This section contains specific instructions for those units used to supply domestic hot water. All warnings, cautions, notes and instructions in the general installation and service sections apply to these instructions. Water heaters are designed for installation with a storage tank. The use of a properly sized pump and the control of water velocity, as explained below, is important for correct operation of your water heater.

WATER VELOCITY CONTROL

IMPORTANT - To ensure proper velocity through the heat exchanger, it is necessary to regulate the temperature rise across the heat exchanger from inlet to outlet. This must be done on initial installation and periodically rechecked. With the correct temperature rise across the heat exchanger, you may be assured of the proper velocity in the tubes. This will yield long life and economical operation from your water heater. Excessive lime build-up in the tube is a result of too little velocity in the tubes. Excessive pitting or erosion in the tube is caused by too much velocity through the tubes. Care should be taken to measure temperature rise and maintain a velocity as follows:

1.The pump must run continuously when the burners are firing.

2.With the pump running and the water heater off, the inlet and outlet thermometers should read the same temperatures. If they do not, an adjustment must be made to your final calculation.

3.Turn the water heater on and allow time for the temperature to stabilize. Record the difference between the inlet and outlet temperatures. This difference will be the “temperature rise.”

4.Compare the temperature rise on the heater with the required temperature rise in Table P. Should adjustment be needed, proceed as follows:

If the temperature rise is too high, the water velocity is too low. Check the following:

1.Check for restrictions in the outlet of the water heater.

2.Be sure all valves are open between the water heater and the tank.

3.Check the pump to be sure it is running properly and that the pump motor is running in the proper direction.

4.Be sure the circulation pipes between the water heater and storage tank are not less than 1 1/2" diameter for a single unit installation.

5.Common manifold piping for multiple unit instal- lations will require larger minimum pipe sizes to

tank tappings to ensure proper flow. See Table Q on page 40.

6.Multiple unit installations may also require a larger circulating pump to achieve the specified flow against the increased head loss of a multiple unit common manifold piping.

If the temperature rise is too low, the water velocity is too high. Adjust as follows:

1.Slowly throttle the valve on the outlet side of the water heater until the temperature rise is steady at the required temperature rise as noted in Table P.

2.Sustained high water velocity and low temperature rise may result in pitting or erosion of the copper tubes in the heat exchanger. This is a non-warrantable failure. Temperature rise must be properly adjusted to achieve the specified flow rate.

REQUIRED TEMPERATURE RISE

Temperature rise is based on the hardness of the potable water to be heated. A different temperature rise is specified for soft water with a hardness of 0 to 7 grains per gallon or for unsoftened water with a hardness of 8 to 25 grains per gallon. The total dissolved solids shall not exceed 350 ppm. If there is any doubt about the hardness or total dissolved solids content of the water to be heated, follow the temperature guidelines for water with 8 to 25 grains of hardness in Table P below. The majority of all potable water supplies will fall within the range of 8 to 25 grains of hardness. See Water Chemistry, page 40.

TABLE - P

REQUIRED TEMPERATURE RISE

 

Btu/hr

0 to 7 Grains

8 to 25 Grains

 

 

Hardness

Hardness

 

INPUT

Temp. Rise oF

Temp. Rise °F

90,000

8

5

 

 

 

 

135,000

12

7

 

 

 

 

180,000

15

10

 

 

 

 

199,999

17

11

 

 

 

 

225,000

20

12

270,000

22

15

315,000

25

17

 

 

 

 

360,000

30

20

 

 

 

 

399,999

35

22

 

 

 

500,000

40

28

39

Image 39
Contents Warranty Special Instructions to OwnerChecking Equipment Contents User Warning Installation Procedure CodesLocation of Unit Clearances from Combustible Construction Clearance from Combustible ConstructionCombustion Air Through Ducts Openings Table a Minimum Recommended Combustion AIR SupplyInput Btu/hr Flue Size VentingConventional Negative Draft Venting System Table B Vent Pipe SizesPage Vent Termination from Peaked Roof 10’ or Less from Ridge Venting TerminationInspection of a Masonry Chimney Sidewall Venting Masonry Chimney InstallationVent Damper and Vent Damper Terminal Block Automatic Vent DamperTable D Manifold Pressure GAS Supply GAS Pressure TestTable C GAS ConnectionTable F Fittings to Equivalent Straight Pipe Table G GAS ConnectionsBtu/hr Distance from Meter In Feet GAS Piping Install Piping to ControlWrench GAS Manifold Pressure Adjustment ProcedurePilot Checking GAS Supply PressureVenting of Combination Gas Valves Combination GAS ValvesRelief Valve Water Heater Relief Valve Water Flow Switch if EquippedTable J AMP Draw Data Minimum Flow Rate Required to Actuate Flow SwitchLOW Water Cutoff if Equipped TWO Stage Burner Control SystemLocating Temperature Control Temperature AdjustmentTemperature Control Settings Operating Temperature ControlHigh-Fire Offset Temperature Control SensorsInstallation of Remote Sensors Wiring of Remote SensorsAdditional Temperature Controls Outdoor AIR Reset OptionBlocked Vent and Flame ROLL-OUT/FLAME Interlock Switch Manual Reset High Water Temperature LimitInitial START-UP What to do if YOU Smell GAS PRE-START ChecklistInput for Your Safety Read Before Operating Lighting Instructions for Standing Pilot Models F1Lighting Wand Safety Shutoff Test for Standing Pilot Ignition System To Turn OFF GAS to ApplianceLighting Instructions for Spark Ignition Pilot Models F9/M9 Operating Instructions To Turn OFF GAS to Appliance Safety Shutoff Test for Spark Ignition Pilot SystemF9/M9 Intermittent Spark Ignition Pilot Models Intermittent Pilot Spark Ignition System F9/M9Freeze Protection Freeze Protection for a HeatingWater Treatment MaintenanceRemoval of Combustion Chamber Lining or Base Panels Inspection Cleaning ProcedureOuter Air Deflector and HEX Filler Bracket Circulator Pump Requirements GAS Train and ControlsWater Connections Heating Boilers only Piping of the Boiler SystemCirculator Pump Specifications Table LCirculator Pump Operation Primary/Secondary Piping of a Single Boiler PRIMARY/SECONDARY Boiler PipingLOW Temperature Bypass Requirements Three WAY ValvesBoiler Flow Rates General Plumbing Rules Table M Minimum Required Flow for Heating BoilerTable N Installation with a Chilled Water SystemWire Gauge Boiler Operating Temperature ControlPower Venter Connection To Terminal Strip Table O Terminal Strip WiringBtu/hr To 7 Grains To 25 Grains Hardness Required Temperature RiseTable P Required Temperature Rise Water Velocity ControlWater Chemistry Softened Water SystemsPump Operation Heat Exchanger Remote Sensor Installation InstructionsThermostat Settings Minimum Pump PerformanceOptional Relief Valve Automatic Vent DampersThermal Expansion Cathodic ProtectionDo not plug or cap the relief valve discharge Troubleshooting Guide 90,000 270,000 Btu/hr Models Water Heaters F1 Schematic Diagram F1 Unit Schematic Diagram F9 Unit Schematic Diagram M9 Unit Schematic Diagram F9/M9 Unit Page
Related manuals
Manual 52 pages 63.01 Kb

000 Btu/hr, 000 - 500, RSB-i&s-05, 45, CP-5M-4/08 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.