York Complete Guide to Efficient Operation of Your Air Conditioner

Page 22

035-17311-003-A-0704

ECONOMIZER

The Economizer can be a factory installed option or a field installed accessory. If factory installed, refer to the instruc- tions included with the outdoor air hood to complete the assembly. Field installed Economizer accessories include complete instructions for installation.

There are two Economizer options:

1.Down Flow application with barometric relief hood standard.

2.Horizontal Flow application that requires the purchase of a barometric relief hood.

POWER EXHAUST

The Power Exhaust can be a factory installed option or a field installed accessory. If factory installed, refer to the instruc- tions included with the outdoor air hood to complete the assembly. Field installed Power Exhaust accessories include complete instructions for installation.

The Power Exhaust factory installed option is for Down Flow application only.

There are two field installed Power Exhaust accessories:

ON position and then OFF or energize and de-energize terminals “R” to “G”.

With the thermostat set to the indoor fan ON position or terminals “R” to “G” energized, turn the Minimum Posi- tion Adjusting screw (located on the damper control module) counterclockwise until the desired minimum damper position has been attained.

ENTHALPY SET POINT ADJUSTMENT

The enthalpy set point may now be set by selecting the desired set point shown in the Enthalpy Set Point Adjustment Figure 20. Adjust as follows:

For a single enthalpy operation carefully turn the set point adjusting screw (found on the damper control mod- ule) to the "A", "B", "C" or "D" setting corresponding to the lettered curve of the Enthalpy Set Point Adjustment Figure 20.

For a dual enthalpy operation, carefully turn the set point adjusting screw fully clockwise past the "D" setting.

POWER EXHAUST DAMPER SET POINT (WITH OR WITH- OUT POWER EXHAUST)

1. Down Flow application.

• With no power exhaust option, adjust the Exhaust Air

Adjustment Screw fully clockwise. This will allow 2nd

2. Horizontal Flow application that requires the purchase of

stage cooling to operate.

 

a barometric relief hood.

• With power exhaust option, each building pressurization

RAIN HOOD

requirement will be different. The point at which the

All of the hood components, including the filters, the gasket-

power exhaust comes on is determined by the econo-

mizer damper position (Percent Open). The Exhaust Air

ing and the hardware for assembling, are packaged and

Adjustment Screw should be set at the Percent Open of

located between the condenser coil section and the main unit

the economizer damper at which the power exhaust is

cabinet, if the unit has factory installed options. If field

needed. It can be set from 0 to 100% damper open.

installed accessories are being installed all parts necessary

 

 

for the installation comes in the accessory.

INDOOR AIR QUALITY AQ

ECONOMIZER AND POWER EXHAUST SET POINT

Indoor Air Quality (indoor sensor input): Terminal AQ accepts

ADJUSTMENTS AND INFORMATION

a +2 to +10 Vdc signal with respect to the (AQ1) terminal.

Remove the top rear access panel from the unit. Locate the

When the signal is below it's set point, the actuator is allowed

to modulate normally in accordance with the enthalpy and

economizer control module, where the following adjustments

mixed air sensor inputs. When the AQ signal exceeds it's set

will be made.

point setting and there is no call for free cooling, the actuator

 

 

 

 

 

 

 

 

 

 

 

 

is proportionately modulated from the 2 to 10 Vdc signal, with

 

 

 

 

 

 

2 Vdc corresponding to full closed and 10 Vdc corresponding

 

 

 

 

 

 

 

 

 

 

 

 

to full open. When there is no call for free cooling, the damper

 

 

 

 

 

 

position is limited by the IAQ Max damper position setting.

 

Extreme care must be exercised in turning all set

 

When the signal exceeds it's set point (Demand Control Ven-

 

point, maximum and minimum damper positioning

 

tilation Set Point) setting and there is a call for free cooling,

 

adjustment screws to prevent twisting them off.

 

the actuator modulates from the minimum position to the full

 

 

 

 

 

 

open position based on the highest call from either the mixed

 

 

 

 

 

 

MINIMUM POSITION ADJUSTMENT

air sensor input or the AQ voltage input.

 

 

• Check that the damper blades move smoothly without

• Optional CO2 Space Sensor Kit Part # 2AQ04700324

 

binding; carefully turn the Minimum Position Adjust

• Optional CO2 Sensor Kit Part # 2AQ04700424

 

screw (found on the damper control module) fully clock-

Replace the top rear access panel on the unit.

 

wise and then set the thermostat indoor fan switch to the

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

22

 

 

 

 

Unitary Products Group

 

Image 22
Contents Installation Manual Table of Contents List of Figures List of Tables Inspection Safety ConsiderationsGeneral Reference½ 12½ Ton Predator Model Number Nomenclature NomenclatureNOMENCLATURE, Additonal Options Johnson UNT Controller, DFS, APS & Phase Monitor Technicoat Condenser Coil, Phase Monitor, & Coil Guard Installation Safety Information InstallationPreceding Installation Location Unit Temperature LimitationsRigging and Handling Point Load Weight Length of Forks Must be a Minimum of 60 InchesDetail B Detail a Detail CBottom Duct Openings from Above Ductwork Duct CoversSide Panels with Hole Plugs Condensate Drain Power and Control Wiring Thermostat WiringControl Wire Sizes Power Wiring DetailElectronic Thermostat Field Wiring RLA Electrical Data DM120 10 TON with Power Convenience Outlet 380 11.5 75.0Physical Data OPTIONS/ACCESSORIESMinimum Supply AIR CFM Economizer and Power Exhaust SET Point Adjustments and InformationEnthalpy SET Point Chart Supply AIR Limitations PhasingBlower Rotation Belt Tension1/2 TON Standard Motor Down Shot Blower PERFORMANCE* † 1/2 TON Optional Motor Down Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 10 TON Optional Motor Down Shot Blower PERFORMANCE* †12-1/2 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Down Shot Blower PERFORMANCE* †1/2 TON Standard Motor Side Shot Blower PERFORMANCE* † 1/2 TON Optional Motor Side Shot Blower PERFORMANCE* †10 TON Standard Motor Down Shot Blower PERFORMANCE* † 12-1/2 TON Standard Motor Side Shot Blower PERFORMANCE* † 12-1/2 TON Optional Motor Side Shot Blower PERFORMANCE* †Checking AIR Quantity Indoor Blower SpecificationsAIR Balance Method ONE Method TWODRY Coil Delta P Supply AIR Drive Adjustment Motor Sheave Datum Diameters OperationAdditional Static Resistance Sequence of Operations OverviewCooling Sequence of Operation Safety Controls Compressor ProtectionElectric Heating Sequence of Operations Electric Heating Operation ErrorsElectric Heat Limit Setting Electric Heat Antictpator SetpointsSTART-UP Cooling Charging the Unit10 TON Standard Efficiency Superheat Charging 12.5 TON Standard Efficiency Superheat ChargingGeneral Normal Maintenance TroubleshootingPredator Flash Codes Basic Troubleshooting Flowchart Unit Control Board Flash CodesCooling Troubleshooting Guide Unitary Products Group 035-17311-003-A-0704 Unitary 5005 Norman Products York Group Drive 73069