Roberts Gorden BH-200, BH-60, BH-40, BH-150, BH-175, BH-115, BH-100 Troubleshooting Flow Chart, Yes

Page 57

Turn up thermostat.

NO

Does the blower turn on?

 

YES

Place a jumper across the

 

thermostat terminals.

NO

Does the blower turn on?

 

YES

 

Check thermostat wiring

 

and replace thermostat if

 

necessary.

 

Unplug burner and check

 

Is there power 120 V at

the burner?

NO

Check relay wiring (if applicable) and wiring

to the burner.

Is the igniter gap

YES

Unplug burner. Does the

NO

blower turn freely?

 

YES

 

Replace blower.

 

Is the vent pipe or the inlet of

Remove obstruction.

YES

Is the blower obstructed?

NO

Blower bearings may have

failed. Replace blower.

12.1 Troubleshooting Flow Chart

Is there spark at the igniter? NO igniter and ignition wire. Are NO they damaged?

YES

Replace igniter and ignition wire as needed.

Check wiring between the

power cord, blower motor NO and transformer.

set at 1/8"?

NO

Carefully reset spark gap to 1/8"

With the blue and yellow wires still removed, is the voltage at the transformer black and white leads 120 V?

YES

Replace transformer.

YES

NO

the burner obstructed?

YES

 

NO

 

Are the air hoses to the

NO

pressure switch secure and

leak free?

 

YES

 

Remove the blue and yellow

 

wires from the transformer.

 

Is there 24 V at the

 

transformer secondary?

 

YES

 

Reconnect transformer

 

wires. Place a jumper wire

YES

across the pressure switch.

 

Is there a spark?

 

NO

 

Replace ignition module.

 

Remove obstruction.

Repair, replace, or tighten hoses as necessary.

Replace pressure switch

SECTION 12: T

51 of 59

ROUBLESHOOTING

Image 57
Contents Or maintenance can result in death, injury or Improper installation, adjustment, alteration, serviceProperty damage. Read the Installation, Operation Installation must be done by a contractor qualifiedPage Roberts-Gordon LLC Page Table of Figures Page Manpower Requirements Heater SafetySafety Labels and Their Placement California PropositionTop and Bottom Panel Label Placement Side and Back Panel Label Placement Installer Responsibility Wall TagNational Standards and Applicable Codes Clearances are the required distances that Maintain clearances to combustibles at all times for safetyC D InchesCentimeters ModelTube, Standard Reflector Model 45 Tilt Reflector ModelInches Centimeters Tube, Opposite 45 Reflector ModelCentimeters Model Venting InchesNational Standards and Applicable Codes Stainless Steel Major ComponentsBurner Tube Reflector End CapStandard Parts List Contents of BH-Series Burner CartonContents of Core and Extension Packages BH-Series Component Package Guide Model Tubing Length Core Packages Minimum Standard AluminizedHeater Installation Typical Suspension Details Linear Heater Assembly Overview Linear Heater Layout Overview Linear Heater Layout Overview Burner Tube InstallationCoupling and Tube Assembly Tube Clamp Package InstallationOpen Closed2 Coupling and Tube Assembly 1 Coupling and Tube AssemblyNot required on the BH-125/150/175/200 Turbulator InstallationHanger Burner Tube Reflector Description Part Number Reflector Support Package 1 Reflector, U-Clip and Reflector Support InstallationBurner Installation Optional Heater Accessories Tube, Standard TubeTube, Opposite Tube Heater Layout Overview Tube Layout Overview Elbow Package Configuration .2.1 Elbow Installation2 Elbow Installation Reflector Joint Detail 5 Reflector Joint Detail2 Side Reflector Installation Reflector Side Extension 1 Bracket InstallationDescription Part Number Lower Clearance Shield Package Distance a Extension 2 Frame Shield Installation3 Grille Installation 2 Grille End Cap InstallationVenting United States RequirementsCanadian Requirements Horizontal Venting Unvented OperationVertical Venting Unvented Operation Tube TerminationVertical Ventilation 4 10 cm Pipe Common Side Wall VentingOutside Wall Common Vertical Venting Outside Combustion Air Supply Vertical Outside Air Supply for Single Heater InstallationHorizontal Outside Air Supply for Double Heater Installation Vertical Outside Air Supply for Double Heater InstallationGAS Piping Correct Positions When attaching gas hoseHold gas nipple securely with pipe wrench Failure to follow these instructions can resultLine Voltage Thermostat Wiring WiringFront View Low Voltage Thermostat WiringInternal Wiring Ladder Diagram Electrical Connection to the Burner Pre-Season Maintenance and Annual Inspection Operation and MaintenanceSequence of Operation To Shut Off HeaterVehicles and Other Vicinity of the HeaterObjects ReflectorBlower Scroll, Wheel Safety LabelsMotor Burner Cup and Orifice ElectrodeTroubleshooting YES Troubleshooting Flow ChartPage Manifold Gas Pressure Setting Replacement Parts Replacement Parts Description Part Number Dimensions General SpecificationsGAS Pressure AT Manifold Pipe ConnectionPage ROBERTS-GORDON LLC will PAY for Warranty is Void ifROBERTS-GORDON LLC will not PAY for Limitations on Authority RepresentativesPage Page Page