Raypak 0133-4001 WH, NH manual Troubleshooting, Mechanical Problem Possible Cause Corrective Action

Page 47

TROUBLESHOOTING

MECHANICAL PROBLEM

POSSIBLE CAUSE

CORRECTIVE ACTION

 

 

 

When heater is turned on nothing

No power to the heater………………….

Check the circuit breaker, outdoor con-

happens.

 

troller, etc., upstream of heater.

 

Bad transformer………………………….

If power to Leads L1 and L2 of trans-

 

 

former, but no power on 24V side, re-

 

 

place.

 

Inoperative thermostat…………………..

Jumper thermostat, replace with new if

 

 

heater fires.

 

Inoperative toggle switch………………..

If power to toggle switch, but not through

 

 

switch, replace.

 

Inoperative relay…………………………. If power to relay, but not operating, re-

 

 

place.

 

 

 

Thermostat in "ON" position causes relay and pump to operate, but heater does not fire.

Main gas valve closed………………...... Open valve.

Plugged bleed line on gas valve or

gas pressure regulator………………….. Loosen bleed line and clean.

Broken pump coupler…………………… Replace coupler. Inspect bearing as-

sembly, and if frozen, lubricate or re- place.

Shutdown by low water cut-off,

caused by air…………………………….. Bleed air from system.

Gas valve defective…………………….. Check for power to gas valve. If valve has

power but will not open, check vent tube for blockage. If clear, replace valve.

Continuous shut down of manual

Temperature setting too low…………….

Reset High Limit to higher temperature.

reset High Limit.

Low water flow……………………………

Check system water pumps.

 

Interrupted pump operation……………..

Check pump oil if necessary.

 

Modulating control set too high………..

Reset modulator to a lower setting.

 

Mechanical modulating control…………

Check and replace if necessary.

 

 

 

Sooting

Air starvation……………………………..

CAUTION-Soot may be combus-

Condensation…………………………….

tible. Wet down and exercise

caution when cleaning.

Toxic fumes which cause a chemical

 

reaction with copper tubes or destroy

 

combustion……………………………….

 

Improper venting…………………………

Refer to installation instructions regard- ing combustion air requirements.

Set bypass valve to prevent heater inlet temperature from dropping below 105° F.

Remove all sources of fumes, such as freon or chloride, or isolate the heater. Follow recommended vent installation instructions.

Continuous shut down of low water

Insufficient system flow………………….

Check pumps and piping.

cut-off or flow switch.

Low water due to leaking………………..

Inspect for leaking and repair.

 

Air in system……………………………...

Inspect for leakage and repair. Install an

 

 

automatic air vent.

 

Line strainer dirty…………………………

Clean.

 

Lime in Heat Exchanger…………………

Ream tubes.

 

 

 

Low flame.

Outer jacket very hot (blistered paint)

Combustion fan not running. (If applicable)

Low gas supply………………………….. Debris in gas line (pipe dope, rocks, etc.).

Gas line too small. Improper size gas meter. Gas regulator adjustment.

Insects or debris clogging………………. Clean burners.

Burner intake ports low gas pressure…. Adjust gas pressure.

Venting or combustion air………………. Refer to installation instructions regard-

 

ing combustion air requirement.

Broken refractory…..…………………….

Replace refractory panels.

Fan relay

Replace fan relay.

Fan

Loose wire connection.

 

Failed fan motor.

47

Image 47
Contents For Your Safety Installation Operating InstructionsTable of Contents HOT Water Supply Heaters General SpecificationsReceiving Equipment ALL Models Approved Model IdentificationGeneral Safety Precautions Installation Codes Installation InstructionsClearances Model Specifications and DimensionsModels Models High Wind Conditions Outdoor Units Only Outdoor Water HeatersVenting Outdoor InstallationsBefore After Installation Drafthood Indoor InstallationsVent TERMINAL/INDOOR Stack Installation Fig. #7043.1 Vent PipingModels 133 Through 261 Where Required Location Vent Damper InstallationVent Damper GAS Supply Connections PlumbingGeneral Venting of Diaphragm GAS Components GAS Pressure RegulatorFlow Rates Piping Domestic HOT Water Supply Heaters General Specifications UNI-TEMP 80 HOT Water Supply SystemsPiping Diagrams Type WH Unitemp 80 System Type NH Instantaneous Type NH Dual Models Minimum Input AdjustmentEconomaster Control Controls GeneralRelief Valve Electronic IgnitionLimit Controls High Limit Flow Switch100% Pilot Safety High and LOW GAS Pressure Switches OptionalComponent Identification ON/OFF Units Electrical ConnectionsSINGLE-STAGE Tankstat Location of Controls 400 WH1, WH2, WH3 LOW NOx WH1Fig. #9334 Initial START-UP Pump and Motor START-UP Procedures Before START-UPScalding TIME/TEMPERATURE Relationships in ScaldsFor Models with Manual GAS Valves For Your Safety Read Before OperatingOperating Instructions To Turn OFF GAS to ApplianceFor Models with Automatic GAS Valves Inspection Procedures BurnersAfter START-UP ControlsInspection Procedures Visual Inspection Burner AdjustmentHigh GAS Pressure Switch START-UP ProceduresMain Burner and Orifice Removal Burner Tray RemovalPilot Removal GAS Valve RemovalHoneywell S8600 Troubleshooting ElectricalWiring Diagrams Wiring Diagram WH2 182/260 Wiring Diagram WH2 330/400 Wiring Diagram WH2 514/624 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH1 181/261 LOW NOx Wiring Diagram WH1 331/401 LOW NOx Mechanical Problem Possible Cause Corrective Action TroubleshootingTube Cleaning Troubleshooting PumpsService and Maintenance Procedures Typical Burner Tray Illustrated Pilot Removal and CleaningHigh Limit or Tankstat Removal Heat Exchanger RemovalTube Replacement Heat Exchanger RE-ASSEMBLYControl Well Replacement Catalog Model Number Cleaning Flue GAS PassagewaysReplacement Parts Scope Warranty