terminal. If 24 volts is not present, check for loose wiring from the Y1 “OUT” terminal to the
13.The UCB can be programmed to lock out compressor operation during free cooling and in low ambient condi- tions. These options are not enabled by default. They can be checked by local York distributors.
14.If none of the above corrected the error, test the integrity of the UCB. Disconnect the C1 terminal wire and jumper it to the Y1 terminal. DO NOT jump the Y1 to C1 termi- nals. If the compressor engages, the UCB has faulted.
15.If none of the above correct the error, replace the UCB.