Raypak 500, 750, 1000 installation instructions Vertical Direct Venting System Installation

Page 39

Vertical Direct Venting System Installation

These installations utilize the boiler mounted blower to draw combustion air from outdoors and uses the natural buoyancy of the heated flue products to create a thermal driving head that expels the exhaust gases from the flue. The negative draft must be within the range of 0.01 to 0.08” negative W.C. to insure proper operation. The vent material must be in accor- dance with the above instructions for vent materials. Vent material must be listed by a nationally recognized test agency.

The maximum and minimum venting length for Category I appliance shall be determined per the latest edition of the National Fuel Gas Code (U.S.) and CAN/CGA-B149.1 and .2 Installation Code (Canada).

The diameter of vent flue pipe should be sized according to part 11 of the latest edition of the National Fuel Gas Code (U.S.) and part 7 and Appendix B of CAN/CGA-B149.1 and .2 installation code (Canada). The minimum flue pipe diameter for conventional negative draft venting using double-wall B type vent is 7” for ADB 500, 8" for the ADB 750, and 9" for the ADB 1000.

NOTICE:

Vent Adapter may have to be used to connect B vent to the unit. (For ADB 500, a 6" diameter to 7" diameter adapter is needed).

The connection from the appliance vent to the stack must be as direct as possible and should be the same as or larger than the vent outlet. The vent must be installed to prevent accumulation of condensate and, where necessary, have means provided for drainage of condensate. The horizontal breaching of a vent must have an upward slope of not less than 1/4 inch per linear foot from the boiler to the vent terminal. The horizontal portions of the vent shall also be supported for the design and weight of the material employed to maintain clearances and to prevent physical damage or separation of joints.

Vertical Direct Vent Termination

The vent terminal should be vertical and should terminate outside the building at least two (2) feet above the highest point of the roof within 10 feet. The vent cap should have a minimum clearance of four (4) feet horizontally from and in no case above or below (unless a four (4) foot horizontal distance is maintained) electric meters, gas meters, regulators and relief equipment. The distance of the vent terminal from adjacent public walkways, adjacent buildings, open windows and building openings must be consistent with the National Fuel Gas Code, or in Canada, the latest edition of CAN/CGA-B149.1 and .2. Installation Code for Gas Burning Appliances and Equipment. Gas vents supported only by flashing and extended above the roof more than five feet should be securely guyed or braced to withstand snow and wind loads.

The vertical direct vent cap is designed for roof top mounting only. The air inlet opening MUST be installed one (1) foot above the roof line or above normal snow levels that might obstruct combustion air flow. This dimension is critical to the correct operation of the boiler and venting system and reduces the chance of blockage from snow. The vent cap must have a minimum 3 foot vertical clearance above the air inlet opening.

39

Image 39
Contents For Your Safety What to do if YOU Smell GAS For Your SafetyPage Table of Contents Product Receipt Section a Before Installing the BoilerRatings and Certification ModelidentificationAdvanced Design Boiler Component Locations Figure A-1Section B Boiler Installation Installation CodesEquipment Base Figure B-1 Outdoor Installation Minimum Clearances Direct Combustion AIR Section C Combustion and Ventilation AIRPage Reliefvalve Piping LOW Temperature SystemTemperature & Pressure Gauge Section D Water Piping GeneralPump Selection Section E Hydronic Heating PipingTHREE-WAY Valves Pressure Drop in Feet of Head Feedwater RegulatorPiping Heating Boilers AIR-SEPARATION/EXPANSION TankDUAL-BOILER PRIMARY/SECONDARY Piping Single Boiler PRIMARY/SECONDARY Piping with CHXDual Boiler -PRIMARY/SECONDARY Piping with CHX Figure E-3bSingle Boiler Domestic HOT Water with ONE Storage Tank Section F Domestic HOT Water PipingFigure F-1c Section G Pool Heating Automatic Chlorinators and Chemical FeedersWinterizingyour Heater Spawater Chemistry Single Boiler Pool ApplicationSingle Boiler Pool Application with CHX Double Boiler Pool Application Figure G-3aSection H GAS Supply Connections GAS Supply ConnectionGAS Supply Pressure Regulator Pressure Settings GAS Pressure RegulatorVenting of Diaphragm GAS Components Surge Protection Section I Electrical Power ConnectionsCheck the Power Source Check Power SourceMaking the Electrical Connections Field Wiring ConnectionElectrical Connections Domestic HOT Water General Section J Venting ConnectionsPage Support of Vent Stack Venting Configurations Figure J-1 Natural Draft Vertical Vent Termination Page Heat Exchanger Category Section J-2Page Category Section J-3Page Vertical Direct Venting/Combustion Air Category Section J-4Vertical Direct Venting System Installation Figure J-5 Page Figure J-6 Section J-6Horizontal Thru-wall Venting System Category IV Installation Figure J-7 Page Figure J-8 Page Outdoor Installation withAdd-On Condensing Heat Exchanger Condensate Trap Alignment Section K Condensate DrainCentral Point Wiring CPW Section L ControlsCPW Board Figure L-1 CPW Board Pump Turn-off Delay Manual High Limit Red Figure L-2 Wiring DiagramAuto Reset High Limit High Limit Manual ResetManual Reset High Limit Flow Switch Flow Switch High Limit Auto ResetGAS Pressure Switch LOW Water CUT OFF OptionalPressure Control Device ACU-TRACK TIME/TEMPERATURE Relationships in Scalds Section M General Safety PrecautionsSection N PRE-START-UP Component and Pressure TAP Locations Figure O-1Section O ADB Initial START-UP Tools NeededPreparation for START-UP Do not Turn on GAS AT this Time START-UP Page Section P Post START-UP Check Emissions GuidelinesCO2 Section Q Operation Operating InstructionsTo Turn OFF GAS to Appliance Suggested Minimum Maintenance Schedule Section R MaintenanceCleaning Boiler Heating Surfaces Vent Switch Adjustment Section S Connecting Condensing Heat Exchanger CHXInsidecombustionaircontamination Appendix aPage Page Page Page Page Pressure Settings START-UP SettingsLitho in U. S. a
Related manuals
Manual 8 pages 63.38 Kb Manual 8 pages 12.19 Kb

1000, 750, 500 specifications

Raypak is a renowned name in the heating industry, particularly known for its high-quality pool and spa heaters. Among their extensive product line, the Raypak 850, 500, 300, 400, and 700 models stand out for their reliability, efficiency, and cutting-edge technologies. Each model is designed to cater to different needs and applications while maintaining Raypak’s commitment to performance.

The Raypak 850 is designed for larger commercial pools or residential setups requiring high output. With a powerful heat exchanger made from copper and bronze, it ensures superior heat transfer and longevity. Its digital control system provides precise temperature regulation, enhancing user experience. Moreover, it features a durable construction with weather-resistant materials, ensuring lasting performance in various environments.

The Raypak 500 model offers a balance between efficiency and compactness. It features eco-friendly technology that reduces energy consumption without sacrificing performance. The integrated thermostat allows users to maintain consistent water temperatures, making it ideal for residential pools. This model is well-regarded for its user-friendly digital display, simplifying operation and monitoring.

For those needing a more moderate capacity, the Raypak 300 is an efficient choice. It combines robust engineering with an easy-to-use interface. Its advanced ignition system improves reliability while minimizing energy waste. The Raypak 300’s compact design allows for easy installation in various spaces, making it an excellent option for smaller pools.

The Raypak 400 heats water quickly and efficiently, making it suitable for both residential pools and spas. It features a high-capacity heating system that ensures optimal performance. With a clear LED display, users can easily monitor their settings, while the integrated diagnostics provide real-time feedback for maintenance and troubleshooting.

Lastly, the Raypak 700 model is known for its versatility and robust performance. It is equipped with advanced safety features, including a high limit switch and water flow detection mechanism, to ensure safe operation. The model's energy-efficient design enhances its eco-friendliness, making it a popular choice among environmentally conscious users.

Collectively, these Raypak models exemplify superior engineering, performance, and user-friendliness. Their innovative features ensure that they meet the varied demands of pool owners while providing reliable heating solutions for leisure and relaxation. Whether for commercial or residential use, the Raypak 850, 500, 300, 400, and 700 offer unmatched quality and efficiency.