U-2 Diagnostics Board

The U-2 Diagnostics board is a solid-state electronic fault indicator that has been engineered to enhance safety, simplify troubleshooting and minimize equip- ment down time. The U-2 safety board is the central point for wiring, operations monitoring, and fault indi- cation for the boiler safeties. By having each safety report directly to the U-2 board, each safety function can be individually monitored.

The U-2 adds complete diagnostics features that aid in the rapid diagnosis of irregularities in boiler operation. A single U-2 Diagnostics Board can monitor a maxi- mum of eight safeties at one time. If, due to code requirements, more than eight safety devices must be monitored, two or more boards will be used to provid- ed extended diagnostics capabilities. Advanced Design Boilers equipped with the standard safety suite will utilize the configuration shown in Table T.

The U-2 safety board has a series of red LED lights to indicate a fault occurring at a monitored safety. An

additional light indicates that the diagnostics board is energized and is currently monitoring for safety faults. (In order to prevent spurious alarm conditions, the U-2 board monitors safeties only during the actual firing cycle.)

Once a fault has been detected, the U-2 board will illu- minate the corresponding LED lamp, will shut-down the boiler, and will light the flashing red LED “Service” lamp on the CPW board. If more than one fault is detected, the U-2 board will display the priority fault based on the safety hierarchy as labeled on the U-2 board. Once the first fault is cleared, the second fault lamp will illuminate until cleared.

WARNING: Only qualified persons shall attempt to repair the boiler. Improper adjustment, service or maintenance may damage the equipment, create a hazard resulting in asphyxiation, explosion, fire, electric shock, personal injury or property damage, and will void the warranty.

 

 

 

Light

Color

Indication

System Enabled

Yellow

U-2 Diagnostics safety board is functional.

 

 

 

Manual High Limit

Red

Water temperature is over the manual high limit setting.

Auto High Limit

Red

Water temperature is over the auto high limit setting.

Flow Switch

Red

Water flow rate is too low.

Low Water Cut-off (option)

Red

Insufficient water volume for boiler operation.

High/Low Gas Pressure

Red

Gas supply pressure is below or above the allowed minimum gas supply

 

 

pressure to ensure safe operation.

Burner High Limit

Red

Mixer or PVC vent pipe, if installed, is over heated.

 

 

 

Blower/Ignition Lockout

Red

Blower failure, not enough combustion air or the equipment has an ignition

 

 

lock-out condition.

Blocked Vent

Red

The vent pressure switch has detected a blocked vent.

 

 

 

 

 

 

Table T: U-2 Diagnostic Board LEDs

43

Image 43
Contents Advanced Design Boiler Page Contents Pay Attention to These Terms Model Identification Before InstallationInstallations at Elevation Product ReceiptComponent Locations Component LocationsTime/Temperature Relationships in Scalds General SafetyEquipment Base InstallationInstallation Codes Indoor InstallationsDirect Vent Outdoor InstallationsCombustion and Ventilation Air Indoor UnitsInstallations1 Canadian Installations2 Canadian Installations InstallationsConventional Combustion Air Supply General Low Temperature SystemTemperature & Pressure Gauge Water PipingHydronic Heating Single Boiler Primary/Secondary Piping Dual Boiler Piping Domestic HOT Water Piping Single Boiler Domestic Hot Water with One Storage Tank Page Pool and Spa Water Chemistry Pool HeatingAutomatic Chlorinators and Chemical Feeders Winterizing Your HeaterSingle Boiler Pool Application Double Boiler Pool Application GAS Supply ConnectionsGas Supply Pressure Gas Supply ConnectionElectrical Power Connections Electrical Connections Domestic Hot Water Field Wiring ConnectionsGeneral Definition of Appliance Categories Venting ConnectionsVent Terminal Location Venting Configurations Venting Installation TipsADB-1501 Natural Draft Vertical Vent Termination Natural Draft Vertical Venting System InstallationADB-1501 Horizontal Thru-Wall Direct Venting/Combustion Air Category Horizontal Thru-wall Direct Vent TerminationÁDB-1501 Vertical Direct Venting/Combustion Air Category Vertical Direct Vent Termination Vertical Direct Venting System InstallationContact the manufacturer for details Horizontal Thru-wall Venting System Category IV Installation PVC, ABS Page Galvanized ADB-751 Venting Material e.g Subtract 10 ft per Condensate Trap Alignment Condensate DrainControls Central Point Wiring CPWCPW Board Blower Fan Post-purge Pump Turn-off DelayFreeze Protection Feature Blower Fan Pre-purgeLight Color Indication Diagnostics BoardFigure L-2 Wiring DiagramIgnition Control Module Flow SwitchHigh Limit Manual Reset High Limit Auto ResetFill the System High and Low Gas Pressure Switches Manual ResetPRE-START-UP Low Water Cut Off OptionalBlower T Fitting Detail Pre-Start-up CheckTools Needed ADB Initial START-UPPreparation for Start-up Page Follow-up Main Burner AdjustmentSafety Inspection Post START-UP CheckOperating Instructions MaintenanceSuggested Minimum Maintenance Schedule OperationMonthly Connecting the Condensing Heat Exchanger CHXCleaning Boiler Heating Surfaces DailyConnecting Add-on Condensing Heat Exchanger to ADB Vent Switch AdjustmentInside Combustion Air Contamination AppendixEmissions Settings and Test Information Bluff Head Body Burner Warranty

751 specifications

The Raypak 751 is a high-efficiency, gas-powered pool and spa heater renowned for its advanced technology and durability. Designed with innovative features, the Raypak 751 prioritizes user convenience and energy efficiency, making it an excellent choice for pool owners seeking reliable heating solutions.

One of the standout features of the Raypak 751 is its robust heat exchanger, built from the finest materials to ensure long-lasting performance. This model utilizes a copper heat exchanger which is highly conductive, allowing for rapid heating of water and maintenance of consistent temperatures. Its design also minimizes scale buildup, extending the longevity of the heater.

The Raypak 751 is equipped with advanced digital controls that make it user-friendly. The intuitive interface allows for precise temperature settings and monitoring, ensuring optimal performance. Additionally, the heater features a temperature display that provides real-time updates, giving users peace of mind when adjusting their pool's environment.

Energy efficiency is a hallmark of the Raypak 751, thanks to its low NOx burner technology. This feature meets stringent environmental regulations while also lowering operational costs. By optimizing fuel usage, the heater not only contributes to reducing greenhouse gas emissions but also provides a more economical heating option for pool and spa owners.

The rugged construction of the Raypak 751 is another characteristic that sets it apart. Its heavy-duty cabinet is designed to withstand the elements, ensuring reliable operation in various weather conditions. The heater is available in multiple configurations, including both natural gas and propane options, allowing for flexible installation depending on the user's needs.

Furthermore, the Raypak 751 incorporates safety features, such as an integrated pressure switch that prevents operation when water flow is insufficient. This protects both the heater and associated plumbing from damage due to overheating or dry firing.

In summary, the Raypak 751 combines cutting-edge technology with user-centric features to deliver a superior pool heating experience. Its high-efficiency performance, durable construction, and advanced safety features make it a top choice for anyone looking to enhance their pool or spa. Whether for residential or commercial applications, the Raypak 751 ensures warmth and comfort, enriching the overall swimming experience.