Lochinvar 000 - 500, 45 Blocked Vent and Flame ROLL-OUT/FLAME Interlock Switch, Initial START-UP

Page 23

Manual Reset High Water Temperature Limit

Control (Standard Fixed Settings on Water Heaters and Optional Adjustable Settings on Boilers and Water Heaters)

Water heaters are supplied with a fixed setting, manual reset high water temperature limit control. This manual reset temperature limit control has a fixed limit setting of 230°F (110°C). If water temperature exceeds this setting, the limit will break the control circuit and shut down the unit. The limit control can only be reset after the water temperature has cooled well below the setting of the limit. Reset of the limit control is accomplished by pushing the Red Reset Button (Manual Reset High Limit) (see Figures 25 - 27 on pages 19 and 20) located on the front side of the control panel. A label on the control panel indicates the exact location of the manual reset high water temperature limit control.

BLOCKED VENT AND FLAME

ROLL-OUT/FLAME INTERLOCK SWITCH

FIG. 31 Blocked Vent Switch Location

FLAME ROLL-OUT SWITCH /

INTERLOCK SWITCH

FIG. 32 Flame Roll-Out/Flame Interlock Switch Location

All units are equipped with manual reset blocked vent and flame roll-out / flame interlock switches. These temperature switches are located in the controls compartment and in the relief opening of the boiler’s built-in draft hood. Each switch has a red reset button. In the event the system has actuated to shut off the main burner gas supply, wait for the boiler to cool, then press the red reset to return the boiler to operation. Operation of a blocked vent and/or flame roll-out / interlock switch usually indicates a problem with the venting system, obstruction of the heat exchanger flue gas passageway and/or a combustion air supply problem. The cause for operation of the blocked vent and/or flame roll-out / interlock switch must be determined and corrected. If the boiler cannot be restored to normal operation, contact a qualified service installer, service agency or the gas supplier.

INITIAL START-UP

Follow the Lighting Instructions on the label applied to the appliance.

A. On water heaters and boilers with the system pump delay option, the operating temperature control will energize the pump relay which energizes the pump on a call for heat. The operating temperature control will de-energize the pump relay approximately 30 seconds after the call for heat ends. If either the inlet sensor or the optional multi-purpose temperature sensor reads below 40°F, the pump relay will turn ON. When the temperature rises above 50°F the pump relay will turn OFF.

23

Image 23
Contents Checking Equipment WarrantySpecial Instructions to Owner Contents User Warning Location of Unit Installation ProcedureCodes Clearances from Combustible Construction Clearance from Combustible ConstructionCombustion Air Through Ducts Openings Table a Minimum Recommended Combustion AIR SupplyInput Btu/hr Flue Size VentingConventional Negative Draft Venting System Table B Vent Pipe SizesPage Vent Termination from Peaked Roof 10’ or Less from Ridge Venting TerminationInspection of a Masonry Chimney Sidewall Venting Masonry Chimney InstallationVent Damper and Vent Damper Terminal Block Automatic Vent DamperTable D Manifold Pressure GAS Supply GAS Pressure TestTable C GAS ConnectionBtu/hr Distance from Meter In Feet Table F Fittings to Equivalent Straight PipeTable G GAS Connections GAS Piping Install Piping to ControlWrench GAS Manifold Pressure Adjustment ProcedurePilot Checking GAS Supply PressureVenting of Combination Gas Valves Combination GAS ValvesRelief Valve Water Heater Relief Valve Water Flow Switch if EquippedTable J AMP Draw Data Minimum Flow Rate Required to Actuate Flow SwitchLOW Water Cutoff if Equipped TWO Stage Burner Control SystemLocating Temperature Control Temperature AdjustmentTemperature Control Settings Operating Temperature ControlHigh-Fire Offset Temperature Control SensorsInstallation of Remote Sensors Wiring of Remote SensorsAdditional Temperature Controls Outdoor AIR Reset OptionInitial START-UP Blocked Vent and Flame ROLL-OUT/FLAME Interlock SwitchManual Reset High Water Temperature Limit What to do if YOU Smell GAS PRE-START ChecklistInput for Your Safety Read Before Operating Lighting Instructions for Standing Pilot Models F1Lighting Wand Lighting Instructions for Spark Ignition Pilot Models F9/M9 Safety Shutoff Test for Standing Pilot Ignition SystemTo Turn OFF GAS to Appliance Operating Instructions To Turn OFF GAS to Appliance Safety Shutoff Test for Spark Ignition Pilot SystemF9/M9 Intermittent Spark Ignition Pilot Models Intermittent Pilot Spark Ignition System F9/M9Freeze Protection Freeze Protection for a HeatingWater Treatment MaintenanceRemoval of Combustion Chamber Lining or Base Panels Inspection Cleaning ProcedureOuter Air Deflector and HEX Filler Bracket Circulator Pump Requirements GAS Train and ControlsWater Connections Heating Boilers only Piping of the Boiler SystemCirculator Pump Operation Circulator Pump SpecificationsTable L Primary/Secondary Piping of a Single Boiler PRIMARY/SECONDARY Boiler PipingBoiler Flow Rates LOW Temperature Bypass RequirementsThree WAY Valves General Plumbing Rules Table M Minimum Required Flow for Heating BoilerTable N Installation with a Chilled Water SystemWire Gauge Boiler Operating Temperature ControlPower Venter Connection To Terminal Strip Table O Terminal Strip WiringBtu/hr To 7 Grains To 25 Grains Hardness Required Temperature RiseTable P Required Temperature Rise Water Velocity ControlPump Operation Water ChemistrySoftened Water Systems Heat Exchanger Remote Sensor Installation InstructionsThermostat Settings Minimum Pump PerformanceOptional Relief Valve Automatic Vent DampersDo not plug or cap the relief valve discharge Thermal ExpansionCathodic Protection Troubleshooting Guide 90,000 270,000 Btu/hr Models Water Heaters F1 Schematic Diagram F1 Unit Schematic Diagram F9 Unit Schematic Diagram M9 Unit Schematic Diagram F9/M9 Unit Page
Related manuals
Manual 52 pages 63.01 Kb

000 Btu/hr, 000 - 500, RSB-i&s-05, 45, CP-5M-4/08 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.