York DM090 Thermostat Wiring, Control Wire Sizes, Power and Control Wiring, Power Wiring Detail

Page 17

035-17311-003-A-0704

THERMOSTAT WIRING

The thermostat should be located on an inside wall approxi- mately 56 inches above the floor where it will not be subject to drafts, sun exposure or heat from electrical fixtures or appliances. Follow the manufacturer's instructions enclosed with thermostat for general installation procedure. Seven (7) color-coded, insulated wires should be used to connect the thermostat to the unit. Refer to Table 7 for control wire sizing and maximum length.

TABLE 7: CONTROL WIRE SIZES

Wire Size

Maximum Length*

18 AWG

150 Feet

 

 

*. From the unit to the thermostat and back to the unit.

POWER AND CONTROL WIRING

Field wiring to the unit, fuses, and disconnects must conform to provisions of National Electrical Code (NEC), ANSI/NFPA No. 70 – Latest Edition (in U.S.A.), current Canadian Electri- cal Code C221, and/or local ordinances. The unit must be electrically grounded in accordance with NEC and CEC as specified above and/or local codes.

Voltage tolerances which must be maintained at the com- pressor terminals during starting and running conditions are indicated on the unit Rating Plate and Table 1.

The internal wiring harnesses furnished with this unit are an integral part of the design certified unit. Field alteration to comply with electrical codes should not be required. If any of the wire supplied with the unit must be replaced, replacement wire must be of the type shown on the wiring diagram and the same minimum gauge as the replaced wire.

A disconnect must be utilized for these units. Factory installed disconnects are available. If installing a disconnect

(field supplied or York Internationalsupplied accessory), refer to Figure 4 for the recommended mounting location.

Avoid damage to internal components if drilling holes for disconnect mounting.

NOTE: Since not all local codes allow the mounting of a dis- connect on the unit, please confirm compliance with local code before mounting a disconnect on the unit.

Electrical line must be sized properly to carry the load. USE COPPER CONDUCTORS ONLY. Each unit must be wired with a separate branch circuit fed directly from the meter panel and properly fused.

Refer to Figures 17, 18 and 19 for typical field wiring and to the appropriate unit wiring diagram mounted inside control doors for control circuit and power wiring information.

When connecting electrical power and control wiring to the unit, water-proof connectors must be used so that water or moisture cannot be drawn into the unit during normal operation. The above water-proofing conditions will also apply when installing a field sup- plied disconnect switch.

POWER WIRING DETAIL

Units are factory wired for the voltage shown on the unit nameplate. Refer to Electrical Data Tables 8 through 13 size power wiring, fuses, and disconnect switch.

Power wiring is brought into the unit through the side of the unit or the basepan inside the curb.

Unitary Products Group

17

Image 17
Contents Installation Manual Table of Contents List of Figures List of Tables General Safety ConsiderationsInspection ReferenceNomenclature ½ 12½ Ton Predator Model Number NomenclatureNOMENCLATURE, Additonal Options Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil, Phase Monitor, & Coil Guard Preceding Installation InstallationInstallation Safety Information Rigging and Handling Unit Temperature LimitationsLocation Length of Forks Must be a Minimum of 60 Inches Point Load WeightDetail C Detail B Detail aBottom Duct Openings from Above Duct Covers DuctworkSide Panels with Hole Plugs Condensate Drain Control Wire Sizes Thermostat WiringPower and Control Wiring Power Wiring DetailElectronic Thermostat Field Wiring RLA 380 11.5 75.0 Electrical Data DM120 10 TON with Power Convenience OutletMinimum Supply AIR CFM OPTIONS/ACCESSORIESPhysical Data Adjustments and Information Economizer and Power Exhaust SET PointEnthalpy SET Point Chart Blower Rotation PhasingSupply AIR Limitations Belt Tension1/2 TON Optional Motor Down Shot Blower PERFORMANCE* † 1/2 TON Standard Motor Down Shot Blower PERFORMANCE* †10 TON Optional Motor Down Shot Blower PERFORMANCE* † 10 TON Standard Motor Down Shot Blower PERFORMANCE* †12-1/2 TON Optional Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Standard Motor Down Shot Blower PERFORMANCE* †1/2 TON Optional Motor Side Shot Blower PERFORMANCE* † 1/2 TON Standard Motor Side Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Side Shot Blower PERFORMANCE* † 12-1/2 TON Standard Motor Side Shot Blower PERFORMANCE* †AIR Balance Indoor Blower SpecificationsChecking AIR Quantity Method ONE Method TWODRY Coil Delta P Supply AIR Drive Adjustment Additional Static Resistance OperationMotor Sheave Datum Diameters Sequence of Operations OverviewCooling Sequence of Operation Compressor Protection Safety ControlsElectric Heat Limit Setting Electric Heating Operation ErrorsElectric Heating Sequence of Operations Electric Heat Antictpator SetpointsCharging the Unit START-UP Cooling12.5 TON Standard Efficiency Superheat Charging 10 TON Standard Efficiency Superheat ChargingPredator Flash Codes Normal Maintenance TroubleshootingGeneral Unit Control Board Flash Codes Basic Troubleshooting FlowchartCooling Troubleshooting Guide Unitary Products Group 035-17311-003-A-0704 Unitary 5005 Norman Products York Group Drive 73069