Raypak 0133-4001 WH, NH manual After START-UP, Inspection Procedures Burners, Controls

Page 33

FOR MODELS WITH AUTOMATIC GAS VALVES

1.Close all gas valves. Turn off electric power supply. Wait five (5) minutes.

2.Open manual pilot valve. Turn on electric power. Pilot is automatically lighted.

3.Open main gas valve.

4.Set temperature controls to desired temperature.

TO SHUT DOWN

Close all manual gas valves. Turn off electric power.

PILOT SHUT-OFF VALVE CONTROL SHOWN IN "ON"

POSITION

GAS INLET

TO PILOT

 

MAIN GAS

 

SHUT-OFF

 

VALVE

 

SHOWN IN

 

THE "ON"

Fig# 8220

POSITION

AFTER START-UP

INTERMITTENT PILOT SYSTEM CHECKOUT PROCEDURE (S8600)

1.Turn on power to the ignition systems and turn gas supply off.

2.Check ignition module as follows:

a.Set the thermostat or controller above room temperature to call for heat.

b.Watch for continuous spark at the pilot burner.

c.Time the spark operation. Time must be within the lockout timing period (15 or 90 seconds).

d.Turn thermostat down to end call for heat and wait 60 seconds on lockout models before beginning step 3.

3.Turn on gas supply.

4.Set thermostat or controller above room temp- erature to call for heat.

5.Systems should start as follows:

a.Spark will turn on and pilot gas valve will open at once. Pilot burner should ignite after gas reaches the pilot burner.

b.Spark ignition should cut-off when pilot flame is established.

c.Main gas valve should open and main burner should ignite after gas reaches the burner port.

INSPECTION PROCEDURES

BURNERS

Clean main burners and air louvers free of dust, lint and debris. Keep heater area clear and free from combustibles and flammable liquids. Do not obstruct the flow of combustion and ventilation air. Make visual check of burner and pilot flame. Yellow flame indicates clogging of air openings. Lifting or blowing flame indi- cates excessively high gas pressure. Low flame indi- cates low gas pressure.

Fig# 8144

TYPICAL MAIN BURNER FLAME (Atmospheric models)

NOTE: Modulating burner flame varies in height from approximately 1/4" at low fire to approximately 4" at high fire.

CONTROLS

Check all controls to see that they are operational. To check electronic safety (IID models), turn off main burner. Observe pilot burner when shutting off pilot gas. Ignition spark should go on. Main gas valve will also drop out.

High Limit Switch - to check high limit switch, turn dial setting down to a point slightly below the tempera- ture of the water leaving the heater. The reset button should snap out and the burner should shut-off. Reset dial to 30°F to 40°F above desired operating tempera- ture and push reset button. Burner should light.

33

Image 33
Contents For Your Safety Installation Operating InstructionsTable of Contents Receiving Equipment ALL Models Approved General SpecificationsModel Identification HOT Water Supply HeatersGeneral Safety Precautions Installation Codes Installation InstructionsClearances Model Specifications and DimensionsModels Models High Wind Conditions Outdoor Units Only Outdoor Water HeatersVenting Outdoor InstallationsBefore After Installation Drafthood Indoor InstallationsVent TERMINAL/INDOOR Stack Installation Fig. #7043.1 Vent PipingModels 133 Through 261 Where Required Location Vent Damper InstallationVent Damper Plumbing GeneralGAS Supply Connections Venting of Diaphragm GAS Components GAS Pressure RegulatorFlow Rates Piping Domestic HOT Water Supply Heaters General Specifications UNI-TEMP 80 HOT Water Supply SystemsPiping Diagrams Type WH Unitemp 80 System Type NH Instantaneous Type NH Dual Models Minimum Input AdjustmentRelief Valve Controls GeneralElectronic Ignition Economaster Control100% Pilot Safety Flow SwitchHigh and LOW GAS Pressure Switches Optional Limit Controls High LimitComponent Identification Electrical Connections SINGLE-STAGE TankstatON/OFF Units Location of Controls 400 WH1, WH2, WH3 LOW NOx WH1Fig. #9334 Initial START-UP Pump and Motor START-UP Procedures Before START-UPScalding TIME/TEMPERATURE Relationships in ScaldsOperating Instructions For Your Safety Read Before OperatingTo Turn OFF GAS to Appliance For Models with Manual GAS ValvesAfter START-UP Inspection Procedures BurnersControls For Models with Automatic GAS ValvesInspection Procedures High GAS Pressure Switch Burner AdjustmentSTART-UP Procedures Visual InspectionPilot Removal Burner Tray RemovalGAS Valve Removal Main Burner and Orifice RemovalHoneywell S8600 Troubleshooting ElectricalWiring Diagrams Wiring Diagram WH2 182/260 Wiring Diagram WH2 330/400 Wiring Diagram WH2 514/624 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH1 181/261 LOW NOx Wiring Diagram WH1 331/401 LOW NOx Mechanical Problem Possible Cause Corrective Action TroubleshootingTroubleshooting Pumps Service and Maintenance ProceduresTube Cleaning High Limit or Tankstat Removal Pilot Removal and CleaningHeat Exchanger Removal Typical Burner Tray IllustratedHeat Exchanger RE-ASSEMBLY Control Well ReplacementTube Replacement Cleaning Flue GAS Passageways Replacement PartsCatalog Model Number Scope Warranty