When fastening ductwork to side duct flanges on unit, insert screws through duct flanges only. DO NOT insert screws through casing. Outdoor duct- work must be insulated and
FIGURE 13 - SIDE PANELS WITH HOLE PLUGS
Note orientation. Panel is “insulation” side up.
CONDENSATE DRAIN
The side condensate drain is reversible and maybe
Plumbing must conform to local codes. Use a sealing com- pound on male pipe threads. Install condensate drain line from the 3/4 inch NPT female connection on the unit to an open drain.
OPTIONALCOIL
GUARD
3"Minimum
FIGURE 16 - CONDENSATE DRAIN
COMPRESSORS
The compressors are mounted on elastomer insulators. The mounting bolts have been fully tightened for shipping.
Do not loosen the compressor mounting bolts.
FIGURE 14 - RETURN DOWNFLOW PLENUM WITH PANEL
FILTERS
FIGURE 15 - DISCHARGE PANEL IN PLACE
Make sure that panel latches are properly positioned on the unit to maintain an airtight seal.