise the refrigerant gas may leak into the room.

 

The poisonous gas generates when gas touches to fire such as fan heater, stove or cocking stove

 

though the refrigerant gas itself is innocuous.

 

When installing equipment which includes a large amount of charged refrigerant such as a multi

 

air conditioner in a sub-room, it is necessary that the density does not the limit even if the

 

refrigerant leaks.

 

If the refrigerant leaks and exceeds the limit density, an accident of shortage of oxygen is caused.

 

 

 

Tighten the flare nut with a torque wrench in the specified manner.

Compulsion

Excessive tighten of the flare nut may cause a crack in the flare nut after a long period, which may

result in refrigerant leakage.

 

 

 

 

Nitrogen gas must be used for the airtight test.

 

 

 

The charge hose must be connected in such a way that it is not slack.

 

 

 

For the installation/moving/reinstallation work, follow to the Installation Manual.

 

If an incorrect installation is done, a trouble of the refrigerating cycle, water leak, electric shock or

 

fire is caused.

 

 

 

Once the repair work has been completed, check for refrigerant leaks, and check the insulation

 

resistance and water drainage.

 

Then perform a trial run to check that the air conditioner is running properly.

 

 

 

After repair work has finished, check there is no trouble. If check is not executed, a fire, electric

 

shock or injury may be caused. For a check, turn off the power breaker.

Check after

 

After repair work (installation of front panel and cabinet) has finished, execute a test run to check

repair

there is no generation of smoke or abnormal sound.

 

 

If check is not executed, a fire or an electric shock is caused. Before test run, install the front

 

panel and cabinet.

 

 

 

Check the following matters before a test run after repairing piping.

 

Connect the pipes surely and there is no leak of refrigerant.

 

The valve is opened.

Do not

Running the compressor under condition that the valve closes causes an abnormal high

operate the

pressure resulted in damage of the parts of the compressor and etc. and moreover if there is

unit with the

leak of refrigerant at connecting section of pipes, the air is suctioned and causes further

valve closed.

abnormal high pressure resulted in burst or injury.

 

 

 

Only a qualified installer (1) or qualified service person (1) is allowed to relocate the air

 

conditioner. It is dangerous for the air conditioner to be relocated by an unqualified individual

 

since a fire, electric shocks, injury, water leakage, noise and/or vibration may result.

Check the following items after reinstallation.

1)The earth wire is correctly connected.

2)The power cord is not caught in the product.

3)There is no inclination or unsteadiness and the installation is stable. Check after If check is not executed, a fire, an electric shock or an injury is caused.

reinstallation

 

When carrying out the pump-down work shut down the compressor before disconnecting the

 

 

refrigerant pipe.

 

Disconnecting the refrigerant pipe with the service valve left open and the compressor still

 

operating will cause air, etc. to be sucked in, raising the pressure inside the refrigeration cycle to

 

an abnormally high level, and possibly resulting in reputing, injury, etc.

 

 

 

When the service panel of the outdoor unit is to be opened in order for the compressor or the

 

area around this part to be repaired immediately after the air conditioner has been shut down, set

 

the circuit breaker to the OFF position, and then wait at least 10 minutes before opening the

 

service panel.

 

If you fail to heed this warning, you will run the risk of burning yourself because the compressor

 

pipes and other parts will be very hot to the touch. In addition, before proceeding with the repair

 

work, wear the kind of insulated heat-resistant gloves designed to protect electricians.

 

 

Cooling check

When the service panel of the outdoor unit is to be opened in order for the fan motor, reactor,

inverter or the areas around these parts to be repaired immediately after the air conditioner has

 

 

been shut down, set the circuit breaker to the OFF position, and then wait at least 10 minutes

 

before opening the service panel.

 

If you fail to heed this warning, you will run the risk of burning yourself because the fan motor,

 

reactor, inverter heat sink and other parts will be very hot to the touch.

 

In addition, before proceeding with the repair work, wear the kind of insulated heat-resistant

 

gloves designed to protect electricians.

– 10 –

Image 10
Contents Split Type Contents 11-3 11-111-2 11-4Original instruction Work undertaken Protective gear worn Explanation of indicationsExplanation of illustrated marks Indication ExplanationConfirmation of warning label on the main unit Electrical Shock HazardProceeding with the repair work Service person is allowed to do this workWithout first conducting these checks DischargedTelephone wires Procedure in the ladders instructionsProtective gloves and safety work clothing Electric shocks, electrical leakage, smoking and/or a fireRefrigerant gas may catch fire Never recover the refrigerant into the outdoor unitWires as before Do not use a welder in the closed roomThough the refrigerant gas itself is innocuous Service panelBefore opening the service panel Refrigerant leaksPage Relocation Explanations given to userDeclaration of Conformity Specifications Flare nut Safety Caution Concerned to New RefrigerantCopper pipe Piping JointTools General tools Conventional tools can be usedSM40, SM45, SM56 type SM80 type Construction Views External Views Page Wiring Diagram Parts name Type Specifications Concealed Duct TypeIndoor Controller Block Diagram Case of Connection of Wired Simple Remote ControllerCase of Connection of Wireless Remote Controller Indoor unit #1 Heder Wireless remote controllerLCD Outline of specifications Remarks Setting at shipment Temperature in heatingRoom temp. control Tc ≥ 60C, the fan speed increases by 1 step Temperature HeatHeating ready is Outline of specificationsFan speed control RemarksTc n TcjTcn ConditionsSetup temperature on Setup at shipmentMode when Room temp. monitorCase of wired remote controller Case of wireless remote controllerGoes on CentralValues of various sensors Conditioner may stop or an error code may be displayed Starts with save operation valid because contents are Pushed for 4 seconds or more on the remote controllerWhen validating the save operation, the next operation This function is set up at the customer’s sideMCC-1631 Indoor P.C. Board Optional Connector Specifications MCC-1631 Troubleshooting procedure Summary of TroubleshootingBefore troubleshooting Wired remote controller typeWireless remote controller type Outline of judgment Lamp indication Check code Cause of trouble occurrenceLamp indication Check code Others Other than Check Code Indoor unit detected Remote controller detectedCentral control devices detected Check Code List Error mode detected by indoor unitError mode detected by outdoor unit Air conditionerOperation of diagnostic function Check Status Operation of diagnostic function Judgment and measures Check code E01 error E09 errorE04 error E10 errorE08, L03, L07, L08 error E18 errorL09 error L30 error L20 errorP30 error Central controller P10 error F10 errorP12 error CN333 CN334Exchange to cooling cycle P19 errorCheck by tester Exchange to heating cycleF02 error F01 errorC06 error 11 model connection interface F29 error E03 error Master indoor unitP31 error Follower indoor unit TD, TL sensor Temperature Resistance value characteristic tableTA, TC, TCJ, TE, TS, to sensor TD, TL sensorPart name Checking procedure Position Resistance valueReplacement procedures CaseContents Setting data read out from EepromC. Board for indoor unit servicing replacement procedures Code No. required at leastWriting the setting data to Eeprom Refer to table Button for the temperature settingEeprom layout diagram Type Code No Setting data Type Type name abbSetting data Type Model Name RAV-SM∗∗∗BT-ETRWiress remote controller Test Run Setup on Remote Controller Wired remote controllerIndoor Unit LED Display on Indoor P.C. Board D501 Red Practical operationD403 Red To change the selected indoor unit, proceed to Procedure Function Selection SetupUsing the set temperature To change item to be set up, proceed to ProcedureItem No. DN table Selection of function Description At shipmentDescription At shipment When connected 2 remote controllers operate the twin Wireless remote controllerWhen connected 2 remote controllers operate an idoor unit Remote controller address A-B selection settingWireless remote controller A-B selection Wireless remote controller B setupContents Temperature Buttons to change the error „ Calling of error history ContentsOrder to monitor another error history, push the set PushingInitial communication „ Indoor unit power-ON sequenceUsual regular communication Model Connection Interface TCC-LINK adapter Microprocessor block diagramModel connection interface wiring connection Model name TCB-PCNT30TLE2Use 2-core with no polar wire Wiring SpecificationsC. Board Switch SW01 Setup To prevent noise trouble, use 2-core shield wireAddress setup How to set up from indoor unit side by remote controllerExternal view of P.C. board assembly Push Test + Vent buttons for 4 seconds or morePage Address Setup Address setup procedureSingle System configurationAddress Setup & Group Control Terminology Triple Single group operationExample It is not influenced by the line 2 or 3 address indoor unitStandard One outdoor unit Automatic Address Example from Unset Address No miswiringOnly turning on source power supply Automatic completion Multiple groups operationSimultaneously for 4 seconds or more Using timer time Buttons, set the line addressPush SET + CL + Test buttons Folloer unit PushButton if the unit stops ProcedureTo know the position of indoor unit body by address Fan and louver of the selected indoor unit only operateDetachment Part name Procedure RemarksAttachment Cover from the projection of the side plate Suction panelElectric parts Then remove the coverControl P.C BoxBoard From control P.C. board Remove connectors for fan motor wiringFan motor Match the fan motor with turning directionDrain pump Float switchDrain pan AttachmentPerform works of 1 Position and fix it as before, using screwsHeat Set the heat exchanger at the originalRAV-SM406BT-E, RAV-SM456BT-E, RAV-SM566BT-E Location Description Model Name RAV SM456BT-E SM566BT-ERAV-SM806BT-E Location Description Model Name RAV-SM406BT-TR, RAV-SM456BT-TR, RAV-SM566BT-TR SM456BT-TR SM566BT-TR RAV-SM806BT-TR RAV-SM806BT-TR Location Model Name RAV Description SM406BT-E SM456BT-E SM566BT-ERAV-SM1106BT-E, RAV-SM1406BT-E, RAV-SM1606BT-E Location Description Model Name RAV SM1106BT-E 100 RAV-SM1106BT-TR, RAV-SM1406BT-TR, RAV-SM1606BT-TR101 RAV-SM1106BT-E TR, RAV-SM1406BT-E TR, RAV-SM1606BT-E TR Check of Concentration Limit Toshiba Carrier Corporation

RAV-SM456BT-E, RAV-SM566BT-TR, RAV-SM566BT-E, RAV-SM456BT-TR, RAV-SM806BT-E specifications

Toshiba has long been recognized as a leader in air conditioning technology, and their latest models, including the RAV-SM806BT-E, RAV-SM566BT-TR, RAV-SM1106BT-E, RAV-SM456BT-E, and RAV-SM1406BT-E, are prime examples of innovation in climate control solutions. These models combine energy efficiency, advanced technology, and user-friendly features to meet diverse cooling and heating needs for both residential and commercial spaces.

The RAV-SM806BT-E is notable for its impressive cooling and heating capabilities, making it suitable for larger areas. With a robust cooling capacity of 8.0 kW, this model is equipped with inverter technology, providing variable speed control that optimizes energy consumption while ensuring consistent comfort levels. Its quiet operation makes it ideal for settings where noise control is crucial, such as offices and bedrooms.

Similarly, the RAV-SM566BT-TR offers a balanced solution for medium-sized environments. With a capacity of 5.6 kW, it features advanced air filtration systems that enhance indoor air quality by removing dust, allergens, and pollutants. This model is particularly appreciated in regions with high air pollution levels, providing a healthier living or working environment.

The RAV-SM1106BT-E stands out for its high efficiency and eco-friendly refrigerant use. This model is designed to reduce greenhouse gas emissions while delivering significant cooling output, making it a responsible choice for environmentally conscious consumers. Additionally, Toshiba’s smart temperature control technology allows users to precisely manage their climate settings through a user-friendly remote control or smartphone app, offering convenience and ease of use.

For those looking for a compact yet powerful solution, the RAV-SM456BT-E is designed to fit smaller spaces without sacrificing performance. With a cooling capacity of 4.5 kW, it still utilizes sophisticated inverter technology, ensuring minimal energy loss and optimal heating and cooling efficiency. Its compact design allows for flexible installations in varied spaces.

Lastly, the RAV-SM1406BT-E model emphasizes versatility and performance. With a cooling capacity of 14.0 kW, it is designed for larger commercial spaces, delivering powerful climate control while maintaining energy efficiency. Its advanced multi-zone system allows simultaneous operation across different areas, adapting to the unique requirements of each zone.

In summary, Toshiba's RAV-SM series reflects the company's commitment to innovation, energy efficiency, and user comfort. Each model offers unique features tailored to specific needs, setting new standards in the air conditioning industry. Whether for residential or commercial use, these systems provide reliable performance while promoting sustainable practices.