INSTALLATION REQUIREMENTS
FLOOR PROTECTION
The American Harvest Multifuel Stove may be installed on a combustible floor, with proper floor protection, or on a masonry hearth. The hearth or noncombustible floor protector must extend a minimum of (6) inches (152mm)in front and (6) inches (152mm) from each side of the ash removal door.
CLEARANCES TO COMBUSTIBLES
The stove must be installed with the following minimum clearances to side and back wall combustible materials. NOTE: These are minimum clearances to combustible walls established by the testing lab. The amount of room needed on the left side of the unit to access the electrical panel is (6) six inches (152mm).
PARALLEL - A - | Left Sidewall to Top Edge of Unit | 6 in./152mm |
B - | Sidewall to Flue | 5 in./127mm |
C - | Backwall to Flue | 3 in./75mm |
D - | Backwall to Unit | 9 in./228mm |
E - | Right Sidewall to Top Edge of Unit | 2 in./50mm |
CORNER - F - | Adjacent Wall to Flue | 3 in./75mm |
G - | Adjacent Wall to Unit | 4 in./100mm |
BACK WALL
SIDE WALL
BACK WALL
SIDE WALL
Alcove / Backwall / Sidewall |
|
Parallel / Alcove Installation | Corner Installation |