Lochinvar 000 Btu/hr, 45 Minimum Flow Rate Required to Actuate Flow Switch, Table J AMP Draw Data

Page 19

A water flow switch meets most code requirements for a low-water cut off device on boilers requiring forced circulation for operation.

TABLE I

MINIMUM FLOW RATE REQUIRED TO

ACTUATE FLOW SWITCH

Pipe Size

GPM Flow Rate

 

 

1 1/2"

13

 

 

2"

18

 

 

LOW WATER CUTOFF (IF EQUIPPED)

A hot water boiler installed above radiation level must be provided with a low water cutoff device either as part of the unit or installed at the time the boiler is installed. An electronic low water cutoff is available as a kit on all units. Low water cutoffs should be inspected every six months, including flushing of float types.

TWO STAGE BURNER

CONTROL SYSTEM

The 45,000 thru 500,000 Btu/hr boilers (M9) are equipped with a two stage burner control system. The 45,000 thru 399,999 Btu/hr models will be equipped with a two stage gas valve to control high/low burner operation. The 500,000 Btu/hr model achieves two stage burner firing by staging the operation of the two combination gas valves.

4.To avoid serious damage, DO NOT energize the appliance until the system is full of water. Serious damage may result.

5.Provide the unit with proper overload protection.

6.Install a wall thermostat on the inside wall. DO NOT install the thermostat in an area affected by drafts, sunlight, light fixtures, hot or cold water pipes or near a fireplace. See “Terminal Strip Con- nection of a Room Thermostat”, page 38 for proper wiring connection.

TABLE J

AMP DRAW DATA

45,000 thru 500,000 Btu/hr Models

MAXIMUM

FIRINGTOTAL AMPS

CONTROLS

@ 120 VAC

 

 

F1 Standing Pilot (Single Stage

 

90,000 - 260,000 Btu/hr)

2.5

F9 Intermittent Pilot (Single Stage

 

90,000 - 399,999 Btu/hr)

2.5

 

 

F9 Intermittent Pilot (Single

 

Stage/2 valves 500,000 Btu/hr)

2.5

 

 

M9 with Internal Pump

 

(45,000 - 260,000 Btu/hr)

2.0

 

 

M9 Intermittent Pilot (Two Stage

 

Valve 315,000 - 399,999 Btu/hr)

2.0

 

 

M9 Intermittent Pilot (Two Stage/2

 

valves 500,000 Btu/hr)

2.0

ELECTRICAL CONNECTIONS

This appliance is wired for 120 VAC service. The appliance, when installed, must be electrically grounded in accordance with the requirements of the authority having jurisdiction or in the absence of such requirements, with the latest edition of the National Electrical Code ANSI/NFPA No. 70. When the unit is installed in Canada, it must conform to the CSA C22.1, Canadian Electrical Code, Part 1 and/or local Electrical Codes.

1.All wiring between the appliance and field installed devices shall be made with type T wire [63° F(35° C) rise].

2.Line voltage wire exterior to the appliance must be enclosed in approved conduit or approved metal clad cable.

3.The pump must run continuously when the appliance is being fired.

Pump Wiring for a Heating Boiler

The heating boiler circulating pump must be purchased locally. The maximum load for the pump switched by the internal pump relay must not exceed 1 HP. The current draw for a field installed 120 VAC pump MUST be added to the boiler’s current draw to determine the minimum wire size for 120 volt service.

FIG. 25 Standing Pilot System F1 Control Panel

19

Image 19
Contents Special Instructions to Owner WarrantyChecking Equipment Contents User Warning Codes Installation ProcedureLocation of Unit Clearances from Combustible Construction Clearance from Combustible ConstructionCombustion Air Through Ducts Openings Table a Minimum Recommended Combustion AIR SupplyInput Btu/hr Flue Size VentingConventional Negative Draft Venting System Table B Vent Pipe SizesPage Vent Termination from Peaked Roof 10’ or Less from Ridge Venting TerminationInspection of a Masonry Chimney Sidewall Venting Masonry Chimney InstallationVent Damper and Vent Damper Terminal Block Automatic Vent DamperTable D Manifold Pressure GAS Supply GAS Pressure TestTable C GAS ConnectionTable G GAS Connections Table F Fittings to Equivalent Straight PipeBtu/hr Distance from Meter In Feet GAS Piping Install Piping to ControlWrench GAS Manifold Pressure Adjustment ProcedurePilot Checking GAS Supply PressureVenting of Combination Gas Valves Combination GAS ValvesRelief Valve Water Heater Relief Valve Water Flow Switch if EquippedTable J AMP Draw Data Minimum Flow Rate Required to Actuate Flow SwitchLOW Water Cutoff if Equipped TWO Stage Burner Control SystemLocating Temperature Control Temperature AdjustmentTemperature Control Settings Operating Temperature ControlHigh-Fire Offset Temperature Control SensorsInstallation of Remote Sensors Wiring of Remote SensorsAdditional Temperature Controls Outdoor AIR Reset OptionManual Reset High Water Temperature Limit Blocked Vent and Flame ROLL-OUT/FLAME Interlock SwitchInitial START-UP What to do if YOU Smell GAS PRE-START ChecklistInput for Your Safety Read Before Operating Lighting Instructions for Standing Pilot Models F1Lighting Wand To Turn OFF GAS to Appliance Safety Shutoff Test for Standing Pilot Ignition SystemLighting Instructions for Spark Ignition Pilot Models F9/M9 Operating Instructions To Turn OFF GAS to Appliance Safety Shutoff Test for Spark Ignition Pilot SystemF9/M9 Intermittent Spark Ignition Pilot Models Intermittent Pilot Spark Ignition System F9/M9Freeze Protection Freeze Protection for a HeatingWater Treatment MaintenanceRemoval of Combustion Chamber Lining or Base Panels Inspection Cleaning ProcedureOuter Air Deflector and HEX Filler Bracket Circulator Pump Requirements GAS Train and ControlsWater Connections Heating Boilers only Piping of the Boiler SystemTable L Circulator Pump SpecificationsCirculator Pump Operation Primary/Secondary Piping of a Single Boiler PRIMARY/SECONDARY Boiler PipingThree WAY Valves LOW Temperature Bypass RequirementsBoiler Flow Rates General Plumbing Rules Table M Minimum Required Flow for Heating BoilerTable N Installation with a Chilled Water SystemWire Gauge Boiler Operating Temperature ControlPower Venter Connection To Terminal Strip Table O Terminal Strip WiringBtu/hr To 7 Grains To 25 Grains Hardness Required Temperature RiseTable P Required Temperature Rise Water Velocity ControlSoftened Water Systems Water ChemistryPump Operation Heat Exchanger Remote Sensor Installation InstructionsThermostat Settings Minimum Pump PerformanceOptional Relief Valve Automatic Vent DampersCathodic Protection Thermal ExpansionDo not plug or cap the relief valve discharge Troubleshooting Guide 90,000 270,000 Btu/hr Models Water Heaters F1 Schematic Diagram F1 Unit Schematic Diagram F9 Unit Schematic Diagram M9 Unit Schematic Diagram F9/M9 Unit Page
Related manuals
Manual 52 pages 63.01 Kb

000 Btu/hr, 000 - 500, RSB-i&s-05, 45, CP-5M-4/08 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.