Lochinvar 45, CP-5M-4/08, RSB-i&s-05 Table a Minimum Recommended Combustion AIR Supply, Openings

Page 6

Outside air openings shall directly communicate with the outdoors. When combustion air is drawn from the outside through a duct, the net free area of each of the two openings must have twice (2 times) the free area required for Outside Air/2 Openings. Table A lists the requirements for the appliance only, additional gas fired appliances located in the same room will require an increase in the net free area to supply adequate combustion air for all appliances. Combustion air requirements are based on the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada refer to National Standard CAN B149.1 or B149.2. Check all local code requirements for combustion air.

All dimensions are based on net free area in square inches. Metal louvers or screens reduce the free area of a combustion air opening a minimum of approximately 25%. Check with louver manufacturers for exact net free area of louvers. Where two openings are provided, one must be within 12" (30 cm) of the ceiling and one must be within 12" (30 cm) of the floor of the room where the appliance is installed. Each opening must have a net free area as specified in Table A. Single openings shall be located within 12" (30 cm) of the ceiling.

￿CAUTION

Under no circumstances should the room where the appliance is installed ever be under a negative pressure. Particular care should be taken where exhaust fans, attic fans, clothes dryers, compressors, air handling units, etc., may take away air from the appliance.

The combustion air supply must be completely free of any flammable vapors that may ignite or chemical fumes which may be corrosive to the appliance. Common corrosive chemical fumes which must be avoided are fluorocarbons and other halogenated compounds, most commonly present as refrigerants or solvents, such as freon, tricholorethylene, perchlorethylene, chlorine, etc. These chemicals, when burned, form acids which quickly attack the heat exchanger finned tubes, headers, flue collectors, and the vent system. The result is improper combustion and a non-warrantable, premature appliance failure.

TABLE - A

MINIMUM RECOMMENDED COMBUSTION AIR SUPPLY

 

 

Combustion Air Source

 

 

Input

Outside Air/2

Outside Air/1

Inside Air/2

 

Btu/hr

Openings

Opening

Openings

 

 

 

 

 

45,000

12 in2

15 in2

100 in2

75,000

19 in2

25 in2

100 in2

90,000

23 in2

30 in2

100 in2

135,000

34 in2

45 in2

135 in2

180,000

45 in2

60 in2

180 in2

199,999

50 in2

67 in2

200 in2

215,000

55 in2

74 in2

224 in2

225,000

56 in2

75 in2

225 in2

260,000

67 in2

89 in2

269 in2

270,000

68 in2

90 in2

270 in2

315,000

79 in2

105 in2

315 in2

360,000

90 in2

120 in2

360 in2

 

 

 

 

399,999

100 in2

133 in2

400 in2

 

 

 

 

500,000

125 in2

167 in2

500 in2

 

 

 

 

 

6

Image 6
Contents Warranty Special Instructions to OwnerChecking Equipment Contents User Warning Installation Procedure CodesLocation of Unit Clearance from Combustible Construction Clearances from Combustible ConstructionCombustion Air Through Ducts Table a Minimum Recommended Combustion AIR Supply OpeningsTable B Vent Pipe Sizes VentingConventional Negative Draft Venting System Input Btu/hr Flue SizePage Venting Termination Vent Termination from Peaked Roof 10’ or Less from RidgeSidewall Venting Masonry Chimney Installation Inspection of a Masonry ChimneyAutomatic Vent Damper Vent Damper and Vent Damper Terminal BlockGAS Connection GAS Supply GAS Pressure TestTable C Table D Manifold PressureTable F Fittings to Equivalent Straight Pipe Table G GAS ConnectionsBtu/hr Distance from Meter In Feet Install Piping to Control GAS PipingGAS Manifold Pressure Adjustment Procedure WrenchChecking GAS Supply Pressure PilotCombination GAS Valves Venting of Combination Gas ValvesRelief Valve Water Flow Switch if Equipped Relief Valve Water HeaterTWO Stage Burner Control System Minimum Flow Rate Required to Actuate Flow SwitchLOW Water Cutoff if Equipped Table J AMP Draw DataOperating Temperature Control Temperature AdjustmentTemperature Control Settings Locating Temperature ControlWiring of Remote Sensors Temperature Control SensorsInstallation of Remote Sensors High-Fire OffsetOutdoor AIR Reset Option Additional Temperature ControlsBlocked Vent and Flame ROLL-OUT/FLAME Interlock Switch Manual Reset High Water Temperature LimitInitial START-UP Lighting Instructions for Standing Pilot Models F1 PRE-START ChecklistInput for Your Safety Read Before Operating What to do if YOU Smell GASLighting Wand Safety Shutoff Test for Standing Pilot Ignition System To Turn OFF GAS to ApplianceLighting Instructions for Spark Ignition Pilot Models F9/M9 Safety Shutoff Test for Spark Ignition Pilot System Operating Instructions To Turn OFF GAS to ApplianceFreeze Protection for a Heating Intermittent Pilot Spark Ignition System F9/M9Freeze Protection F9/M9 Intermittent Spark Ignition Pilot ModelsMaintenance Water TreatmentInspection Cleaning Procedure Removal of Combustion Chamber Lining or Base PanelsOuter Air Deflector and HEX Filler Bracket Piping of the Boiler System GAS Train and ControlsWater Connections Heating Boilers only Circulator Pump RequirementsCirculator Pump Specifications Table LCirculator Pump Operation PRIMARY/SECONDARY Boiler Piping Primary/Secondary Piping of a Single BoilerLOW Temperature Bypass Requirements Three WAY ValvesBoiler Flow Rates Table M Minimum Required Flow for Heating Boiler General Plumbing RulesInstallation with a Chilled Water System Table NTable O Terminal Strip Wiring Boiler Operating Temperature ControlPower Venter Connection To Terminal Strip Wire GaugeWater Velocity Control Required Temperature RiseTable P Required Temperature Rise Btu/hr To 7 Grains To 25 Grains HardnessWater Chemistry Softened Water SystemsPump Operation Minimum Pump Performance Remote Sensor Installation InstructionsThermostat Settings Heat ExchangerAutomatic Vent Dampers Optional Relief ValveThermal Expansion Cathodic ProtectionDo not plug or cap the relief valve discharge Troubleshooting Guide 90,000 270,000 Btu/hr Models Water Heaters F1 Schematic Diagram F1 Unit Schematic Diagram F9 Unit Schematic Diagram M9 Unit Schematic Diagram F9/M9 Unit Page
Related manuals
Manual 52 pages 63.01 Kb

000 Btu/hr, 000 - 500, RSB-i&s-05, 45, CP-5M-4/08 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.