Raypak 902B, 302B Suggested Minimum Maintenance Schedule, Preventive Maintenance Schedule

Page 52

MAINTENANCE

Suggested Minimum

Maintenance Schedule

Regular service by a qualified service agency and maintenance must be performed to ensure maximum operating efficiency.

Maintenance as outlined below may be performed by the owner.

Daily

1.Check that the area where the heater is installed is free from combustible materials, gasoline, and other flammable vapors and liquids.

2.Check for and remove any obstruction to the flow of combustion or ventilation air to heater.

Monthly

1.Check for piping leaks around circulators, mixing valves, relief valves, and other fittings. If found, repair at once. DO NOT use petroleum-based stop-leak compounds.

2.Visually inspect burner flame.

3.Visually inspect venting system for proper func- tion, deterioration or leakage.

4.Check air vents for leakage.

Yearly (Beginning Of Each Heating Season)

Schedule annual service call by qualified service agency.

1.Visually check top of vent for soot. Call service person to clean. Some sediment at bottom of vent is normal.

2.Visually inspect venting system for proper func- tion, deterioration or leakage.

3.Check that area is free from combustible materi- als, gasoline, and other flammable vapors and liquids.

4.Check for and remove any obstruction to the flow of combustion or ventilation air to heater.

5.Follow pre-start-up check in the Start-up section.

6.Visually inspect burner flame. It should be light blue. Remove and visually inspect hot surface ig- niter and sensor for damage, cracking or debris build-up.

7.Check operation of safety devices. Refer to manu- facturers’ instructions.

8.Follow oil-lubricating instructions on circulator if required. Over-oiling will damage circulator. Water-lubricated circulators do not need oiling.

9.To avoid potential of severe burn, DO NOT REST HANDS ON OR GRASP PIPES. Use a light touch; return piping will heat up quickly.

10.Check blower and blower motor.

11.Check for piping leaks around circulators, relief valves and other fittings. Repair, if found. DO NOT use petroleum-based stop-leak.

12.Clean air filter.

Periodically

1.Check relief valve. Refer to manufacturer’s in- structions on valve.

2.Test low water cut-off, if used. Refer to manufac- turer’s instructions.

3.Clean screen and air filter in intake.

Preventive Maintenance Schedule

The following is required procedure in CSD-1 states and good practice for all Hi Delta installations.

Daily

1.Check gauges, monitors and indicators.

2.Check instrument and equipment settings. (See “Post Start-Up Check” on page 49.)

3.Check burner flame. (Should see light blue flame).

52

Image 52
Contents Installation & Operating Instructions Deletions None Contents Pay Attention to These Terms Before Installation Installations at ElevationProduct Receipt Model IdentificationComponent Locations Component Locations BackGeneral Information Time/Temperature Relationships in Scalds General SafetyWater Time to Produce Serious Temp Burn Installation Installation CodesEquipment Base StackingOutdoor Installations Indoor InstallationsClearances Ft 91 cm within a Combustion and Ventilation Air Indoor UnitsReversing Air Filter Direct VentInstallations Conventional Combustion Air SupplyTruSeal Combustion Air All Air from Inside the BuildingCanadian Installations Water PipingGeneral Reversing Water ConnectionsRelief Valve Piping Hydrostatic Test Cold Water OperationTemperature & Pressure Gauge Hydronic HeatingPump Selection Cold Water StartsPressure Drop in Feet of Head Feedwater Regulator PipingAir-Separation/Expansion Tank Three-Way ValvesPotable Water and Space Heating Pool HeatingAutomatic Chlorinators and Chemical Feeders Winterizing Your HeaterPool/Spa Water Chemistry Water HardnessPH of Water Total Dissolved SolidsGas Supply Gas Supply ConnectionModel Table K Maximum Equivalent Pipe LengthGas Supply Pressure Electrical Power ConnectionsField-Connected Controllers Check the Power Source Field Wiring ConnectionMaking the Electrical Connections Stage Tankstat Venting Flue Exhaust TeeModel Diameter Order Number Appliance CategoriesSupport of Vent Stack Vent Terminal LocationCanadian Installations InstallationsChanging the Flue Outlet Venting Installation Tips Venting ConfigurationsInstallation Natural Draft Vertical Venting CategoryTermination Common Venting SystemCertified Vertical Venting Combustion Air Air Inlet HeightHorizontal Through-the-Wall Venting Category Horizontal Through-the-Wall Venting CategoryDirect Vent Horizontal Through- the-Wall Model Certified Maximum Combustion Air InletVenting EquivalentDirect Vent Vertical Direct Vent VerticalControls Outdoor InstallationFreeze Protection Heater Sequence of Operation Models 302B-902BExternal Lights Color Indication Ignition Module Code ConditionHigh Limit Manual Reset Flow SwitchHigh and Low Gas Pressure Switches Low Water Cut-Off OptionalUDB Fault History UDB Diagnostic BoardPump Time Delay Table R UDB Fault Messages 87%-Efficiency Boilers Special Instructions Water PipingVenting Appliance Categories Model 10F 20F 30F Min. Flow Max Flow GpmVent Terminal Location Vertical Venting CategoryCondensate Management Certified Maximum Combustion Air Air Inlet Model Venting 752BE Combustion Air 902BE 30’ 80’Direct Vent Horizontal Through- the-Wall ABS Cpvc Wiring Diagram START-UP Pre Start-upMain Burner Adjustment Blower AdjustmentStart-Up Safety Inspection Leak Test Procedure Dual-Seat Gas ValvesFollow-Up Pilot Turn-Down TestPost Start-Up Check Leak TestLighting Instructions OperationTo Turn Off Gas To Appliance Troubleshooting StepSuggested Minimum Maintenance Schedule MaintenancePreventive Maintenance Schedule Weekly Semi-AnnuallyAnnually As RequiredAppendix Inside Air ContaminationLimited Parts Warranty HI Delta Types H and WH Limited Parts Warranty HI Delta Type P START-UP Checklist for FAN-ASSISTED Raypak Products Important Instructions for the Commonwealth of Massachusetts
Related manuals
Manual 2 pages 32.1 Kb

302B, 902B specifications

Raypak is a prominent name in the heating industry, particularly known for its advanced technology and robust design in residential and commercial heating solutions. Two of their notable models, the Raypak 302B and 402B, exemplify innovation and efficiency in hydronic heating systems, designed to meet diverse needs while ensuring optimal performance.

The Raypak 302B and 402B are high-efficiency boilers that utilize gas-fueled systems. The 302B model has a heating capacity of 302,000 BTU/h, while the 402B boasts a maximum capacity of 402,000 BTU/h. This range of heating output makes these models suitable for a variety of applications, from residential heating needs to larger commercial spaces that require a reliable heat source.

One of the standout features of the Raypak 302B and 402B is their use of fire-tube heat exchanger technology. This design promotes efficient heat transfer and allows for lower emissions, thus minimizing the environmental impact. The fire-tube design also contributes to a longer lifespan and reduced maintenance costs, making these boilers a cost-effective solution over time.

Equipped with advanced control systems, the Raypak 302B and 402B ensure precise temperature regulation and improved energy usage. The digital display provides real-time feedback and diagnostics, enhancing user experience and simplifying troubleshooting. These models are also compatible with various building management systems, providing users with versatility in integration to optimize building performance.

In addition to their technological advancements, these boilers are designed with user safety and convenience in mind. They include features such as built-in safety controls, easy access for service and maintenance, and a compact footprint to fit into tight spaces. Their robust construction ensures durability, which is crucial for systems that operate under high demand.

Moreover, both models have been engineered to succeed in various climates, making them reliable choices for users in diverse geographical locations. With their energy-efficient operation, reliable performance, and advanced features, the Raypak 302B and 402B embody quality and innovation in the heating market, ensuring comfortable environments while lowering energy costs and environmental footprints.