Lochinvar 150 - 500 Troubleshooting, Check control module fuses, Before troubleshooting

Page 21

Service Manual

3Troubleshooting

￿WARNING

Label all wires prior to disconnection when servicing controls. Wiring errors can cause improper and dangerous operation. Always disconnect power to the water heater before servicing. Failure to comply could result in severe personal injury, death, or substantial property damage.

Check control module fuses

NOTICE

ALWAYS check control module fuses before

replacing control module or any major

 

 

 

components (blower, etc.). If one of these

 

fuses is blown, it can prevent the control

 

module or other components from

 

operating.

￿WARNING Never jumper (bypass) any device except for momentary testing as

outlined in the Troubleshooting chart. Severe personal injury, death, or substantial property damage can result.

Before troubleshooting:

1.Have the following items:

a.Voltmeter that can check 120 VAC, 24 VAC, and 12 VDC.

b.Continuity checker.

c.Contact thermometer.

2.Check for 120 VAC (minimum 102 VAC to maximum 132 VAC) to water heater.

3.Make sure thermostat is calling for heat and contacts (including appropriate zone controls) are closed. Check for 24 VAC between thermostat wire nuts and ground.

4.Make sure all external limit controls are installed and operating.

Check the following:

1.Wire connectors to control module are securely plugged in at the module and originating control.

2.Gas pressures:

Maximum: 14 inches w.c. (natural and LP) with no flow (lockup) or with water heater on

Minimum: 4 inches w.c. (natural), 8 inches w.c. (LP) with gas flowing (verify during water heater startup)

1.Turn OFF power to the water heater at the external line switch.

2.Remove top access cover.

3.Remove the control module cover.

4.Inspect fuses F2, F3, F4, and F5, see FIG 3-1 below.

Figure 3-1Control Module Fuses

F3 - 1.25 AMP FUSE

MAIN BOARD

F4 - 3.15 AMP FUSE

GAS VALVE

F5 - 5 AMP FUSE

PUMPS

F2 - 3.15 AMP FUSE

24V SUPPLY

5.The water heater is shipped with three (3) spare fuses in a plastic bag attached to the control module cover.

6.If necessary, replace open fuse (F3 is 1.25 amps, F2 and F4 are 3.15 amps, and F5 is 5 amps).

Note: Fuses F2 - F5 are all slow blow fuses.

￿WARNING Do not jumper fuse or replace with any fuse except as specified. Failure to comply could

result in severe personal injury, death, or substantial property damage.

7.Install control module cover and top access cover after fuse inspection.

8.Restore power to the water heater at the external line switch and verify water heater operation (Section 10 - Start-up in the Armor Water Heater Installation and Operation Manual) after completing water heater service.

21

Image 21
Contents Models 150 Contents Please read before proceeding Handling ceramic fiber materialsNiosh stated First Aid Service What is in this manual?Maintenance TroubleshootingArmor water heater display ServiceControl inputs Control outputs How the water heater operates General OperationSequence of operation Saving parametersSequence of operation Use this procedure to access menus from the display panel Display panel menu accessButton Operation Display Comments Display panel parameter accessWHR Parameter tableNot used Data logging Viewable and changeable control parametersWHR settings FunctionsNot used Control modes Circulation pumps Service NotificationMaintenance Maintenance and annual startup Service technicianOwner maintenance Maintenance Check water system Flue vent system and air pipingCheck expansion tank Check water heater relief valveCheck all water heater wiring Check ignition ground wiringCheck control settings Perform start-up and checksCleaning water heater heat exchanger Check flame signalReview with owner Oiled bearing circulatorsBefore troubleshooting TroubleshootingCheck control module fuses Check the followingNo Burner No DisplayOperation Unit Does NotTemperature F Resistance Ω Checking temperature sensorsNo Pump Noisy OperationRelief Valve OpeningFlame Flow SwitchSequence GV/RelayNo Flame Ign Running No FlameHigh Limit Manual ResetFan Low Fan Speed LowFan Speed High Fan HighSensor Open Sensor ShortedRem Ctrl Flt ParametersProgr Watch Dog Error Service BlkNo Error Stored Low 24 VACGas Valve Adjustment Combustion Analysis ProcedureOr Obstruction Gas Supply PressureGas valve adjustment procedure Models 150Model Page

150 - 500 specifications

Lochinvar has established itself as a leader in the field of hydronic heating solutions, and the Lochinvar 150 - 500 series is a prime example of its commitment to innovation and efficiency. Designed primarily for commercial applications, this line of high-efficiency boilers is engineered to provide optimized performance, reliability, and cost-effectiveness.

One of the standout features of the Lochinvar 150 - 500 series is its robust construction. Built with a durable stainless-steel heat exchanger, these boilers offer superior resistance to corrosion, ensuring a longer lifespan and consistent performance over time. The advanced design of the heat exchanger also maximizes heat transfer, contributing to higher efficiency ratings.

In terms of technology, the Lochinvar 150 - 500 series incorporates the Concentric Venting System, which allows for flexible installation options and reduces the overall footprint required for the boiler setup. This system is particularly advantageous in commercial settings where space can be limited. The boilers are equipped with smart controls that provide real-time monitoring and diagnostics, allowing for easier maintenance and reducing downtime.

The series features a comprehensive modulation range, allowing the boilers to adjust their output based on the heating demand. This capability not only enhances efficiency but also lowers energy consumption, making it an eco-friendly choice for businesses seeking to reduce their environmental impact. The Lochinvar 150 - 500 boilers utilize innovative combustion technologies, including an integrated burner that ensures optimal combustion efficiency and reduced emissions.

Safety is a priority with the Lochinvar 150 - 500 series, which includes multiple safety features such as lockout protection, pressure switches, and high-temperature limit controls. These measures ensure that the unit operates safely under varying conditions, providing peace of mind for operators.

Additionally, the compact design of the Lochinvar 150 - 500 series allows for easy transportation and installation. Its lightweight structure enables it to be maneuvered through tight spaces typically found in commercial buildings, making it a versatile option for installers.

In summary, the Lochinvar 150 - 500 series is an excellent choice for anyone seeking a reliable, efficient, and technologically advanced boiler solution. With its durable construction, advanced features, and commitment to safety and efficiency, this series stands out as a trusted option in the competitive market of hydronic heating systems.