Toshiba RAV-SP300UT-UL, RAV-SP420UT-UL, RAV-SP240UT-UL, RAV-SP360UT-UL System Characteristics

Page 5

4-way Air Discharge Cassette Type

Owner’s Manual

2. SYSTEM CHARACTERISTICS

Air conditioner operating conditions

For proper performance, operate the air conditioner under the following temperature conditions:

 

Outdoor temperature

:

23 °F to 109.4 °F (-5 °C to 43 °C) *

 

 

 

 

 

Cooling operation

Room temperature

:

69.8 °F to 89.6 °F (21 °C to 32 °C) (Dry bulb temperature),

59 °F to 75.2 °F (15 °C to 24 °C) (Wet bulb temperature)

 

[CAUTION]

Room relative humidity – less than 80 %. If the air conditioner operates in excess of

 

this figure, condensation may occurs on the surface of the air conditioner.

 

 

Dry operation

Outdoor temperature

:

59 °F to 109.4 °F (15 °C to 43 °C)

 

 

 

 

Room temperature

:

62.6 °F to 89.6 °F (17 °C to 32 °C)

 

 

 

 

Heating operation

Outdoor temperature

: -4 °F to 59 °F (-20 °C to 15 °C) (Wet bulb temperature)

Room temperature

:

59 °F to 86 °F (15 °C to 30 °C) (Dry bulb temperature)

 

 

 

 

 

 

*: The air conditioner can be operate when outside temperature is 5°F to 23°F (-15°C to -5°C). Installing wind baffle to the outdoor unit is necessary to operate the air conditioner in that outside temperature range.

For further details, refer to the installation manual of the outdoor unit.

If air conditioner is used outside of the above conditions, safety protection may work.

3 minute protection function

There is a 3-minute time delay between compressor starts.

Auto restart

The unit will stop after a power failure.

The unit will restart automatically in the same operating mode as before the power failure when the power is restored.

Fan operation

Heating

When there is a call for heating, the fan will not start right away. There is a delay of approximately 5 minutes to ensure that the indoor heat exchanger warmed up.

When the room temperature reaches the set temperature, the fan will run at ultra low speed to avoid blowing cold air on the occupants in the space.

Cooling

When the room temperature reaches the set temperature, the fan will run at ultra low speed.

Defrost

When the unit is operating in the heating mode frost forms on the outdoor heat exchanger.

When this occurs, defrost is initiated automatically. During the defrost period (2 to 10 minutes) both the indoor and outdoor units stop running.

A hissing noise might be heard when the defrost cycle is initiated.

During the defrosting operation, the defrosted water will be drained from the bottom plate of the outdoor unit.

Heating capacity

In the heating operation, the heat is absorbed from the outside and brought into the room. This way of heating is called heat pump system. When the outside temperature is too low, it is recommended to use another heating apparatus in combination with the air conditioner.

Attention to snowfall and freeze on the outdoor unit

In snowy areas, the air inlet and air outlet of the outdoor unit are often covered with snow or frozen up. If snow or freeze on the outdoor unit is left as it is, it may cause machine failure or poor warming.

In cold areas, pay attention to the drain hose so that it perfectly drains water without water remaining inside for freeze prevention. If water freezes in the drain hose or inside the outdoor unit, it may cause machine failure or poor warming.

EN

– 4 –

4-EN

Image 5
Contents AIR Conditioner Split Type Contents Precautions for Safety Way Air Discharge Cassette Type System Characteristics Checks before operating Select a comfortable set point and minimize adjusting itEnergy Saving Recommendations „ Indoor unit Part Names„ Outdoor unit Part sold separately„ Display section Wired Remote ControlPower saving mode display Self cleaning displayPre-heat display No function display„ Operation section Remote control sensorButton Operation lamp„ Preparation Correct UsageStart StopAuto Changeover When restarting the operation after stop„ Timer operation Timer OperationCancel of timer operation SetFor cooling For heating Louver DirectionSet louver direction Display when stopping the swingHeat operation COOL/DRY operation„ Set louver direction individually Select a louver you want to adjust byOperation Pushing right side of the buttonSelf Cleaning Mode Power Saving ModeTo stop self cleaning, push button twice in succession Push button during operation„ Swing mode Advanced SettingsPush button to lock the louver Push button to complete the setting„ Louver lock No swing „ Change power saving mode setting „ Cancel louver lockPush Time buttons to adjust the power-save setting Push left side of button to select an indoor unit to be setPeriodic Maintenance MaintenanceBe sure to clean the heat exchanger with pressurized water Replacing antibacterial glassCleaning Unit Grille and Frame Cleaning the air filterCleaning The Louvers Preparing for long Shut Down PeriodInstallation place Information for InstallationElectrical wiring Do not install the air conditioner in the following placesBe careful with noise or vibrations MaintenanceRe-Installation Fan does not stop when the operation is stopped Trouble ShootingIndoor unit or outdoor unit makes a strange noise RecheckDo not turn off the circuit breaker When the protective device is activatedProtective device Memo EH99933501