York Understanding Flash Codes: Control Waiting ASCD and Compressor Lockout Issues

Page 40

035-17311-003-A-0704

TABLE 37: UNIT CONTROL BOARD FLASH CODES

Flash Code

Description

On Steady

Control Failure - Replace Control

Heart Beat

Normal Operation

 

 

1 Flash

Not Applicable

 

 

2 Flashes

Control waiting ASCD*

3 Flashes

HPS1 - Compressor Lock out

 

 

4 Flashes

HPS2 - Compressor Lock out

 

 

5 Flashes

LPS1 - Compressor Lock out

 

 

6 Flashes

LPS2 - Compressor Lock out

 

 

7 Flashes

FS1 - Compressor Lock out

 

 

8 Flashes

FS2 - Compressor Lock out

 

 

9 Flashes

Ignition Control Locked Out/

Ignition Control Failure / Limit Switch Trip / No Jumper Plug in Heat Section

 

 

 

10 Flashes

Compressors Locked Out On Low

Outdoor Air Temperature*

 

11 Flashes

Compressors Locked Out Because The

Economizer Is Using Free Cooling*

 

12 Flashes

Fan Overload Switch Trip - Not Applicable On This Unit *

 

 

13 Flashes

Compressor Held Off Due To Low Voltage*

 

 

14 Flashes

EEPROM Storage Failure (Control Failure)

 

 

OFF

No Power or Control Failure

*. These flash codes do not represent alarms.

 

Monitored

No

 

 

Programming?

No

 

Call for

No

Loss of

Yes

 

Systems

 

 

 

 

 

 

 

Call for

 

 

 

 

 

 

 

 

Heating?

 

 

 

Problem?

 

 

 

 

 

 

 

 

 

 

 

Heating?

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

Yes

 

 

Yes

 

 

No

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Program

 

 

 

 

 

 

 

 

 

 

 

Trip/Failure

 

 

 

 

 

Unit

 

 

 

Call for

 

 

 

 

 

 

 

 

 

 

 

Control

 

 

 

 

 

Heat

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Board

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Heat Off

Call for 2nd

Stage

Cooling

No

Monitor

 

 

 

 

No

Turn off ID

Yes

Fan on

 

Blower Motor

 

>30 secs?

 

 

Yes

 

No

Lossof Call

 

 

 

 

for ID Blower?

 

 

 

 

 

Energize ID

 

 

 

 

 

Blower Motor

 

 

 

 

 

 

 

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

No

Fan off

 

 

 

 

 

 

 

 

 

 

>10 secs?

 

 

 

 

 

 

Yes

 

 

 

 

 

 

 

 

 

No

Call for

 

 

 

 

 

 

 

 

ID Blower?

Call for

Yes

Cooling?

 

 

No

 

 

 

 

 

 

No

Loss of Call

Yes

 

for Cooling?

 

First

Stage?

Yes

Call for 1st

Stage

Cooling

Cool Off

FIGURE 24 - BASIC TROUBLESHOOTING FLOWCHART

40

Unitary Products Group

Image 40
Contents Installation Manual Table of Contents List of Figures List of Tables Safety Considerations GeneralInspection Reference½ 12½ Ton Predator Model Number Nomenclature NomenclatureNOMENCLATURE, Additonal Options Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil, Phase Monitor, & Coil Guard Installation Safety Information InstallationPreceding Installation Location Unit Temperature LimitationsRigging and Handling Point Load Weight Length of Forks Must be a Minimum of 60 InchesDetail B Detail a Detail CBottom Duct Openings from Above Ductwork Duct CoversSide Panels with Hole Plugs Condensate Drain Thermostat Wiring Control Wire SizesPower and Control Wiring Power Wiring DetailElectronic Thermostat Field Wiring RLA Electrical Data DM120 10 TON with Power Convenience Outlet 380 11.5 75.0Physical Data OPTIONS/ACCESSORIESMinimum Supply AIR CFM Economizer and Power Exhaust SET Point Adjustments and InformationEnthalpy SET Point Chart Phasing Blower RotationSupply AIR Limitations Belt Tension1/2 TON Standard Motor Down Shot Blower PERFORMANCE* † 1/2 TON Optional Motor Down Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 10 TON Optional Motor Down Shot Blower PERFORMANCE* †12-1/2 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Down Shot Blower PERFORMANCE* †1/2 TON Standard Motor Side Shot Blower PERFORMANCE* † 1/2 TON Optional Motor Side Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Standard Motor Side Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Side Shot Blower PERFORMANCE* †Indoor Blower Specifications AIR BalanceChecking AIR Quantity Method ONE Method TWODRY Coil Delta P Supply AIR Drive Adjustment Operation Additional Static ResistanceMotor Sheave Datum Diameters Sequence of Operations OverviewCooling Sequence of Operation Safety Controls Compressor ProtectionElectric Heating Operation Errors Electric Heat Limit SettingElectric Heating Sequence of Operations Electric Heat Antictpator SetpointsSTART-UP Cooling Charging the Unit10 TON Standard Efficiency Superheat Charging 12.5 TON Standard Efficiency Superheat ChargingGeneral Normal Maintenance TroubleshootingPredator Flash Codes Basic Troubleshooting Flowchart Unit Control Board Flash CodesCooling Troubleshooting Guide Unitary Products Group 035-17311-003-A-0704 Unitary 5005 Norman Products York Group Drive 73069