Lochinvar 45, CP-5M-4/08 Table M Minimum Required Flow for Heating Boiler, General Plumbing Rules

Page 36

TABLE - M

MINIMUM REQUIRED FLOW FOR

HEATING BOILER

Input Btu/hr

GPM Flow

45,000

1.9

75,000

3.1

 

 

90,000

3.7

 

 

135,000

5.6

 

 

180,000

7.4

 

 

215,000

8.9

 

 

260,000

10.7

 

 

315,000

13.0

 

 

360,000

14.9

 

 

399,999

16.5

 

 

500,000

20.7

NOTE:

Minimum flow is based on a 40°F temperature rise across the boiler. Minimum flow may not prove a flow switch installed in the boiler piping. Use care when operating a boiler at or near the minimum recommended flow because conditions unique to the installation (system pressure, operation of multiple zone valves, glycol, variations in flow, etc.,) may result in overheating of the boiler water causing noise or nuisance operation of safety limit controls. Typical heating boiler applications will operate with a 20°F to 30°F temperature rise across the boiler.

TYPICAL HEATING BOILER

INSTALLATIONS

PLACING THE BOILER IN OPERATION

Filling the System: All air must be purged from the system for proper operation. An air scoop and air vent must be located close to the boiler outlet and there should be a minimum distance between the cold water feed and the system purge valve.

1.Close all drain cocks and air vents.

2.Open the makeup water valve and slowly fill the system.

3.If a makeup water pump is employed, adjust the pressure to provide a minimum of 12 psi at the highest point in the system. If a pressure regulator is also installed in the line, it should be adjusted to the same pressure.

4.Close all valves. Purge one circuit at a time as follows:

A.Open one circuit drain valve and let the water drain for at least five minutes. Ensure that there are no air bubbles visible in the water stream before closing the drain valve.

B.Repeat this procedure for each circuit.

5.Open all valves after all circuits have been purged. Make sure there are no system leaks.

NOTE:

Do not use petroleum based stop leak products. All system leaks must be repaired. The constant addition of make-up water can cause damage to the boiler heat exchanger due to scale accumulation. Scale reduces flow and heat transfer, causing overheating of the heat exchanger.

General Plumbing Rules

1.Check all local codes.

2.For serviceability of the boiler, always install unions.

3.Always pipe pressure relief valves to an open drain.

4.Locate system air vents at the highest point of the system.

5.Expansion tank must be installed near the boiler and on the suction side of the pump.

6.Support all water piping.

6.Run the system circulating pump for a minimum of 30 minutes with the boiler turned off.

7.Open all strainers in the system and check for debris.

8.Recheck all air vents as described in step 4, General Plumbing Rules.

9.Inspect the liquid level in the expansion tank. The system must be full and under normal operating pressure to ensure proper water level in the expansion tank. Ensure that diaphragm type expansion tanks are properly charged and not water logged.

36

Image 36
Contents Warranty Special Instructions to OwnerChecking Equipment Contents User Warning Installation Procedure CodesLocation of Unit Clearance from Combustible Construction Clearances from Combustible ConstructionCombustion Air Through Ducts Table a Minimum Recommended Combustion AIR Supply OpeningsVenting Conventional Negative Draft Venting SystemTable B Vent Pipe Sizes Input Btu/hr Flue SizePage Venting Termination Vent Termination from Peaked Roof 10’ or Less from RidgeSidewall Venting Masonry Chimney Installation Inspection of a Masonry ChimneyAutomatic Vent Damper Vent Damper and Vent Damper Terminal BlockGAS Supply GAS Pressure Test Table CGAS Connection Table D Manifold PressureTable F Fittings to Equivalent Straight Pipe Table G GAS ConnectionsBtu/hr Distance from Meter In Feet Install Piping to Control GAS PipingGAS Manifold Pressure Adjustment Procedure WrenchChecking GAS Supply Pressure PilotCombination GAS Valves Venting of Combination Gas ValvesRelief Valve Water Flow Switch if Equipped Relief Valve Water HeaterMinimum Flow Rate Required to Actuate Flow Switch LOW Water Cutoff if EquippedTWO Stage Burner Control System Table J AMP Draw DataTemperature Adjustment Temperature Control SettingsOperating Temperature Control Locating Temperature ControlTemperature Control Sensors Installation of Remote SensorsWiring of Remote Sensors High-Fire OffsetOutdoor AIR Reset Option Additional Temperature ControlsBlocked Vent and Flame ROLL-OUT/FLAME Interlock Switch Manual Reset High Water Temperature LimitInitial START-UP PRE-START Checklist Input for Your Safety Read Before OperatingLighting Instructions for Standing Pilot Models F1 What to do if YOU Smell GASLighting Wand Safety Shutoff Test for Standing Pilot Ignition System To Turn OFF GAS to ApplianceLighting Instructions for Spark Ignition Pilot Models F9/M9 Safety Shutoff Test for Spark Ignition Pilot System Operating Instructions To Turn OFF GAS to ApplianceIntermittent Pilot Spark Ignition System F9/M9 Freeze ProtectionFreeze Protection for a Heating F9/M9 Intermittent Spark Ignition Pilot ModelsMaintenance Water TreatmentInspection Cleaning Procedure Removal of Combustion Chamber Lining or Base PanelsOuter Air Deflector and HEX Filler Bracket GAS Train and Controls Water Connections Heating Boilers onlyPiping of the Boiler System Circulator Pump RequirementsCirculator Pump Specifications Table LCirculator Pump Operation PRIMARY/SECONDARY Boiler Piping Primary/Secondary Piping of a Single BoilerLOW Temperature Bypass Requirements Three WAY ValvesBoiler Flow Rates Table M Minimum Required Flow for Heating Boiler General Plumbing RulesInstallation with a Chilled Water System Table NBoiler Operating Temperature Control Power Venter Connection To Terminal StripTable O Terminal Strip Wiring Wire GaugeRequired Temperature Rise Table P Required Temperature RiseWater Velocity Control Btu/hr To 7 Grains To 25 Grains HardnessWater Chemistry Softened Water SystemsPump Operation Remote Sensor Installation Instructions Thermostat SettingsMinimum Pump Performance Heat ExchangerAutomatic Vent Dampers Optional Relief ValveThermal Expansion Cathodic ProtectionDo not plug or cap the relief valve discharge Troubleshooting Guide 90,000 270,000 Btu/hr Models Water Heaters F1 Schematic Diagram F1 Unit Schematic Diagram F9 Unit Schematic Diagram M9 Unit Schematic Diagram F9/M9 Unit Page
Related manuals
Manual 52 pages 63.01 Kb

000 Btu/hr, 000 - 500, RSB-i&s-05, 45, CP-5M-4/08 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.