Lochinvar 000 Btu/hr, CP-5M-4/08, 45, RSB-i&s-05, 000 - 500 Clearance from Combustible Construction

Page 4

CLEARANCE FROM

COMBUSTIBLE CONSTRUCTION

Clearances from Combustible Construction:

Right Side - 6" Rear - 6"

Left Side - 18" (24" suggested for service) Front - 18" (24" suggested for service) Top - (measured from the top of the unit)

45,000 - 180,000 Btu/hr Models - 14"

199,999 - 500,000 Btu/hr Models - 29"

All units have been approved for alcove installation (an ALCOVE is a closet enclosure without a front door).

The boiler must not be installed on carpeting.

All units have been approved for use on combustible surfaces.

Allow sufficient space for servicing pipe connections, pump and other auxiliary equipment, as well as the appliance.

 

14"

6"

6"

 

 

18"

 

18"

FIG. 3 Clearances Models 45,000 - 180,000 Btu/hr

29"

6"

6"

18"

18"

FIG. 4 Clearances Models 199,999 - 500,000 Btu/hr

COMBUSTION AND VENTILATION AIR

REQUIREMENTS FOR

CONVENTIONALLY VENTED

APPLIANCES

Provisions for combustion and ventilation air must be in accordance with Section 5.3, Air for Combustion and Ventilation, of the latest edition of the National Fuel Gas Code, ANSI Z223.1, in Canada, the latest edition of CGA Standard B149 Installation Code for Gas Burning Appliances and Equipment, or applicable provisions of the local building codes.

The room where the appliance is installed MUST be provided with properly sized openings to assure adequate combustion air and proper ventilation when the appliance is installed with conventional venting.

4

Image 4
Contents Special Instructions to Owner WarrantyChecking Equipment Contents User Warning Codes Installation ProcedureLocation of Unit Clearance from Combustible Construction Clearances from Combustible ConstructionCombustion Air Through Ducts Table a Minimum Recommended Combustion AIR Supply OpeningsVenting Conventional Negative Draft Venting SystemTable B Vent Pipe Sizes Input Btu/hr Flue SizePage Venting Termination Vent Termination from Peaked Roof 10’ or Less from RidgeSidewall Venting Masonry Chimney Installation Inspection of a Masonry ChimneyAutomatic Vent Damper Vent Damper and Vent Damper Terminal BlockGAS Supply GAS Pressure Test Table CGAS Connection Table D Manifold PressureTable G GAS Connections Table F Fittings to Equivalent Straight PipeBtu/hr Distance from Meter In Feet Install Piping to Control GAS PipingGAS Manifold Pressure Adjustment Procedure WrenchChecking GAS Supply Pressure PilotCombination GAS Valves Venting of Combination Gas ValvesRelief Valve Water Flow Switch if Equipped Relief Valve Water HeaterMinimum Flow Rate Required to Actuate Flow Switch LOW Water Cutoff if EquippedTWO Stage Burner Control System Table J AMP Draw DataTemperature Adjustment Temperature Control SettingsOperating Temperature Control Locating Temperature ControlTemperature Control Sensors Installation of Remote SensorsWiring of Remote Sensors High-Fire OffsetOutdoor AIR Reset Option Additional Temperature ControlsManual Reset High Water Temperature Limit Blocked Vent and Flame ROLL-OUT/FLAME Interlock SwitchInitial START-UP PRE-START Checklist Input for Your Safety Read Before OperatingLighting Instructions for Standing Pilot Models F1 What to do if YOU Smell GASLighting Wand To Turn OFF GAS to Appliance Safety Shutoff Test for Standing Pilot Ignition SystemLighting Instructions for Spark Ignition Pilot Models F9/M9 Safety Shutoff Test for Spark Ignition Pilot System Operating Instructions To Turn OFF GAS to ApplianceIntermittent Pilot Spark Ignition System F9/M9 Freeze ProtectionFreeze Protection for a Heating F9/M9 Intermittent Spark Ignition Pilot ModelsMaintenance Water TreatmentInspection Cleaning Procedure Removal of Combustion Chamber Lining or Base PanelsOuter Air Deflector and HEX Filler Bracket GAS Train and Controls Water Connections Heating Boilers onlyPiping of the Boiler System Circulator Pump RequirementsTable L Circulator Pump SpecificationsCirculator Pump Operation PRIMARY/SECONDARY Boiler Piping Primary/Secondary Piping of a Single BoilerThree WAY Valves LOW Temperature Bypass RequirementsBoiler Flow Rates Table M Minimum Required Flow for Heating Boiler General Plumbing RulesInstallation with a Chilled Water System Table NBoiler Operating Temperature Control Power Venter Connection To Terminal StripTable O Terminal Strip Wiring Wire GaugeRequired Temperature Rise Table P Required Temperature RiseWater Velocity Control Btu/hr To 7 Grains To 25 Grains HardnessSoftened Water Systems Water ChemistryPump Operation Remote Sensor Installation Instructions Thermostat SettingsMinimum Pump Performance Heat ExchangerAutomatic Vent Dampers Optional Relief ValveCathodic Protection Thermal ExpansionDo not plug or cap the relief valve discharge Troubleshooting Guide 90,000 270,000 Btu/hr Models Water Heaters F1 Schematic Diagram F1 Unit Schematic Diagram F9 Unit Schematic Diagram M9 Unit Schematic Diagram F9/M9 Unit Page
Related manuals
Manual 52 pages 63.01 Kb

000 Btu/hr, 000 - 500, RSB-i&s-05, 45, CP-5M-4/08 specifications

The Lochinvar 000 BTU/hr, 45,000 - 260 is a high-efficiency water heater designed for residential and commercial applications, showcasing advanced technologies that set it apart in the industry. With a powerful heating capacity of up to 260,000 BTU/hr, this unit is engineered to meet the varying demands of hot water for both large households and businesses.

One of the standout features of the Lochinvar 000 is its innovative design that maximizes energy efficiency. Utilizing condensing technology, this water heater captures and reuses exhaust gases that would otherwise be lost, thereby improving thermal efficiency significantly. The result is an impressive Energy Factor (EF) rating that not only promotes sustainability but also translates into lower energy bills for the end user.

The unit is equipped with a user-friendly digital control interface that simplifies operation and monitoring. This control system allows for precise temperature adjustments, ensuring that users can maintain their desired water temperatures effortlessly. Additionally, the advanced diagnostics provided by the control system help in troubleshooting potential issues before they develop into more significant problems, enhancing the reliability of the unit.

Durability is another hallmark of the Lochinvar 000. Constructed with high-quality materials, including a robust stainless-steel tank, this water heater is designed to withstand the rigors of daily use. The stainless-steel construction also helps to resist corrosion, which is a common issue in water heaters, thereby extending the lifespan of the unit.

Furthermore, Lochinvar has integrated safety features into the design of the 000 model, including an automatic shut-off system and advanced flame safeguard controls to prevent hazardous situations. This focus on safety ensures peace of mind for users, making it an ideal choice for family homes and workplaces alike.

In terms of installation, the Lochinvar 000 is relatively straightforward, with options for both indoor and outdoor setups. The compact design allows for flexible installation, accommodating various space requirements without compromising performance.

Overall, the Lochinvar 000 BTU/hr, 45,000 - 260 combines reliability, efficiency, and advanced technology, making it a superior choice for those seeking a powerful and dependable water heating solution. This water heater not only meets but exceeds modern expectations for performance and safety, catering to a wide range of hot water needs.