TROUBLESHOOTING - ELECTRICAL

(ELECTRONIC IGNITION IID)

Intermittent Pilot System

HONEYWELL S8600

WARNING

HIGH VOLTAGE

For qualified Technicians ONLY

NOTE: Some heaters may be equipped with an ignition module that shuts off pilot gas if pilot fails to light. To reset, interrupt power to heater.

START

TURN GAS SUPPLY OFF.

TURN THERMOSTAT

(CONTROLLER) TO CALL

FOR HEAT

POWER TO MODULE

(24 V NOMINAL)?

YES

SPARK ACROSS

IGNITER/SENSOR GAP?

YES

NO

NO

NOTE: Before troubleshooting, familiarize yourself with the start-up and checkout procedure.

Check line voltage power, low voltage transformer, limit controller, thermostat (controller) and wiring.

Pull ignition lead and check spark at module.

If spark is okay:

Check ignition cable, ground wiring, ceramic insulator and gap, and correct.

Check boot of the ignition cable for signs of melting or buckling. Take protective action to shield cable and boot from excessive temperatures.

If not, replace module.

TURN GAS SUPPLY ON PILOT BURNER LIGHTS?

YES

SPARK STOPS WHEN

PILOT IS LIT?

YES

MAIN BURNER LIGHTS?

YES

SYSTEM RUNS UNTIL CALL FOR HEAT ENDS?

YES

NO

 

• Check that all manual gas valves are open, supply tubing and pressures are good,

 

 

 

and pilot burner orifice is not blocked.

 

 

Check electrical connections between module and pilot operator on gas control.

Check for 24 Vac across PV-MV/PV terminals on module. If voltage is okay, replace gas control; if not, replace module.

 

 

NOTE: If S8600H goes into lockout, reset system. Lockout is used on propane

 

 

models.

NO

 

Check continuity of ignition cable and ground wire.

 

 

 

Clean flame rod.

 

 

Check electrical connections between flame rod and module.

 

 

Check for cracked ceramic flame rod insulator.

 

 

Check that pilot flame covers flame rod and is steady and blue.

 

 

Adjust pilot flame.

 

 

If problem persists, replace module.

 

 

 

 

 

 

Check for 24 Vac across MV-MV/PV terminals. If no voltage, replace module.

NO

 

 

Check electrical connections between module and gas control. If okay, replace

 

 

 

 

gas valve or gas control operator, i.e. pilot gas valve, flow switch etc.

 

 

 

 

NOTE: IF S8600H goes into lockout, reset system.

NO

• Check continuity of ignition cable and ground wire.

 

NOTE: If ground is poor or erratic, shutdowns may occur occasionally even though operation is normal at the time of checkout.

Check that pilot flame covers flame rod and is steady and blue.

If checks are okay, replace module.

CALL FOR HEAT ENDS SYSTEM SHUTS OFF?

YES

NO

Check for proper thermostat (controller) operation.

Remove MILLIVOLT lead at module; if valve closes, recheck temperature controller and wiring; if not, replace gas valve.

TROUBLESHOOTING ENDS

37

Image 37
Contents For Your Safety Installation Operating InstructionsTable of Contents Receiving Equipment ALL Models Approved General SpecificationsModel Identification HOT Water Supply HeatersGeneral Safety Precautions Installation Codes Installation InstructionsClearances Model Specifications and DimensionsModels Models High Wind Conditions Outdoor Units Only Outdoor Water HeatersVenting Outdoor InstallationsBefore After Installation Drafthood Indoor InstallationsVent TERMINAL/INDOOR Stack Installation Fig. #7043.1 Vent PipingModels 133 Through 261 Where Required Location Vent Damper InstallationVent Damper General PlumbingGAS Supply Connections Venting of Diaphragm GAS Components GAS Pressure RegulatorFlow Rates Piping Domestic HOT Water Supply Heaters General Specifications UNI-TEMP 80 HOT Water Supply SystemsPiping Diagrams Type WH Unitemp 80 System Type NH Instantaneous Type NH Dual Models Minimum Input AdjustmentRelief Valve Controls GeneralElectronic Ignition Economaster Control100% Pilot Safety Flow SwitchHigh and LOW GAS Pressure Switches Optional Limit Controls High LimitComponent Identification SINGLE-STAGE Tankstat Electrical ConnectionsON/OFF Units Location of Controls 400 WH1, WH2, WH3 LOW NOx WH1Fig. #9334 Initial START-UP Pump and Motor START-UP Procedures Before START-UPScalding TIME/TEMPERATURE Relationships in ScaldsOperating Instructions For Your Safety Read Before OperatingTo Turn OFF GAS to Appliance For Models with Manual GAS ValvesAfter START-UP Inspection Procedures BurnersControls For Models with Automatic GAS Valves Inspection Procedures High GAS Pressure Switch Burner AdjustmentSTART-UP Procedures Visual InspectionPilot Removal Burner Tray RemovalGAS Valve Removal Main Burner and Orifice RemovalHoneywell S8600 Troubleshooting ElectricalWiring Diagrams Wiring Diagram WH2 182/260 Wiring Diagram WH2 330/400 Wiring Diagram WH2 514/624 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH2 Wiring Diagram WH1 181/261 LOW NOx Wiring Diagram WH1 331/401 LOW NOx Mechanical Problem Possible Cause Corrective Action TroubleshootingService and Maintenance Procedures Troubleshooting PumpsTube Cleaning High Limit or Tankstat Removal Pilot Removal and CleaningHeat Exchanger Removal Typical Burner Tray IllustratedControl Well Replacement Heat Exchanger RE-ASSEMBLYTube Replacement Replacement Parts Cleaning Flue GAS PassagewaysCatalog Model Number Scope Warranty