York DM090 installation manual 12-1/2 TON Standard Motor Down Shot Blower PERFORMANCE* †

Page 27
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.
Blower performance for gas heat includes maximum number of heat tubes available for each tonnage.

035-17311-003-A-0704

TABLE 21: 12-1/2 TON STANDARD MOTOR DOWN SHOT BLOWER PERFORMANCE* †

 

 

 

 

 

 

 

 

 

TURNS OPEN**

 

 

 

 

 

 

 

 

ESP

 

0

 

 

1

 

 

2

 

 

 

 

3

 

 

4

 

 

5

 

 

CFM

W††

BHP

CFM

W††

BHP

CFM

W††

 

BHP

CFM

 

W††

BHP

CFM

W††

BHP

CFM

W††

BHP

0.4

5078

3630

3.89

4809

3103

3.33

4594

3053

 

3.27

4360

 

2478

2.66

4090

2093

2.24

3812

1798

1.93

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

4865

3456

3.71

4584

2961

3.17

4349

2912

 

3.12

4106

 

2318

2.49

3814

1964

2.11

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

4642

3284

3.52

4356

2828

3.03

4089

2776

 

2.98

3840

 

2137

2.29

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

4408

3114

3.34

4124

2705

2.90

3815

2647

 

2.84

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

4164

2947

3.16

3889

2592

2.78

-

-

 

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

3910

2787

2.99

-

-

-

-

-

 

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*.

†.Blower performance includes two-inch throwaway filters.

‡.ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the total static pressure of the blower.

**. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.

††.W = Watts

TABLE 22: 12-1/2 TON OPTIONAL MOTOR DOWN SHOT BLOWER PERFORMANCE* †

 

 

 

 

 

 

 

 

 

TURNS OPEN**

 

 

 

 

 

 

 

 

ESP

 

0

 

 

1

 

 

2

 

 

 

 

3

 

 

4

 

 

5

 

 

CFM

W††

BHP

CFM

W††

BHP

CFM

W††

 

BHP

CFM

 

W††

BHP

CFM

W††

BHP

CFM

W††

BHP

0.4

5994

5400

5.79

5565

4369

4.69

5488

4169

 

4.47

5264

 

3599

3.86

4990

3085

3.31

4738

2812

3.02

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.6

5824

5216

5.59

5368

4186

4.49

5289

3991

 

4.28

5049

 

3437

3.69

4763

2937

3.15

4491

2655

2.85

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

0.8

5641

5022

5.39

5170

4012

4.30

5076

3807

 

4.08

4822

 

3272

3.51

4528

2790

2.99

4235

2497

2.68

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.0

5444

4819

5.17

4971

3846

4.12

4847

3618

 

3.88

4584

 

3103

3.33

4286

2644

2.83

3969

2340

2.51

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.2

5233

4609

4.94

4771

3687

3.95

4604

3426

 

3.67

4335

 

2933

3.15

4035

2499

2.68

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.4

5009

4394

4.71

4571

3537

3.79

4346

3233

 

3.47

4074

 

2762

2.96

3777

2356

2.53

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.6

4771

4174

4.48

4370

3395

3.64

4074

3040

 

3.26

3802

 

2590

2.78

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.8

4520

3951

4.24

4169

3262

3.50

3786

2850

 

3.06

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.0

4255

3728

4.00

3966

3137

3.36

-

-

 

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

2.2

3976

3505

3.76

3763

3020

3.24

-

-

 

-

-

 

-

-

-

-

-

-

-

-

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

*.

†.Blower performance includes two-inch throwaway filters.

‡.ESP (External Static Pressure) given is that available for the supply and return air duct system. All internal resistances have been deducted from the total static pressure of the blower.

**. “Turns Open” refers to the setting of the variable pitch motor sheave, where “0 Turns Open” is fully closed.

††.W = Watts

Unitary Products Group

27

Image 27
Contents Installation Manual Table of Contents List of Figures List of Tables Reference Safety ConsiderationsGeneral InspectionNomenclature ½ 12½ Ton Predator Model Number NomenclatureNOMENCLATURE, Additonal Options Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil, Phase Monitor, & Coil Guard Installation Installation Safety InformationPreceding Installation Unit Temperature Limitations LocationRigging and Handling Length of Forks Must be a Minimum of 60 Inches Point Load WeightDetail C Detail B Detail aBottom Duct Openings from Above Duct Covers DuctworkSide Panels with Hole Plugs Condensate Drain Power Wiring Detail Thermostat WiringControl Wire Sizes Power and Control WiringElectronic Thermostat Field Wiring RLA 380 11.5 75.0 Electrical Data DM120 10 TON with Power Convenience OutletOPTIONS/ACCESSORIES Physical DataMinimum Supply AIR CFM Adjustments and Information Economizer and Power Exhaust SET PointEnthalpy SET Point Chart Belt Tension PhasingBlower Rotation Supply AIR Limitations1/2 TON Optional Motor Down Shot Blower PERFORMANCE* † 1/2 TON Standard Motor Down Shot Blower PERFORMANCE* †10 TON Optional Motor Down Shot Blower PERFORMANCE* † 10 TON Standard Motor Down Shot Blower PERFORMANCE* †12-1/2 TON Optional Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Standard Motor Down Shot Blower PERFORMANCE* †1/2 TON Optional Motor Side Shot Blower PERFORMANCE* † 1/2 TON Standard Motor Side Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Side Shot Blower PERFORMANCE* † 12-1/2 TON Standard Motor Side Shot Blower PERFORMANCE* †Method ONE Method TWO Indoor Blower SpecificationsAIR Balance Checking AIR QuantityDRY Coil Delta P Supply AIR Drive Adjustment Sequence of Operations Overview OperationAdditional Static Resistance Motor Sheave Datum DiametersCooling Sequence of Operation Compressor Protection Safety ControlsElectric Heat Antictpator Setpoints Electric Heating Operation ErrorsElectric Heat Limit Setting Electric Heating Sequence of OperationsCharging the Unit START-UP Cooling12.5 TON Standard Efficiency Superheat Charging 10 TON Standard Efficiency Superheat ChargingNormal Maintenance Troubleshooting GeneralPredator Flash Codes Unit Control Board Flash Codes Basic Troubleshooting FlowchartCooling Troubleshooting Guide Unitary Products Group 035-17311-003-A-0704 Unitary 5005 Norman Products York Group Drive 73069